background image

Dixell

 

Installing and Operating Instructions 

1592007230

 

 

1592007230 XR40C GB r1.0 15.05.2003 

XR40C 

4/4 

14. CONNECTIONS 

14.1  XR40C: 8A COMPRESSOR 

N.C.

1

2

3

4

5

6

7

9 10 11 12

Comp

Def

Ev

ap

.

Ro

om

8

Hot Key

8(3)A250V

8(3)A250V

Line

 

 

12Vac/dc supply

: connect to the terminals 7 and 8. 

24Vac/dc supply

: connect to the terminals 7 and 8. 

120Vac supply

: connect to the terminals 7 and 8. 

 

14.2  XR40C: 20A COMPRESSOR  

 

N.C.

1

2

3

4

5

6

7

9 10 11 12

Comp

Def

Ev

ap

.

Ro

om

8

Hot Key

8(3)A250V

20(8)A250V

Line

 

 
12Vac/dc supply

: connect to the terminals 7 and 8. 

24Vac/dc supply

: connect to the terminals 7 and 8. 

120Vac supply

: connect to the terminals 7 and 8. 

 
 

15.  DEFAULT SETTING VALUES  

Label

Name Range 

°C/°F 

Set 

Set point 

LS÷US 

-5/0 

Hy 

Differential 

0,1

÷

25.5°C/ 1

÷

 255°F 

2/4 

LS 

Minimum set point 

-50°C

÷

SET/-58°F

÷

SET 

-50/-58 

US 

Maximum set point 

SET

÷

110°C/ SET 

÷

 230°F 

110/230 

Ot 

Thermostat probe calibration 

-12

÷

12°C /-120

÷

120°F 

P2P

Evaporator probe presence 

n=not present; Y=pres. 

OE 

Evaporator probe calibration 

-12

÷

12°C /-120

÷

120°F 

OdS

Outputs delay at start up 

0÷255 min 

AC 

Anti-short cycle delay 

÷

 50 min 

CCt 

Continuos cycle duration 

0.0÷24.0h 

0.0 

COn

Compressor ON time with faulty 
probe 

÷

 255 min 

15 

COF

Compressor OFF time with faulty 
probe 

÷

 255 min 

30 

CF 

Temperature measurement unit 

°C 

÷

 °F 

°C/°F 

rES 

Resolution 

in=integer; dE= dec.point

 

dE/- 

Lod 

Probe displayed 

P1;P2 

P1 

tdF 

Defrost type 

EL=el. heater;  in= hot gas 

EL 

dtE 

Defrost termination temperature 

-50 

÷

 50 °C 

8/46 

IdF 

Interval between defrost cycles 

÷

 120 ore 

MdF

(Maximum) length for defrost 

÷

 255 min 

30 

dSd

Start defrost delay 

0÷99min 

dFd 

Displaying during defrost 

rt, it, SEt, DEF 

it 

dAd

MAX display delay after defrost 

0 ÷ 255 min 

30 

Fdt 

Draining time 

0÷120 min 

dPo

 

First defrost after startup 

n=after IdF; y=immed. 

dAF

Defrost delay after fast freezing 

0 ÷ 23h e 50’ 

0.0 

ALc

Temperat. alarms configuration 

rE= related to set; 

Ab = absolute 

Ab 

ALU

MAXIMUM temperature alarm 

Set

÷

110.0°C; Set÷230°F 

110/230

ALL

Minimum temperature alarm 

-50.0°C

÷

Set/ -58°F

÷

Set 

-50/-58

ALd

Temperature alarm delay 

÷

 255 min 

15 

dAO

Delay of temperature alarm at 
start up 

÷

 23h e 50’ 

1.30 

i1P 

Digital input polarity 

oP=opening;CL=closing 

CL 

i1F 

Digital input configuration 

EAL=extern. alarm; bAL=lock 

regulation; PAL=press. switch; 
dor=door switch; dEF=defrost; 

LHt=disabled; Htr = Cooling - 

heating 

EAL 

did 

Digital input alarm delay 

0÷255min 

Nps

Number of activation of pressure 
switch 

0 ÷15  

15 

odc 

Compressor status with open 
door:   

no, Fan = normal;  

CPr; F_C = Compr. OFF; 

 

no 

PbC

Kind of probe 

Ptc; ntc 

ntc/Ptc

dP1

Room probe display 

-- 

-- 

dP2

Evaporator probe display 

-- 

-- 

rEL 

Software release 

-- 

4.0 

Ptb 

Map code 

-- 

 

Hidden parameters 

 

 

 

 

Dixell s.r.l.  Z.I. Via dell’Industria, 27 
32010 Pieve d’Alpago (BL) ITALY 
tel. +39 - 0437 - 98 33  -  fax +39 - 0437 - 98 93 13 

E-mail: [email protected] - http://www.dixell.com

 

Reviews: