4.5.3 Technical
specifications
4.5.3.1 Analogue inputs
Analogue conversion type:
10-bit A/D converter
Number of inputs:
7
Type of analogue input:
(configurable via software parameter)
NTC Dixell (-50T110°C; 10K
Ω
±1% at 25°C)
PTC Dixell(-55T115°C; 990
Ω
±1% at 25°C)
PT1000 Dixell (-100T150°C; 1K
Ω
at 0°C)
Digital input (potential free contact)
Voltage: 0 - V, 0 - 5V, 0 - 10V (input resistance 3.7K
Ω
)
Current: 0 - 20mA, 4 - 20mA (input resistance 100
Ω
)
Digital input status variation detection time:
100ms (in any case it depends on the cycle time set by the user in the
given application)
Accuracy:
NTC, PTC, PT1000: ±1°C
0-1V: ±20mV
0-5V: ±100mV
0-10V:±200mV
2-20mA, 4-20mA: ±0.30mA
Additional power:
+12V: 40mA max per terminal
+5v: 100mA
Notes:
Any inputs that are powered with a voltage that differs from that supplied
by the device (+12V or +5V) must be powered separately with another
transformer (do not use the same secondary of the controller's power) in
order to prevent the inputs from malfunctioning or being damaged.
4.5.3.2 Digital inputs
Type:
(configurable via software parameter)
Opto-insulated potential free contact
Number of inputs:
3
Digital input status variation detection time:
100ms (in any case it depends on the cycle time set by the user in the
given application)
Notes:
Do not use live contacts in order to prevent the inputs from being
damaged.
4.5.3.3 Analogue outputs
Type:
Non opto-insulated internal power
Number of outputs:
3
Type of analogue output:
(configurable via software parameter)
3 fixed outputs 0-10Vdc (Out1 - Out3)
Maximum load:
40mA (Out1 - Out3)
22
Ω
per live analogue output
Accuracy:
Out1 - Out3: ±2% full scale
Resolution:
8bit
Notes:
The electrical devices controlled by these analogue outputs must be
powered separately with another transformer (do not use the same
secondary of the controller's power) in order to prevent the outputs from
malfunctioning or being damaged.
4.5.3.4 Digital outputs
Type:
Relays with NO contacts
Number of outputs:
6
Type of output:
(configurable via software parameter)
Relays with normally open contact:
Maximum load:
5A(250Vac) SPST 5(2)A
Notes:
Verify the capacity of the output used. There is double insulation between
the digital outputs and the low voltage of the rest of the circuit.
The common relays of the outputs are separate and split into groups.
Different voltages can be used for different groups of relays but the same
voltage must be used within each group.
Summary of Contents for iPro SERIES
Page 1: ...iPro SERIES V 3 2 ...
Page 2: ......
Page 18: ...1592025700 IPROFAMILY stp GB 2012 08 08 doc iPro Series 18 72 4 1 3 6 Wiring diagrams ...