1592020080 XR72CX GB m&M r1.1 27.03.2015 

XR72CX 

2/4 

6.3

 

HOW TO START A MANUAL DEFROST 

 

Push the 

DEF 

key for more than 2 seconds and a manual defrost will start. 

6.4

 

HOW TO CHANGE A PARAMETER VALUE 

To change the parameter’s value operate as follows:  
1.

 

Enter the Programming mode by pressing the 

Set

 + 

n

 keys for 3s (the “

°C” or “°F”

 LED starts 

blinking). 

2.

 

Select the required parameter. Press the “

SET

” key to display its value 

3.

 

Use “

UP

” or “

DOWN

” to change its value. 

4.

 

Press “

SET

” to store the new value and move to the following parameter. 

To exit

: Press 

SET + UP 

or wait 15s without pressing a key. 

NOTE

: the set value is stored even when the procedure is exited by waiting the time-out to expire. 

6.5

 

THE HIDDEN MENU 

The hidden menu Includes all the parameters of the instrument. 

6.5.1  HOW TO ENTER THE HIDDEN MENU 

1.

 

Enter the Programming mode by pressing the 

Set

 + 

n

 keys for 3s (the “

°C” or “°F”

 LED starts 

blinking). 

2.

 

Released  the  keys,  then  push  again  the  Set+

n

  keys  for  more  than  7s.  The  Pr2  label  will  be 

displayed immediately followed from the HY parameter.  

NOW YOU ARE IN THE HIDDEN MENU.

 

3.

 

Select the required parameter. 

4.

 

Press the “

SET

” key to display its value 

5.

 

Use 

or 

n

 to change its value. 

6.

 

Press “

SET

” to store the new value and move to the following parameter. 

To exit

: Press 

SET + 

or wait 15s without pressing a key. 

NOTE1: 

if none parameter is present in Pr1, after 3s the “noP” message is displayed. Keep the keys 

pushed till the Pr2 message is displayed.  

NOTE2

: the set value is stored even when the procedure is exited by waiting the time-out to expire. 

6.5.2  HOW  TO  MOVE  A  PARAMETER  FROM  THE  HIDDEN  MENU  TO  THE 
FIRST LEVEL AND VICEVERSA. 

Each  parameter  present  in  the  HIDDEN  MENU  can  be  removed  or  put  into  “THE  FIRST  LEVEL” 
(user level) by pressing 

“SET + 

n

.  

In HIDDEN MENU when a parameter is present in First Level the decimal point is on. 

6.6

 

HOW TO LOCK THE KEYBOARD 

1. 

 

Keep pressed for more than 3 s the 

UP

 +  

DOWN

 keys. 

2. 

 

The “POF” message will be displayed and the keyboard will be locked. At this point it will be 
possible only to see the set point or the MAX o Min temperature stored 

3. 

 

If a key is pressed more than 3s the “POF” message will be displayed. 

6.7

 

TO UNLOCK THE KEYBOARD 

Keep  pressed  together  for  more  than  3s  the 

and 

n

  keys,  till  the 

“Pon” 

message  will  be 

displayed. 

6.8

 

THE CONTINUOUS CYCLE 

When  defrost  is  not  in  progress,  it  can  be  activated  by  holding  the  “

o

”  key  pressed  for  about  3 

seconds. The compressor operates to maintain the “

ccS

” set point for the time set through the “

CCt

” 

parameter. The cycle can be terminated before the end of the set time using the same activation key 

o

” for 3 seconds. 

6.9

 

THE ON/OFF FUNCTION 

 

 

With “

onF = oFF

”, pushing the 

ON/OFF

 key, the instrument is switched off. The 

“OFF” 

message is displayed. In this configuration, the regulation is disabled.  
To switch the instrument on, push again the ON/OFF key. 

 

WARNING:  Loads  connected  to  the  normally  closed  contacts  of  the  relays  are  always 

supplied and under voltage, even if the instrument is in stand by mode.  

7.

 

PARAMETERS 

REGULATION 
Hy Differential

: (0,1 ÷ 25,5°C / 1÷255 °F) Intervention differential for set point. Compressor Cut IN 

is Set Point + differential (Hy). Compressor Cut OUT is when the temperature reaches the set 
point. 

LS  Minimum set point:

 (- 50°C÷SET/-58°F÷SET): Sets the minimum value for the set point. 

US Maximum set point: 

(SET÷110°C/ SET÷230°F). Set the maximum value for set point. 

Ot  Thermostat probe calibration

: (-12.0÷12.0°C; -120÷120°F) allows to adjust possible offset of 

the thermostat probe. 

P2P  Evaporator probe presence: n

= not present: the defrost stops by time; 

y=

 present: the defrost 

stops by temperature. 

OE Evaporator probe calibration:

 (-12.0÷12.0°C; -120÷120°F). allows to adjust possible offset of 

the evaporator probe. 

P3P  Third  probe  presence  (P3):  n

=  not  present:,  the  terminal  operates  as  digital  input.; 

y=

 

present:, the terminal operates as third probe. 

O3 Third probe calibration  (P3):

 (-12.0÷12.0°C; -120÷120°F). allows to adjust possible offset of 

the third probe. 

P4P Fourth probe presence

: (n = Not present; y = present). 

o4  Fourth probe calibration

: (-12.0

12.0°C) allows to adjust possible offset of the fourth probe. 

odS Outputs activation delay at start up:

 (0÷255min) This function is enabled at the initial start up 

of the instrument and inhibits any output activation for the period of time set in the parameter.  

AC    Anti-short  cycle  delay

:  (0÷50  min)  minimum  interval  between  the  compressor stop and the 

following restart. 

AC1 2

nd

 compressor delay at start up 

(0÷255s) Time interval between the switching on of the first 

compressor and the second one. 

rtr  Percentage  of  the  second  and  first  probe  for  regulation  (0÷100;  100  =  P1,  0  =  P2  ): 

it 

allows to set the regulation according to the percentage of the first and second probe, as for the 
following formula (rtr(P1-P2)/100 + P2). 

CCt Compressor ON time during continuous  cycle: 

(0.0÷24.0h; res. 10min) Allows to set the 

length of the continuous cycle: compressor stays on without interruption for the CCt time. Can be 
used, for instance, when the room is filled with new products. 

CCS Set point for continuous cycle: 

(-50÷150°C) it sets the set point used during the continuous 

cycle. 

COn Compressor ON time with faulty probe: 

(0÷255 min) time during which the compressor is 

active in case of faulty thermostat probe. With COn=0 compressor is always OFF. 

COF Compressor OFF time with faulty probe: 

(0÷255 min) time during which the compressor is 

OFF in case of faulty thermostat probe. With COF=0 compressor is always active. 

DISPLAY 
CF  Temperature  measurement  unit: 

 

°C=

Celsius; 

°F

=Fahrenheit.  WARNING:  When  the 

measurement unit is changed the SET point and the values  of the parameters Hy, LS, US, Ot, 
ALU and ALL have to be checked and modified if necessary). 

rES  Resolution (for °C)

: (in = 1°C; dE = 0.1 °C) allows decimal point display. 

Lod  Instrument  display

:  (P1;  P2,  P3,  P4,    SET,  dtr):  it  selects  which  probe  is  displayed  by  the 

instrument: 

P1

 = Thermostat probe; 

P2

 = Evaporator probe; 

P3

 = Third probe(only for model 

with  this  option  enabled); 

P4

  =  Fourth  probe,

  SET

  =  set  point;   

dtr

  =  percentage  of 

visualization. 

rEd  X- REP display (

optional

)

: (P1; P2, P3, P4,  SET, dtr): it selects which probe is displayed by 

X- REP: 

P1

 = Thermostat probe; 

P2

 = Evaporator probe; 

P3

 = Third probe(only for model with 

this option enabled); 

P4

 = Fourth probe,

 SET

 = set point;  

dtr

 = percentage of visualization. 

dLy  Display delay: 

(0 ÷20.0m; risul. 10s) when the temperature increases, the display is updated 

of 1 °C/1°F after this time. 

dtr  Percentage of the second and first probe for visualization when Lod = dtr (0÷100; 100 = 

P1, 0 = P2 ): if Lod = dtr 

it allows to set the visualization according to the percentage of the 

first and second probe, as for the following formula (dtr(P1-P2)/100 + P2). 

DEFROST 
tdF   Defrost type

: EL = electrical heater; in = hot gas 

dFP  Probe  selection  for  defrost  termination:  nP

  =  no  probe; 

P1

  =thermostat  probe; 

P2  = 

evaporator probe; 

P3

 =configurable probe; 

P4

 = Probe on Hot Key plug. 

dtE  Defrost termination temperature

: (-50÷50 °C/  

-58÷122°F) (Enabled only when EdF=Pb) sets the temperature measured by the evaporator 
probe, which causes the end of defrost. 

IdF   Interval  between  defrost  cycles

:  (0÷120h)  Determines  the  time  interval  between  the 

beginning of two defrost cycles. 

MdF    (Maximum)  length  for  defrost

:  (0÷255min)  When 

P2P  =  n

,  (not  evaporator  probe:  timed 

defrost) it sets the defrost duration, when 

P2P = y

 (defrost end based on temperature) it sets 

the maximum length for defrost. 

dSd Start defrost delay

: ( 0÷99min) This is useful when different defrost start times are necessary 

to avoid overloading the plant.  

dFd    Temperature  displayed  during  defrost

:  (

rt

  =  real temperature; 

it

 = temperature at  defrost 

start; 

SEt

 = set point; 

dEF

 = “dEF” label) 

dAd  MAX  display  delay  after  defrost

:  (0÷255min).  Sets  the  maximum  time  between  the  end of 

defrost and the restarting of the real room temperature display. 

Fdt  Drip time

: (0

120 min) time interval between reaching defrost termination temperature and the 

restoring of the control’s normal operation. This time allows the evaporator to eliminate water 
drops that might have formed due to defrost. 

dPo  First defrost after start-up

: (y = immediately; n = after the IdF time) 

dAF  Defrost  delay  after  continuous  cycle

:  (0

23.5h)  time  interval  between  the  end  of  the  fast 

freezing cycle and the following defrost related to it. 

FANS 
FnC Fans operating mode

C-n

= runs with the compressor, OFF during defrost;  

o-n

 = continuous mode, OFF during defrost;  

C-Y

 = runs with the compressor, ON during defrost;  

o-Y

 = continuous mode, ON during defrost;  

Fnd  Fans  delay  after  defrost:

  (0÷255min)  Interval  between  end  of  defrost  and  evaporator  fans 

start.

 

Fct  Temperature differential avoiding short cycles of fans 

(0÷59°C; Fct=0 function disabled). If 

the difference of temperature between the evaporator and the room probes is more than the 
value of the Fct parameter, the fans are switched on.

 

FSt   Fans  stop  temperature

:  (-50÷50°C/122°F)  setting  of  temperature,  detected  by  evaporator 

probe, above which fans are always OFF. 

Fon Fan ON time:

 (0÷15 min)

 with 

Fnc = C_n or C_y, (fan activated in parallel with compressor). it 

sets the evaporator fan ON cycling time when the compressor is off. With Fon =0 and FoF ≠ 0 
the fan are always off, with Fon=0 and FoF =0 the fan are always off.

 

FoF Fan OFF time:

 (0÷15 min)

 with 

Fnc = C_n or C_y, (fan activated in parallel with compressor). it 

sets the evaporator fan off cycling time when the compressor is off. With Fon =0 and FoF ≠ 0 
the fan are always off, with Fon=0 and FoF =0 the fan are always off.

 

FAP  Probe selection for fan management: nP

 = no probe; 

P1

 =thermostat probe; 

P2 = 

evaporator 

probe; 

P3

 =configurable probe; 

P4

 = Probe on Hot Key plug. 

ALARMS 
ALC  Temperature alarms configuration:

 (Ab; rE) 

 

Ab=  absolute  temperature:  alarm  temperature  is  given  by  the  ALL  or  ALU  values.    rE  = 
temperature  alarms  are  referred  to  the  set  point.  Temperature  alarm  is  enabled  when  the 
temperature exceeds the “SET+ALU” or “SET-ALL” values. 

ALU  MAXIMUM temperature alarm

: (SET÷110°C; SET÷230°F) when this temperature is reached  

the alarm is enabled, after the “ALd” delay time. 

ALL Minimum temperature alarm

: (-50.0 ÷ SET°C; -58÷230°F when this temperature is reached  

the alarm is enabled, after the “ALd” delay time. 

AFH  Differential  for  temperature  alarm/  fan  recovery: 

(0,1÷25,5°C;  1÷45°F)  Intervention 

differential for recovery of temperature alarm. It’s also used for the restart of the fan when the 
FSt temperature is reached  

ALd    Temperature  alarm  delay

:  (0÷255  min)  time  interval  between  the  detection  of  an  alarm 

condition and alarm signalling. 

dAO Exclusion of temperature alarm at startup

: (from 0.0 min to 23.5h) time interval between the 

detection of the temperature alarm condition after instrument power on and alarm signalling. 

CONDENSER TEMPERATURE ALARM 
AP2  Probe selection for temperature alarm of condenser: nP

 = no probe; 

P1

 =thermostat probe; 

P2 = 

evaporator probe; 

P3

 =configurable probe; 

P4

 = Probe on Hot Key plug. 

AL2  Low  temperature  alarm  of  condenser

:

 

(-55÷150°C)  when  this  temperature  is  reached  the 

LA2 alarm is signalled, possibly after the Ad2 delay. 