background image

 

1592020080 XR72CX GB m&M r1.1 27.03.2015 

XR72CX 

1/4 

Digital controller with defrost and fans management

 

XR72CX 

 

1.

 

GENERAL WARNING 

1.1

 

PLEASE READ BEFORE USING THIS MANUAL 

 

This manual is part of the product and should be kept near the instrument for easy and quick reference. 

 

The instrument shall not be used for purposes different from those described hereunder. It cannot be 
used as a safety device. 

 

Check the application limits before proceeding. 

 

Dixell Srl reserves the right to change the composition of its products, even without notice, ensuring the 
same and unchanged functionality. 

1.2

 

 SAFETY PRECAUTIONS 

 

Check the supply voltage is correct before connecting the instrument. 

 

Do not expose to water or moisture: use the controller only within the operating limits avoiding sudden 
temperature changes with high atmospheric humidity to prevent  formation of condensation 

 

Warning: disconnect all electrical connections before any kind of maintenance. 

 

Fit the probe where it is not accessible by the End User. The instrument must not be opened. 

 

In case of failure or faulty operation send the instrument back to the distributor or to “Dixell S.r.l.” (see 
address) with a detailed description of the fault. 

 

Consider the maximum current which can be applied to each relay (see Technical Data). 

 

Ensure that the wires for probes, loads and the power supply are separated and far enough from each 
other, without crossing or intertwining. 

 

In case of applications in industrial environments, the use of mains filters (our mod. FT1) in parallel with 
inductive loads could be useful. 

2.

 

GENERAL DESCRIPTION 

Model 

XR72CX

, format 32 x 74 mm, is microprocessor based controller, suitable for applications on 

medium  or  low  temperature  ventilated  refrigerating  units.  It  has  four  relay  outputs  to  control 
compressor  1,  compressor  2,  fan and defrost,  which can be either electrical or reverse cycle (hot 
gas).  It  is  also  provided  with  up  to  four  NTC  or  PTC  probe  inputs,  the  first  one  for  temperature 
control,  the  second  one,  to  be  located  onto  the  evaporator,  to  control  the  defrost  termination 
temperature and to managed the fan. The digital input can operate as third temperature probe.  The 
fourth one, to connect to the HOT KEY terminals is used to signal the condenser temperature alarm 
or to display a temperature. 
The HOT KEY output allows to connect the unit, by means of the external module XJ485-CX,  to a 
network  line 

ModBUS-RTU

  compatible  such  as  the  Dixell  monitoring  units    of  X-WEB  family.  It 

allows to program the controller by means the HOT KEY programming  keyboard.  
The  instrument  is  fully  configurable  through  special  parameters  that  can  be  easily  programmed 
through the keyboard. 

3.

 

CONTROLLING LOADS 

3.1

 

COMPRESSOR 

The  regulation  is  performed  according 
to  the  temperature  measured  by  the 
thermostat  probe  with  a  positive 
differential  from  the  set  point:  if  the 
temperature  increases  and reaches set 
point plus differential the compressor is 
started  and  then  turned  off  when  the 
temperature reaches the set point value 
again. 

Time

Temper.

Compr.

SET

ON

 

In  case  of  fault  in  the  thermostat  probe  the  start  and  stop  of  the  compressor  are  timed  through 
parameters “

COn

” and “

COF

”. 

3.2

 

2

ND

 COMPRESSOR MANAGEMENT – XR72C ONLY 

The relay of the second compressor is activated in parallel with the relay of the first compressor, with 
a possible delay set in the 

AC1 

parameter. Both the compressors are switched off at the same time. 

3.3

 

DEFROST 

Two defrost modes are available through the “

tdF

” parameter: defrost through electrical heater (

tdF 

= EL

) and hot  gas  defrost (

tdF = in

). Other parameters are used to control the interval between 

defrost cycles (IdF), its maximum length (MdF) and two defrost modes: timed or controlled by the 
evaporator’s probe (P2P).  
At the end of defrost dripping time is started, its length is set in the FSt parameter. With FSt =0 the 
dripping time is disabled. 

3.4

 

CONTROL OF EVAPORATOR FANS 

The fan control mode is selected by means of the “

FnC

” parameter: 

FnC = C_n:

  fans will switch ON and OFF with the compressor and

 not run

 during defrost; 

FnC = o_n

  fans will run even if the compressor is off, and not run during defrost; 

After defrost, there is a timed fan delay allowing for drip time, set by means of the “

Fnd

” parameter. 

FnC = C_Y

   fans will switch ON and OFF with the compressor and 

run

 during defrost; 

FnC = o_Y

  fans will run continuously also during defrost 

 

An additional parameter “

FSt

” provides the setting of temperature, detected by the evaporator probe, 

above  which  the  fans  are  always  OFF.  This  is  used  to  make  sure  circulation  of  air  only  if  his 
temperature is lower than set in “FSt”. 

3.4.1  Forced activation of fans 

This function managed by the 

Fct

 parameter is designed to avoid short cycles of fans, that could 

happen  when  the  controller  is  switched  on  or  after  a  defrost,  when  the  room  air  warms  the 
evaporator. 

Functioning: 

if  the  difference  of  temperature  between  the  evaporator  and  the  room 

probes is more than the value of the Fct parameter, the fans are switched on. With Fct=0 the function 
is disabled. 

3.4.2  Cyclical activation of the fans with compressor off. 

When  Fnc  =  c-n  or  c-Y  (fans  in  parallel  to  the  compressor),  by  means  of  the  Fon  and  FoF 
parameters the fans can carry out on and off cycles even if the compressor is switched off. When the 
compressor is stopped the fans go on working for the Fon time. With Fon =0 the fans remain always 
off, when the compressor is off.  

4.

 

FRONT PANEL COMMANDS 

 

 

 

: To display target set point; in programming mode it  selects a parameter  or confirm an 

operation. 

 (DEF) 

To start a manual defrost 

 

 (

UP)

: To see the max. stored temperature; in programming mode it browses the parameter 

codes or increases the displayed value. 

 (

DOWN

) To see the min stored temperature; in programming mode it browses the parameter 

codes or decreases the displayed value. 

 

To switch the instrument off, if onF = oFF.  

 

Not used. 

KEY COMBINATIONS: 

  

 



To lock & unlock the keyboard

.

 

 

+

  

 

To enter in programming mode. 

  

+

  

 

To return to the room temperature display. 

4.1

 

USE OF LEDS 

Each LED function is described in the following table. 

LED 

MODE 

FUNCTION 

 

ON 

Compressor enabled 

 

Flashing  Anti-short cycle delay enabled 

 

ON 

Defrost enabled 

 

Flashing  Drip time in progress 

 

ON 

Fans enabled 

 

Flashing  Fans delay after defrost in progress. 

 

ON 

An alarm is occurring 

  ON 

Continuous cycle is running 

  ON 

Energy saving enabled 

°C/°F 

ON 

Measurement unit 

°C/°F 

Flashing  Programming phase 

5.

 

MAX & MIN TEMPERATURE MEMORIZATION 

5.1

 

HOW TO SEE THE MIN TEMPERATURE 

1. 

 

Press and release the 

n

 key. 

2. 

 

The “Lo” message will be displayed followed by the minimum temperature recorded. 

3. 

 

By pressing the 

n

 key again or by waiting 5s the normal display will be restored. 

5.2

 

HOW TO SEE THE MAX TEMPERATURE 

1. 

 

Press and release the 

o

 key. 

2. 

 

The “Hi” message will be displayed followed by the maximum  temperature recorded. 

3. 

 

By pressing the 

o

 key again or by waiting 5s the normal display will be restored. 

5.3

 

HOW TO RESET THE MAX AND MIN TEMPERATURE RECORDED 

1.

 

Hold press the SET key for more than 3s, while the max. or min temperature is displayed. (rSt 
message will be displayed) 

2.

 

To confirm the operation the “rSt” message starts blinking and the normal temperature will be 
displayed. 

6.

 

MAIN FUNCTIONS 

6.1

 

HOW TO SEE THE SETPOINT 

 

1.

 

Push  and  immediately  release  the 

SET 

key:  the  display  will  show  the 

Set point value; 

2.

 

Push and immediately release the 

SET 

key or wait for 5 seconds to  

display the probe value again. 

6.2

 

HOW TO CHANGE THE SETPOINT 

1.

 

Push the 

SET 

key for more than 2 seconds to change the Set point value; 

2.

 

The value of the set point will be displayed and the “

°C” or “°F”

 LED starts blinking; 

3.

 

To change the Set value push the 

or 

n

 arrows within 10s. 

4.

 

To memorise the new set point value push the 

SET

 key again or wait 10s. 