background image

dIXEL

 

Installing and Operating Instructions 

1592026000 

 

1592026000 XW20K GB R1.0 22.02.2008.doc 

                       

XW20K 

3/5 

 

SHy  Differential for auxiliary relay: 

(0,1÷25,5°C; 1÷45°F): Intervention differential for auxiliary relay 

set point, always positive.  

ArP  Probe selection for auxiliary

nP

 = aux relay is switched by digital input with i1F = AUS; 

P1 = 

Probe 1 (Thermostat probe); 

P2 = 

not set it; 

P3 = 

Probe 3 (display probe).; 

P4 = 

Probe 4 

Sdd  Auxiliary output working during defrost:  

n = 

the auxiliary output is switched off during defrost 

y = 

the auxiliary output goes on working during defrost  

ALARMS 
ALP Probe for temperature alarm setting: P1 = 

thermostat probe; P2 = evaporator probe; P3 = 

condenser 1 probe; P4 O condenser 2 probe. 

ALC Temperature alarm configuration 

rE

 = High and Low alarms related to Set Point  

Ab

 = High and low alarms related to the absolute temperature. 

ALU High temperature alarm setting:

  

 

ALC= rE, 0 

÷

 

50°C or 90°F 

 

ALC= Ab, ALL 

÷

 110°C or 230°F 

 

when this temperature is reached and after the ALd delay time the HA alarm is enabled. 

 

ALL  Low temperature alarm setting: 

ALC = rE , 0 

÷

 50 °C or 90°F;  

ALC = Ab , - 50°C 

or -58°F 

÷

 ALU when this temperature is reached and after the ALd delay time, the LA alarm is 

enabled. 

AFH Temperature alarm and fan differential: 

(0,1÷25,5°C; 1÷45°F) Intervention differential for 

temperature alarm set point and fan regulation set point, always positive.

 

ALd Temperature alarm delay:

 (0÷255 min) time interval between the detection of an alarm 

condition and the corresponding alarm signalling. 

dAo Delay of temperature alarm at start-up:

 (0min÷23h 50min) time interval between the detection 

of the temperature alarm condition after the instrument power on and the alarm signalling.

 

CONDENSER TEMPERATURE ALARM 
AP2  Probe selection for temperature alarm of condenser: nP

 = no probe; 

P1

 =thermostat probe; 

P2 = 

evaporator probe; 

P3

 =third probe; 

P4

 = fourth probe. 

AL2 Low temperature alarm of condenser

:

 

(-55÷150°C) when this temperature is reached the LA2 

alarm is signalled, possibly after the Ad2 delay. 

Au2 High temperature alarm of condenser

:

 

(-55÷150°C) when this temperature is reached the HA2 

alarm is signalled, possibly after the Ad2 delay. 

AH2 Differential for temperature condenser alarm recovery

:

 

(0,1÷25,5°C; 1÷45°F) 

Ad2 Condenser temperature alarm delay

: (0÷255 min) time interval between the detection of the 

condenser alarm condition and alarm signalling. 

dA2  Condenser temperature alarm exclusion at start up

: (from 0.0 min to 23.5h, res. 10min) 

bLL  Compressor off with low temperature alarm of condenser

:

 n = no: 

compressor keeps on 

working

; Y = yes, 

compressor is switched off till the alarm is present, in any case regulation 

restarts after AC time at minimum.

 

AC2 Compressor off with high temperature alarm of condenser

:

 n = no: 

compressor keeps on 

working

; Y = yes, 

compressor is switched off till the alarm is present, in any case regulation 

restarts after AC time at minimum.

 

RELAY OA3 (22-23) CONFIGURATION 
tbA  Alarm relay silencing (with oA3=ALr):  

n

= silencing disabled: alarm relay stays on till alarm condition lasts,  

=silencing enabled: alarm relay is switched OFF by pressing a key during an alarm 

oA3 Fourth relay configuration (22-23):

 

dEF: 

do not select it!.

; FAn: 

do not select it!.

; ALr

: alarm; 

Lig

: light;

 AuS

: Auxiliary relay; 

onF

: always on with instrument on; 

db = 

heating element for

 

neutral zone regulation; 

cP2 =

 second compressor, 

dF2: 

do not select it.

 

AoP Alarm relay polarity: 

it set if the alarm relay is open or closed when an alarm happens. 

CL

terminals 1-2 closed during an alarm; 

oP

 = terminals 1-2 open during an alarm

 

 

 

 

DIGITAL INPUT  
i1P  Digital input polarity: oP: 

the digital input is activated by opening the contact; 

CL: 

the digital 

input is activated by closing the contact.

 

i1F Digital input configuration: EAL 

= external alarm: “EA” message is displayed; 

bAL 

= serious 

alarm “CA” message is displayed. 

PAL 

= pressure switch alarm, “CA” message is displayed; 

dor

 

= door switch function; 

dEF

 = activation of a defrost cycle; 

AUS 

=to switch on and off the 22-23 

relay with oA3 = AUS; 

Htr 

= kind of action inversion (cooling – heating); 

FAn = not set it; ES = 

Energy saving. 

did

:

 

(0

÷

255 min) 

with

 

i1F= EAL or i1F = bAL digital input alarm delay:

 delay between the detection 

of the external alarm condition and its signalling. 

with

 

i1F= dor: door open signalling delay 

with i1F = PAL: time for pressure switch function: 

time interval to calculate the number of the 

pressure switch activation. 

nPS Pressure switch number:

 (0 

÷

15) Number of activation of the pressure switch, during the “

did

” 

interval, before signalling the alarm event (I2F= PAL).  

If the nPS activation in the did time is reached, switch off and on the instrument to restart 

normal regulation. 

odc  Compressor status when open door:

  

no;

 

Fan

 = normal; 

CPr; F_C 

= Compressor OFF.  

rrd  Outputs restart after doA alarm: no = 

outputs not affected by the doA alarm;  

yES = 

outputs 

restart with the doA alarm;  

HES Temperature increase during the Energy Saving cycle :

 (-30,0°C

÷

30,0°C/-22÷86°F) it sets 

the increasing value of the set point during the Energy Saving cycle.  

OTHER 
Adr   RS485 serial address 

(1÷247)

Identifies the instrument address when connected to a ModBUS 

compatible monitoring system. 

PbC Type of probe:

 it allows to set the kind of probe used by the instrument: 

PbC

 = PBC probe, 

ntc = 

NTC probe. 

onF  on/off key enabling: nu = 

disabled; 

oFF = 

enabled; 

ES = 

to start a energy saving cycle. 

dP3 Third probe display

optional

dP4 Fourth probe display

rSE  Real set point:

 it shows the set point used during the energy saving cycle or during the 

continuous cycle. 

rEL   Release software:

 (read only) Software version of the microprocessor. 

Ptb   Parameter table:

 (read only) it shows the original code of the 

dIXEL

 parameter map. 

 

7. Digital input 

The free voltage digital input is programmable in different configurations by the “

i1F

” parameter. 

DOOR SWITCH INPUT  (i1F = dor) 

It signals the door status and the corresponding relay output status through the “

odc

” parameter: 

no,

 

Fan

 = normal (any change); 

CPr,

 

F_C

 = Compressor OFF. 

Since the door is opened, after the delay time set through parameter “

did

”, the door alarm is enabled, 

the display shows the message “

dA

” and 

the regulation restarts is rtr = yES.

 The alarm stops as 

soon as the external digital input is disabled again. With the door open, the high and low temperature 

alarms are disabled. 

GENERIC ALARM (i1F = EAL) 

As soon as the digital input is activated the unit will wait for “

did

” time delay before signalling the “

EAL

” 

alarm message. The outputs status don’t change. The alarm stops just after the digital input is de-

activated. 

SERIOUS ALARM MODE (i1F = bAL) 

When the digital input is activated, the unit will wait for “

did

” delay before signalling the “

CA

” alarm 

message. The relay outputs are switched OFF. The alarm will stop as soon as the digital input is de-

activated. 

PRESSURE SWITCH (i1F = PAL) 

If during the interval time set by “

did

” parameter, the pressure switch has reached the number of 

activation of  the “

nPS

” parameter, the “

CA

” pressure alarm message will be displayed. The 

compressor and the regulation are stopped. When the digital input is ON the compressor is always 

OFF. 

If the nPS activation in the did time is reached, switch off and on the instrument to restart 

normal regulation. 

AUXILIARY OUTPUT SWITCHING  (i1F =AUS) 

With oA3 = AUS and i1F = AUX it switches the fourth relay (22-23). 

START DEFROST (i1F = dFr) 

It starts a defrost if there are the right conditions. After the defrost is finished, the normal regulation will 

restart only if the digital input is disabled otherwise the instrument will wait until the “MdF” safety time 

is expired. 

INVERSION OF  THE KIND OF ACTION: HEATING-COOLING (i1F = Htr) 

This function allows to invert the regulation of the controller: from cooling to heating and viceversa. 

ENERGY SAVING (i1F = ES) 

The Energy Saving function allows to change the set point value as the result of the SET+ HES 

(parameter) sum. This function is enabled until the digital input is activated. 

DIGITAL INPUTS POLARITY  

The digital input polarity depends on the “

i1P

” parameter. 

i1P=CL

: the input is activated by closing the contact.

 

i1P=OP

: the input is activated by opening the contact 

8.  Installation and mounting 

T620

 keyboard shall be mounted on vertical panel, in a 150x31 mm hole, and fixed using two screws 

 3 x 2mm. To obtain an IP65 protection grade use the front panel rubber gasket (mod. RG-L).  

V620

 keyboard shall be mounted on vertical panel, in a 72x56 mm hole, and fixed using two screws 

 

3 x 2mm. To obtain an IP65 protection grade use the front panel rubber gasket (mod. RGW-V). 

CX620

 keyboard shall be mounted on vertical panel, in a 29x71 mm hole, and fixed using the special 

bracket supplied.  

The controller 

XW20K

 shall be mounted in a din rail 

It must be connected to the keyboard by means of a two-wire cable (

 1mm). The temperature range 

allowed for correct operation is 0 - 60 °C. Avoid places subject to strong vibrations, corrosive gases, 

excessive dirt or humidity. The same recommendations apply to probes. Let the air circulate by the 

cooling holes. 

 

XW20K – 8 DIN CASE - DIMENSIONS 

 

 

9. Electrical connections 

XW20K

 is provided with screw terminal blocks to connect cables with a cross section up to 2,5 mm

for 

the RS485(optional) and the keyboard. Connecting other inputs, power supply and relays, 

XW20K

 is 

provided with Faston connections (6,3mm). Heat-resistant cables have to be used. Before connecting 

cables make sure the power supply complies with the instrument’s requirements. Separate the probe 

cables from the power supply cables, from the outputs and the power connections. Do not exceed the 

maximum current allowed on each relay, in case of heavier loads use a suitable external relay. 

N.B.

 Maximum current allowed for all the loads is 20A. 

9.1

 

PROBE CONNECTIONS 

The probes shall be mounted with the bulb upwards to prevent damages due to casual liquid 

infiltration. It is recommended to place the thermostat probe away from air streams to correctly 

measure the average room temperature. Place the defrost termination probe among the evaporator 

Summary of Contents for CX620

Page 1: ...e terminated before the end of the set time using the same activation key o for 3 seconds DEFROST Defrost is performed through a simple stop of the compressor Parameter IdF controls the interval between defrost cycles while its length is controlled by parameter MdF 3 3 DEFROST Defrost is performed through a simple stop of the compressor The parameters involved are to control the interval between d...

Page 2: ...OFF for 5 sec and the ON OFF LED is switched ON During the OFF status all the relays are switched OFF and the regulations are stopped if a monitoring system is connected it does not record the instrument data and alarms When the instrument is in stand by the keyboard displays oFF N B During the OFF status the Light and AUX buttons are active 5 11 TO SEE THE PROBE VALUES 1 Enter in Pr1 level 2 Para...

Page 3: ...cycle 30 0 C 30 0 C 22 86 F it sets the increasing value of the set point during the Energy Saving cycle OTHER Adr RS485 serial address 1 247 Identifies the instrument address when connected to a ModBUS compatible monitoring system PbC Type of probe it allows to set the kind of probe used by the instrument PbC PBC probe ntc NTC probe onF on off key enabling nu disabled oFF enabled ES to start a en...

Page 4: ...y Alarm EE flashes when a failure in the memory data occurs In such cases the alarm output is enabled 12 3 ALARM RECOVERY Probe alarms P1 probe1 faulty P3 and P4 they automatically stop 10s after the probe restarts normal operation Check connections before replacing the probe Temperature alarms HA LA HA2 and LA2 automatically stop as soon as the temperature returns to normal values Alarms EA and C...

Page 5: ...alarm n 0 Y 1 n Pr2 AC2 Compr off for condenser high temperature alarm n 0 Y 1 n Pr2 AUXILIARY OUTPUT tbA Alarm relay disabling n no y yes y Pr2 oA3 Fourth relay configuration ALr alarm dEF do not select it Lig Light AUS AUX onF always on Fan do not select it db do not select it dF2 do not select it Lig Pr2 AoP Alarm relay polarity oA3 ALr oP cL cL Pr2 DIGITAL INPUT i1P Digital input polarity oP o...

Reviews: