Dixell
Installing and Operating Instructions
1592007230
1592007230 XR40C GB r1.0 15.05.2003
XR40C
4/4
14. CONNECTIONS
14.1 XR40C: 8A COMPRESSOR
N.C.
1
2
3
4
5
6
7
9 10 11 12
Comp
Def
Ev
ap
.
Ro
om
8
Hot Key
8(3)A250V
8(3)A250V
Line
12Vac/dc supply
: connect to the terminals 7 and 8.
24Vac/dc supply
: connect to the terminals 7 and 8.
120Vac supply
: connect to the terminals 7 and 8.
14.2 XR40C: 20A COMPRESSOR
N.C.
1
2
3
4
5
6
7
9 10 11 12
Comp
Def
Ev
ap
.
Ro
om
8
Hot Key
8(3)A250V
20(8)A250V
Line
12Vac/dc supply
: connect to the terminals 7 and 8.
24Vac/dc supply
: connect to the terminals 7 and 8.
120Vac supply
: connect to the terminals 7 and 8.
15. DEFAULT SETTING VALUES
Label
Name Range
°C/°F
Set
Set point
LS÷US
-5/0
Hy
Differential
0,1
÷
25.5°C/ 1
÷
255°F
2/4
LS
Minimum set point
-50°C
÷
SET/-58°F
÷
SET
-50/-58
US
Maximum set point
SET
÷
110°C/ SET
÷
230°F
110/230
Ot
Thermostat probe calibration
-12
÷
12°C /-120
÷
120°F
0
P2P
Evaporator probe presence
n=not present; Y=pres.
y
OE
Evaporator probe calibration
-12
÷
12°C /-120
÷
120°F
0
OdS
Outputs delay at start up
0÷255 min
0
AC
Anti-short cycle delay
0
÷
50 min
1
CCt
Continuos cycle duration
0.0÷24.0h
0.0
COn
Compressor ON time with faulty
probe
0
÷
255 min
15
COF
Compressor OFF time with faulty
probe
0
÷
255 min
30
CF
Temperature measurement unit
°C
÷
°F
°C/°F
rES
Resolution
in=integer; dE= dec.point
dE/-
Lod
Probe displayed
P1;P2
P1
tdF
Defrost type
EL=el. heater; in= hot gas
EL
dtE
Defrost termination temperature
-50
÷
50 °C
8/46
IdF
Interval between defrost cycles
1
÷
120 ore
6
MdF
(Maximum) length for defrost
0
÷
255 min
30
dSd
Start defrost delay
0÷99min
0
dFd
Displaying during defrost
rt, it, SEt, DEF
it
dAd
MAX display delay after defrost
0 ÷ 255 min
30
Fdt
Draining time
0÷120 min
0
dPo
First defrost after startup
n=after IdF; y=immed.
n
dAF
Defrost delay after fast freezing
0 ÷ 23h e 50’
0.0
ALc
Temperat. alarms configuration
rE= related to set;
Ab = absolute
Ab
ALU
MAXIMUM temperature alarm
Set
÷
110.0°C; Set÷230°F
110/230
ALL
Minimum temperature alarm
-50.0°C
÷
Set/ -58°F
÷
Set
-50/-58
ALd
Temperature alarm delay
0
÷
255 min
15
dAO
Delay of temperature alarm at
start up
0
÷
23h e 50’
1.30
i1P
Digital input polarity
oP=opening;CL=closing
CL
i1F
Digital input configuration
EAL=extern. alarm; bAL=lock
regulation; PAL=press. switch;
dor=door switch; dEF=defrost;
LHt=disabled; Htr = Cooling -
heating
EAL
did
Digital input alarm delay
0÷255min
5
Nps
Number of activation of pressure
switch
0 ÷15
15
odc
Compressor status with open
door:
no, Fan = normal;
CPr; F_C = Compr. OFF;
no
PbC
Kind of probe
Ptc; ntc
ntc/Ptc
dP1
Room probe display
--
--
dP2
Evaporator probe display
--
--
rEL
Software release
--
4.0
Ptb
Map code
--
-
Hidden parameters
Dixell s.r.l. Z.I. Via dell’Industria, 27
32010 Pieve d’Alpago (BL) ITALY
tel. +39 - 0437 - 98 33 - fax +39 - 0437 - 98 93 13
E-mail: [email protected] - http://www.dixell.com