1592025700 IPROFAMILY stp GB 2012.08.08.doc
iPro Series
29/72
44
RL3
Relay 3 normally open contact
45
RL4
Relay 4 normally open contact
46
RL5
Relay 5 normally open contact
47
C
Common relays 5, 6, 7 and 8 (MAX 10A)
48
C
Common relays 5, 6, 7 and 8 (MAX 10A)
49
RL6
Relay 6 normally open contact
50
RL7
Relay 7 normally open contact
51
RL8
Relay 8 normally open contact
60
Remote Display
Connection for VISOGRAPH remote terminal (Vnr)
61
Remote Display
Connection for VISOGRAPH remote terminal (+)
62
Remote Display
Connection for VISOGRAPH remote terminal (-)
63
RS485 Slave
RS485 Slave connection (-)
64
RS485 Slave
RS485 Slave connection (+)
65 LAN
LAN
Connection
(-)
66 LAN
LAN
Connection
(+)
4.3.3 Technical
specifications
4.3.3.1 Analogue inputs
Analogue conversion type:
10-bit A/D converter
Number of inputs:
6
Type of analogue input:
(configurable via software parameter)
NTC Dixell (-50T110°C; 10K
Ω
±1% at 25°C)
PTC Dixell(-55T115°C; 990
Ω
±1% at 25°C)
Digital input (potential free contact)
Voltage: 0 - V, 0 - 5V, 0 - 10V (input resistance 3.7K
Ω
)
Current: 0 - 20mA, 4 - 20mA (input resistance 100
Ω
)
Digital input status variation detection time:
100ms (in any case it depends on the cycle time set by the user in the
given application)
Accuracy:
NTC, PTC: ±1
0-1V: ±20mV
0-5V: ±100mV
0-10V:±200mV
2-20mA, 4-20mA: ±0.30mA
Additional power:
+12V: 200mA in total (b12V and analogue outputs)
+5v: 100mA
Notes:
Any inputs that are powered with a voltage that differs from that supplied
by the device (+12V or +5V) must be powered separately with another
transformer (do not use the same secondary of the controller's power) in
order to prevent the inputs from malfunctioning or being damaged.
4.3.3.2 Digital inputs
Type:
(configurable via software parameter)
Opto-insulated live contact (24Vac/dc)
External power 24Vac/dc ±20%
Number of inputs:
11
Digital input status variation detection time:
100ms (in any case it depends on the cycle time set by the user in the
given application)
Notes:
Use another transformer (do not use the same secondary of the
controller's power) in order to prevent the inputs from malfunctioning or
being damaged.
Note: the digital inputs as dry contacts are available on request.
Summary of Contents for iPro SERIES
Page 1: ...iPro SERIES V 3 2 ...
Page 2: ......
Page 18: ...1592025700 IPROFAMILY stp GB 2012 08 08 doc iPro Series 18 72 4 1 3 6 Wiring diagrams ...
Page 20: ...1592025700 IPROFAMILY stp GB 2012 08 08 doc iPro Series 20 72 4 2 IPRO GENIUS IPG200D RANGE ...
Page 54: ...1592025700 IPROFAMILY stp GB 2012 08 08 doc iPro Series 54 72 5 1 4 Dimensions ...
Page 72: ...1592025700 IPROFAMILY stp GB 2012 08 08 doc iPro Series 72 72 ...