Installing and Operating Instructions 

1592002250

 

 

1592002250 XT151-160D GB R.1.08.03.2005 

XT151D – XT160D 

1/4 

XT151D – XT160D 

Three Four  Stages Digital Controllers  
with Multi Probe Input 

 

 

1.

 

GENERAL WARNING 

1.1

 

PLEASE READ BEFORE USING THIS MANUAL 

 

This manual is part of the product and should be kept near the instrument for easy and quick reference. 

 

The instrument shall not be used for purposes different from those described hereunder. It cannot be 
used as a safety device. 

 

Check the application limits before proceeding. 

1.2

 

 SAFETY PRECAUTIONS 

 

Check the supply voltage is correct before connecting the instrument. 

 

Do not expose to water or moisture: use the controller only within the operating limits avoiding sudden 
temperature changes with high atmospheric humidity to prevent  formation of condensation 

 

Warning: disconnect all electrical connections before any kind of maintenance. 

 

The instrument must not be opened. 

 

In case of failure or faulty operation send the instrument back to the distributor or to “ DIXELL S.p.A” 
(see address) with a detailed description of the fault. 

 

Consider the maximum current which can be applied to each relay (see Technical Data). 

 

Ensure that the wires for probes, loads and the power supply are separated and far enough from each 
other, without crossing or intertwining. 

 

In case of applications in industrial environments, the use of mains filters (our mod. FT1) in parallel with 
inductive loads could be useful. 

 

2.

 

GENERAL DESCRIPTION 

The XT151D and XT160D (DIN RAIL format) are three (XT151D) or four (XT160D) stage ON/OFF 
controllers for temperature, humidity and pressure applications  with direct or inverse action, user-
selectable. The analogue input type can be set by parameter between the following, according to the 
model: 

-

 

PTC, NTC;  

-

 

PTC, NTC, Pt100, Thermocouple J, K, S;  

-

 

4÷20mA, 0÷1V, 0÷10V. 

  

3.

 

FIRST INSTALLATION 

3.1

 

PROBE SETTING 

The pre-set probe type is written on the label of the instrument, 

see picture. If it is different from the probe that has be used, set 

the probe following procedure below 

3.1.1  How to set the probe. 

1.

 

Enter the programming menu by pressing the SET+ 

n

 for 3s. 

2.

 

Select the Pbc (Probe configuration) parameter and push the SET key. 

3.

 

Set the kind of probe: 

a.

 

Controller for temperaturePt= Pt100, = J thermocouple, c = K thermocouple, 
= S thermocouple; Ptc = PTC; ntc = ntc. 

b.

 

Controller with current or voltage inputs: cur=4÷20mA, 0-1= 0÷1V, 10= 0÷10V  

4.

 

Push the SET key to confirm it. 

5.

 

Switch the controller off and on again. 

 
NOTE:  Before proceeding check and, if necessary; set with appropriate values the Minimum Set 

Points (LS1 e LS2) and Maximum Set Points (US1 e US2). See also the paragraphs concerning 

the programming. 
 

4.

 

REGULATIONS 

4.1

 

3 OR 4 INDEPENDENT OUTPUTS (OUC=IND) 

3 or 4 independent control stages (ouC=ind): output #1 at direct (S1C=dir) or inverse (S1C=in) 
action; output #2 at (S2C = dir) direct or inverse (S2C =in) action, output #3 at (S3C = dir) direct or 
inverse (S3C =in) action, output #4 (only for XT160D) at (S4C = dir) direct or inverse (S4C =in) 
action. 

 

E.I. with OUC = ind, S1C = dir (cooling), S2C = dir (cooling), S3C = dir (cooling), S4C = dir 

(cooling). 

 

 

4.2

 

3 OR 4 DEPENDENT OUTPUTS  (OUC=DIP) 

With dependent control stages (ouC=diP) SET2 and SET3 are related to SET1:  
therefore SET2 is: SET1+SET2, while SET3 = SET1 + SET3 
output #1 with direct or inverse action according to the S1C parameter; output #2 with direct or 
inverse action according to the S2C, output #3 with direct or inverse action according to the S3C, 
output #4 (only for XT160D) with direct or inverse action according to the S4C. 
 

E.I. 3 outputs OUPUTS (XT151D) with ouC=diP (dependent), S1C = dir (cooling), S2C = dir 

(cooling), S3C = dir (cooling). 

 

 

5.

 

FRONT PANEL COMMANDS 

 

 

 

SET: To display and modify target set 

points; in programming mode it  
selects a parameter  or confirm an 
operation.  

TO SWITCH THE INSTRUMENT 
ON/OFF
: If the function is enabled 
(par. onF=yES), by pressing the 
SET key for more than 4s the 
controller is switched OFF. To 
switch the instrument on again 
press the SET key. 

o

 UP: in programming mode it browses 

the parameter codes or increases 
the displayed value. Hold it pressed 
for a faster change 

n

  DOWN:  in programming mode it 

browses the parameter codes or 
decreases the displayed value. Hold 
it pressed for a faster change 

 

KEY COMBINATIONS: 

n

  

To lock & unlock the keyboard. 

SET + 

n

 

To enter in programming mode. 

SET + 

o  

To return to the room temperature display. 

5.1

 

USE OF LEDS 

A series of light points on the front panels is used to monitor the loads controlled by the instrument. 
Each LED function is described in the following table. 

 

LED 

MODE 

FUNCTION 

ON 

Output 1 enabled 

 

ON 

Output 2 enabled 

ON 

Output 3 enabled 

 

ON 

Output 4 enabled – Only for XT160D 

 

Flashing  - Programming Phase (flashing with LED1) 

Summary of Contents for XT151D

Page 1: ... temperature Pt Pt100 J J thermocouple c K thermocouple S S thermocouple Ptc PTC ntc ntc b Controller with current or voltage inputs cur 4 20mA 0 1 0 1V 10 0 10V 4 Push the SET key to confirm it 5 Switch the controller off and on again NOTE Before proceeding check and if necessary set with appropriate values the Minimum Set Points LS1 e LS2 and Maximum Set Points US1 e US2 See also the paragraphs ...

Page 2: ...wn Sc Set4 Sets the minimum acceptable value for the set point4 US1 Maximum set point1 Set1 Full Sc Sets the maximum acceptable value for set point1 US2 Maximum set point2 Set2 Full Sc Sets the maximum acceptable value for set point2 US3 Maximum set point3 Set3 Full Sc Sets the maximum acceptable value for set point3 US4 Maximum set point4 only for XT160D Set4 Full Sc Sets the maximum acceptable v...

Page 3: ...gain or remove the Hot key to abort the operation 11 2 HOW TO PROGRAM AN INSTRUMENT USING A HOT KEY DOWNLOAD 1 Turn OFF the instrument 2 Insert a programmed Hot Key into the 5 PIN receptacle and then turn the Controller ON 3 Automatically the parameter list of the Hot Key is downloaded into the Controller memory the doL message is blinking followed a by flashing End 4 After 10 seconds the instrume...

Page 4: ...ation rE relat Ab absolute rE Pr2 ALL Minumum alarm ALC rE ALC Ab 0 Start Sc Set1 Start Sc ALu 10 0 20 Pr2 ALU Maximum alarm ALC rE ALC Ab 0 Full Sc Set1 ALL Full Scale 10 0 20 Pr2 ALH Alarm recovery differential 0 Full scale 2 0 4 Pr2 ALd Alarm delay 0 999 min 15 Pr2 dAO Alarm delay at start up 0 23h 50min 1 3 Pr2 tbA1 Alarm relay disabling no yES yES Pr2 AS1 Alarm relay polarity CL oP oP Pr2 So1...

Reviews: