background image

 

1592020080 XR72CX GB m&M r1.1 27.03.2015 

XR72CX 

4/4 

14.2

 

OTHER MESSAGES 

Pon 

Keyboard unlocked. 

PoF 

Keyboard locked 

noP 

In programming mode

: none parameter is present in Pr1 

On the display

 or in dP2, dP3, dP4: the selected probe is nor enabled 

15.

 

TECHNICAL DATA 

Housing: 

self extinguishing ABS.

 

Case: XR72CX 

frontal 32x74 mm; depth 60mm; 

Mounting: XR72CX 

panel mounting in a 71x29mm panel cut-out 

Protection: 

IP20; 

Frontal protection: XR72CX 

IP65 

Connections: 

Screw terminal block 

 2,5 mm

2

 wiring. 

Power  supply: 

according  to  the  model:  12Vac/dc,  ±10%;  24Vac/dc,  ±10%;    230Vac 

10%, 

50/60Hz, 110Vac 

10%, 50/60Hz

 

Power absorption: 

3VA max

 

Display

: 3 digits, red LED, 14,2 mm high; 

Inputs

: Up to 4 NTC or PTC probes.

 

Digital input: 

 free voltage contact 

Relay outputs: compressor 1 

SPST 8(3) A, 250Vac; SPST 16(6)A 250Vac

 

 

defrost: 

SPDT 8(3) A, 250Vac or SPST 16(6)A 250Vac 

 

fan: 

SPST 5A, 250Vac or SPST 16(6)A 250Vac 

 

compressor 2: 

SPDT 8(3) A, 250Vac or SPST 16(6)A 250Vac 

Data storing

: on the non-volatile memory (EEPROM). 

Kind of action: 

1B; 

Pollution grade: 

2;

Software class: 

A.;  

Rated impulsive voltage

: 2500V; 

Overvoltage Category

: II

 

Operating temperature: 

0÷60 °C;

Storage temperature: 

-30÷85 °C.  

Relative humidity:

 20

85% (no condensing) 

Measuring and regulation range: NTC probe: 

-40÷110°C (-40÷230°F);  

PTC probe: 

-50÷150°C (-58÷302°F) 

Resolution: 

0,1 °C or 1°C or 1 °F (selectable); 

Accuracy (ambient temp. 25°C)

:  ±0,7 °C ±1 digit 

16.

 

CONNECTIONS 

The X-REP

 

output

 

excludes

 the TTL output.. It’s present in the following codes:  

XR72CX- xx

2

xx, XR72CX –xx

3

xx; 

16.1

 

XR72CX – 8A OR 16A COMP. RELAY - 230VAC OR 120VAC 

 

NOTE: 

The compressor 

relay is 8(3)A or 16(6)A 
according to the model. 

24Vac supply

: connect 

to the terminals 5 and 6. 
 

16.2

 

XR72CX –4 X 16A - 12VAC/DC 

 

 

17.

 

DEFAULT SETTING VALUES  

Label 

Name 

Range 

°C/°F 

Level 

Set 

Set point 

LS÷US 

-5.0 

- - - 

Hy 

Differential 

0,1

25.5°C/ 1

 255°F 

2.0 

Pr1 

LS 

Minimum set point 

-50°C

SET/-58°F

SET 

-50.0 

Pr2 

US 

Maximum set point 

SET

110°C/ SET 

 230°F 

110 

Pr2 

Ot 

Thermostat probe calibration 

-12

12°C /-120

120°F 

0.0 

Pr1 

P2P 

Evaporator probe presence 

n=not present; Y=pres. 

Pr1 

OE 

Evaporator probe calibration 

-12

12°C /-120

120°F 

0.0 

Pr2 

P3P 

Third probe presence 

n=not present; Y=pres. 

Pr2 

O3 

Third probe calibration 

-12

12°C /-120

120°F 

Pr2 

P4P 

Fourth probe presence 

n=not present; Y=pres. 

Pr2 

O4 

Fourth probe calibration 

-12

12°C /-120

120°F 

Pr2 

OdS 

Outputs delay at start up 

0÷255 min 

Pr2 

AC 

Anti-short cycle delay 

 50 min 

Pr1 

AC1 

2

nd

 compressor delay 

 255s 

Pr1 

rtr 

P1-P2 percentage for regulation 

 0 ÷ 100 (100=P1 , 0=P2) 

100 

Pr2 

CCt 

Continuos cycle duration 

0.0÷24.0h 

0.0 

Pr2 

CCS 

Set point for continuous cycle 

 (-55.0÷150,0°C) (-67÷302°F) 

-5 

Pr2 

COn 

Compressor ON time with faulty probe 

 255 min 

15 

Pr2 

COF 

Compressor OFF time with faulty probe  0 

 255 min 

30 

Pr2 

Label 

Name 

Range 

°C/°F 

Level 

CF 

Temperature measurement unit 

°C 

 °F 

°C  

Pr2 

rES 

Resolution 

in=integer; dE= dec.point

 

dE  

Pr1 

Lod 

Probe displayed 

P1;P2 

P1 

Pr2 

rEd

X-REP display 

P1 - P2 - P3 - P4 - SEt - dtr 

P1 

Pr2 

dLy 

Display temperature delay   

0 ÷ 20.0 min  (10 sec.)  

Pr2 

dtr 

P1-P2 percentage for disply 

 1 ÷ 99 

50 

Pr2 

tdF 

Defrost type 

EL=el. heater;  in= hot gas 

EL 

Pr1 

dFP 

Probe selection for defrost termination 

nP; P1; P2; P3; P4 

P2 

Pr2 

dtE 

Defrost termination temperature 

-50 

 50 °C 

Pr1 

IdF 

Interval between defrost cycles 

 120 ore 

Pr1 

MdF 

(Maximum) length for defrost 

 255 min 

30 

Pr1 

dSd 

Start defrost delay 

0÷99min 

Pr2 

dFd 

Displaying during defrost 

rt, it, SEt, DEF 

it 

Pr2 

dAd 

MAX display delay after defrost 

0 ÷ 255 min 

30 

Pr2 

Fdt 

Draining time 

0÷120 min 

Pr2 

dPo

 

First defrost after startup 

n=after IdF; y=immed. 

Pr2 

dAF 

Defrost delay after fast freezing 

0 ÷ 23h e 50’ 

0.0 

Pr2 

Fnc 

Fan operating mode 

C-n, o-n, C-y, o-Y 

o-n 

Pr1 

Fnd 

Fan delay after defrost 

0÷255min 

10 

Pr1 

Fct 

Differential  of  temperature  for  forced 
activation of fans 

0÷50°C 

10 

Pr2 

FSt 

Fan stop temperature 

-50÷50°C/-58÷122°F 

Pr1 

Fon 

Fan on time with compressor off 

0÷15 (min.) 

Pr2 

FoF 

Fan off time with compressor off 

0÷15 (min.) 

Pr2 

FAP 

Probe selection for fan management 

nP; P1; P2; P3; P4 

P2 

Pr2 

ALc 

Temperat. alarms configuration 

rE= related to set; 

Ab = absolute 

Ab 

Pr2 

ALU 

MAXIMUM temperature alarm 

Set

110.0°C; Set÷230°F 

110 

Pr1 

ALL 

Minimum temperature alarm 

-50.0°C

Set/ -58°F

Set 

-50.0 

Pr1 

AFH 

Differential for temperat. alarm recovery 

(0,1°C÷25,5°C) (1°F÷45°F) 

Pr2 

ALd 

Temperature alarm delay 

 255 min 

15 

Pr2 

dAO 

Delay of temperature alarm at start up 

 23h e 50’ 

1.3 

Pr2 

AP2 

Probe for temperat. alarm of condenser 

nP; P1; P2; P3; P4 

P4 

Pr2 

AL2 

Condenser for low temperat. alarm 

(-55 ÷ 150°C) (-67÷ 302°F) 

-40 

Pr2 

AU2 

Condenser for high temperat. alarm 

(-55 ÷ 150°C) (-67÷ 302°F) 

110 

Pr2 

AH2 

Differ. for condenser temp. alar. recovery  [0,1°C ÷ 25,5°C]  [1°F ÷ 45°F] 

Pr2 

Ad2 

Condenser temperature alarm delay  

 0 ÷ 254 (min.) , 255=nU 

15 

Pr2 

dA2 

Delay of cond. temper. alarm at start up 

0.0 ÷ 23h  50’ 

1,3 

Pr2 

bLL 

Compr.  off  for  condenser  low 
temperature alarm 

n(0) - Y(1) 

Pr2 

AC2 

Compr.  off  for  condenser  high 
temperature alarm 

n(0) - Y(1) 

Pr2 

i1P 

Digital input polarity 

oP=opening;CL=closing 

cL 

Pr1 

i1F 

Digital input configuration 

EAL, bAL, PAL, dor; dEF; Htr, AUS 

dor 

Pr1 

did 

Digital input alarm delay 

0÷255min 

15 

Pr1 

Nps 

Number of activation of pressure switch 

0 ÷15  

15 

Pr2 

odc 

Compress  and  fan  status  when  open 
door 

no; Fan; CPr; F_C 

 

F-c 

Pr2 

rrd 

Regulation restart with door open alarm 

n – Y 

Pr2 

HES 

Differential for Energy Saving 

 (-30°C÷30°C) (-54°F÷54°F) 

Pr2 

PbC 

Kind of probe 

Ptc; ntc 

Pr2 

Adr 

Serrial address 

1÷247 

Pr2 

onF 

on/off key enabling 

nu, oFF; ES 

ntc 

Pr1 

dP1 

Room probe display 

-- 

nu 

Pr2 

dP2 

Evaporator probe display 

-- 

 -- 

Pr1 

dP3 

Third probe display 

-- 

 -- 

Pr1 

dP4 

Fourth probe display 

-- 

 -- 

Pr1 

rSE 

Valore set operativo 

actual set 

 -- 

Pr2 

rEL 

Software release 

-- 

 -- 

Pr2 

Ptb 

Map code 

-- 

 -- 

Pr2 

 

2

 Only for models XR72CX–xx

2

xx, XR72CX–xx

3

xx;  

 

 
 