Ptb 

Parameter table code: readable only. 

8. DIGITAL 

INPUT 

The free contact digital input is programmable in five different configurations by 
the “

i1F

” parameter. 

8.1  DOOR SWITCH INPUT  (i1F = dor) 

It signals the door status and the corresponding relay output status through the 

odc

” parameter: 

no,

 

Fan

 = normal (any change); 

CPr, F_C

 = Compressor OFF; 

Since the door is opened, after the delay time set through parameter “

did

”, the 

door alarm is enabled, the display shows the message “

dA

” and 

the regulation 

restarts

. The alarm stops as soon as the external digital input is disabled again. 

With the door open, the high and low temperature alarms are disabled. 

8.2  GENERIC ALARM (i1F = EAL) 

As soon as the digital input is activated the unit will wait for “

did

” time delay before 

signalling the “

EAL

” alarm message. The outputs status don’t change. The alarm 

stops just after the digital input is de-activated. 

8.3  SERIOUS ALARM MODE (i1F = bAL) 

When the digital input is activated, the unit will wait for “

did

” delay before 

signalling the “

CA

” alarm message. The relay outputs are switched OFF. The 

alarm will stop as soon as the digital input is de-activated. 

8.4  PRESSURE SWITCH (i1F = PAL) 

If during the interval time set by “

did

” parameter, the pressure switch has reached 

the number of activation of  the “

nPS

” parameter, the “

CA

” pressure alarm 

message will be displayed. The compressor and the regulation are stopped. When 
the digital input is ON the compressor is always OFF. 

If the nPS activation in the did time is reached, switch off and on the 
instrument to restart normal regulation. 

8.5  START DEFROST (i1F = dFr) 

It starts a defrost if there are the right conditions. After the defrost is finished, the 
normal regulation will restart only if the digital input is disabled otherwise the 
instrument will wait until the “MdF” safety time is expired. 

8.6  INVERSION OF  THE KIND OF ACTION: HEATING-
COOLING (i1F = Htr) 

This function allows to invert the regulation of the controller: from cooling to 
heating and viceversa. 

8.7  DIGITAL INPUTS POLARITY  

The digital input polarity depends on the “

i1P

” parameter. 

i1P=CL

: the input is activated by closing the contact.

 

i1P=OP

: the input is activated by opening the contact 

 

9.  INSTALLATION AND MOUNTING 

Instrument 

XR40C

 shall be mounted on vertical panel, 

in a 29x71 mm hole, and fixed using the special bracket 
supplied.  
To obtain an IP65 protection grade use the front panel 
rubber gasket (mod. RG-C) as shown in figure.  

 

The temperature range allowed for correct operation is 0

÷

60 °C. Avoid places 

subject to strong vibrations, corrosive gases, excessive dirt or humidity. The same 
recommendations apply to probes. Let air circulate by the cooling holes. 

10. ELECTRICAL 

CONNECTIONS 

The instrument is provided with screw terminal block to connect cables with a 
cross section up to 2,5 mm

2

. Before connecting cables make sure the power 

supply complies with the instrument’s requirements. Separate the probe cables 
from the power supply cables, from the outputs and the power connections. Do not 
exceed the maximum current allowed on each relay, in case of heavier loads use 
a suitable external relay. 

10.1 PROBE 

CONNECTION 

The probes shall be mounted with the bulb upwards to prevent damages due to 
casual liquid infiltration. It is recommended to place the thermostat probe away 
from air streams to correctly measure the average room temperature. Place the 
defrost termination probe among the evaporator fins in the coldest place, where 
most ice is formed, far from heaters or from the warmest place during defrost, to 
prevent premature defrost termination. 

11.  HOW TO USE THE HOT KEY  

11.1  HOW TO PROGRAM A HOT KEY FROM THE 
INSTRUMENT (UPLOAD) 

1. 

Program one controller with the front keypad. 

2. 

When the controller is ON, insert the “

Hot key

” and push 

o

 key; the  

"uPL" 

message appears followed a by flashing 

“End”

 

3. Push 

SET”

 key and the 

End

 will stop flashing. 

4. Turn 

OFF the instrument remove the 

“Hot Key”, 

then turn it ON again. 

 

NOTE

: the “

Err

” message is displayed for failed programming. In this case push 

again 

o

 key if you want to restart the upload again or remove the “

Hot key

” to 

abort the operation. 

11.2  HOW TO PROGRAM AN INSTRUMENT USING A HOT KEY 
(DOWNLOAD) 

1. 

Turn OFF the instrument. 

2. 

Insert  a 

programmed “Hot Key” into the 5 PIN receptacle 

and then turn 

the Controller ON. 

3. Automatically 

the 

parameter list of the 

“Hot Key”

 is downloaded into the 

Controller memory, the “

doL

” message is blinking followed a by flashing 

“End”.

 

4.  After 10 seconds the instrument will restart working with the new 

parameters.  

5. Remove 

the 

“Hot Key”.

 

NOTE 

the message “

Err

” is displayed for failed programming. In this case turn the 

unit off and then on if you want to restart the download again or remove the “

Hot 

key

” to abort the operation. 

 

12. ALARM 

SIGNALS 

Message 

Cause 

Outputs 

“P1” 
 

Room probe  failure 

Compressor output according 
to par. “Con” and “COF” 

“P2” 

Evaporator probe  failure 

Defrost end is timed 

“HA” Maximum 

temperature alarm 

Outputs unchanged. 

“LA”  

Minimum temperature alarm 

Outputs unchanged. 

“dA” 

Door open 

Regulation restarts  

“EA”  

External alarm 

Output unchanged. 

“CA”  

Serious external alarm (i1F=bAL) 

All outputs OFF. 

“CA” 

Pressure switch alarm (i1F=PAL) 

All outputs OFF 

12.1  ALARM RECOVERY  

Probe alarms “

P1

” and “

P2

” start some seconds after the fault in the related probe; 

they automatically stop some seconds after the probe restarts normal operation. 
Check connections before replacing the probe. 
Temperature alarms “

HA

” and “

LA

” automatically stop as soon as the thermostat 

temperature returns to normal values and when defrost starts. 
Alarms 

“EA”

 and 

“CA” 

(with i1F=bAL)

 

recover as soon as the digital input is 

disabled. 
Alarm “

CA”

 (with i1F=PAL) recovers only by 

switching off and on

 the instrument. 

13. TECHNICAL 

DATA 

Housing: 

self extinguishing ABS.

 

Case: XR40C 

frontal 32x74 mm; depth 60mm; 

Mounting 

XR40C 

panel mounting in a 71x29mm panel cut-out 

Protection: 

IP20.

 

Frontal protection: 

IP65 with frontal gasket RG-C (optional). 

Connections: 

Screw terminal block 

 2,5 mm

2

 wiring. 

Power supply: 

according to the model: 12Vac/dc, ±10%; 24Vac/dc, ±10%;  

230Vac 

±

10%, 50/60Hz, 110Vac 

±

10%, 50/60Hz

 

Power absorption: 

3VA max

 

Display

: 3 digits, red LED, 14,2 mm high.  

Inputs

: 2 NTC or PTC probes. 

Digital input: 

free contact 

Relay outputs

 

 compressor: 

SPDT relay 8(3) A, 250Vac or  

 

SPST relay 20(8)A; 250Vac

 

 

defrost: 

SPDT relay 8(3) A, 250Vac 

Data storing

: on the non-volatile memory (EEPROM). 

Kind of action: 

1B; 

Pollution grade: 

normal; 

Software class: 

A.

 

Operating temperature: 

0÷60 °C. 

Storage temperature: 

-30÷85 °C.  

Relative humidity:

 20

÷

85% (no condensing) 

Measuring and regulation range:  

NTC probe: 

-40÷110°C (-40÷230°F) 

PTC probe: 

-50÷150°C (-58÷302°F) 

Resolution: 

0,1 °C or 1°C or 1 °F (selectable). 

Accuracy (ambient temp. 25°C)

:  ±0,7 °C ±1 digit 