FT7000, RACK MONITOR MANUAL 11033PA-ATEX
Installation
INSTALLATION TO BE COMPLETED BY A QUALIFIED HAZARDOUS LOCATION TECHNICIAN.
L’INSTALLATION DOIT ÊTRE COMPLÉTÉ PAR UN TECHNICIEN QUALIFIÉ.
The FT7000 Rack monitor in suitable for installation in Class I Division 1/Zone 1 hazardous locations as
defined by NEC NFPA70 and IECEx standard 60079. Installation to be performed by a qualified
professional.
Mechanical
The recommended mounting method is using the included carriage bolts. This method will require that
the back side of the installation surface be accessible. If this mounting method will not work, the
enclosure may be installed using lag bolts, however caution should be taken to ensure the monitor is
securely installed.
1.
Using the bolt pattern provided below, locate a sturdy area, large enough to install the monitor.
Keep in mind the lid hinge will open 180° to the right. Conduit may run to the left, right, and
bottom sides of the monitor. The FT7000 should be positioned vertically at eye level, with
indicators facing the lane, for greatest visibility. The enclosure can withstand rain and sun
exposure, but will last longer when protected from the elements. Using the bypass function will
require the face of the FT7000 to be reachable.
2.
Level the bolt pattern and drill four holes marked on the pattern.