1592016100 XV300K GB r.1.0 03.06.2011.doc XV300K 5/13
5
STANDARD REFERENCES
According to safety directive 2006/95CE, reference standard
EN60730-1
. According to EMC 89/336
reference standard EN 61800-3. With refer to some typical applications, the XV308K, XV312K and
XV320K regulators are suitable for residential and commercial ambient, while the XV328K and XV340K
regulators are suitable for industrial ambient. XV300K regulators are designed to be installed inside a
machine or a standard electrical cabinet and are therefore considered a component.
The installer must
guarantee that the machine conforms to such regulations.
WARNING:
this control does not contain current harmonics filter and it may cause interference, in which
case the user may be required to take adequate measures with refer at
EN 61000-2-4
and
EN 61000-3-12
.
6
MECHANICAL INSTALLATION
The
XV300K
regulator must be mounted to walls vertically, in order to guarantee adequate dispersion of
heat in the heatsink. Avoid positioning it near heat sources and keep out of direct sunlight. The regulator
has covering IP55 but must be protected from sprays of water, oil, corrosive liquids, deposits of metallic
dust and gas. Make sure also that it is not exposed to vibrations. Set the regulator in a ventilated place to
let the heat come out.
Model
Weight
(kg)
Dimensions
(mm)
A B C
Fixing screw
(mm)
D
E F Ø
XV308K
2,5
230
165
150
215
90
/
M4
XV312K
4
230
265
165
215
200
/
M4
XV320K
4,8
230
265
230
165
220
200
/
M4
XV328K
7
340
270
235
322
165
/
M5
XV340K
9
340
270
235
322
165
/
M5