Installing and Operating Instructions 

1592026000 

 

1592026000 XW20K GB R1.0 22.02.2008.doc 

                       

XW20K 

2/5 

 

 

 

 

To enter the programming mode. 

 

 

 

 

To exit the programming mode.

 

5.1

 

USE OF LEDS 

Each LED function is described in the following table. 

LED 

MODE 

Function 

 

ON 

The compressor is running 

 

FLASHING 

- Programming Phase (flashing with LED 

- Anti-short cycle delay enabled 

 

FLASHING 

Programming Phase (flashing with LED 

 

ON 

The defrost is enabled 

 

FLASHING 

Drip time in progress 

 

ON 

The Fast Freezing cycle is enabled 

  

ON - 

ALARM 

signal 

- In “Pr2” indicates that the parameter is also present in “Pr1” 

 

ON 

Continuous cycle is running 

  ON 

Energy saving enabled 

 

ON Light 

on 

  ON 

Auxiliary relay on (CX620 only) 

°C/°F 

ON 

Measurement unit (CX620 only) 

 

5.2

 

HOW TO SEE THE MIN TEMPERATURE 

1.  

Press and release the 

n

 key. 

2.  

The “Lo” message will be displayed followed by the minimum temperature recorded. 

3. 

By pressing the 

n

 key or waiting for 5s the normal display will be restored. 

5.3

 

HOW TO SEE THE MAX TEMPERATURE 

1.  

Press and release the 

o

 key. 

2.  

The “Hi” message will be displayed followed by the maximum  temperature recorded. 

3. 

By pressing the 

o

 key or waiting for 5s the normal display will be restored. 

5.4

 

HOW TO RESET THE MAX AND MIN TEMPERATURE RECORDED 

To reset the stored temperature, when max or min temperature is displayed : 

1.

 

Press SET key until “rST” label starts blinking. 

 

N.B. After the installation RESET the temperature stored .

 

5.5

 

HOW TO SEE AND MODIFY THE SET POINT 

1.

 

Push and immediately release the 

SET 

key: the display will show the Set point value; 

2.

 

To change the Set value push the 

or 

n

 arrows within 10s. 

3.

 

To memorise the new set point value push the 

SET

 key again or wait 10s. 

5.6

 

TO START A MANUAL DEFROST  

 

 

1. Push 

the 

DEF 

key for more than 2 seconds and a manual defrost will start. 

5.7

 

TO ENTER IN PARAMETERS LIST “PR1”  

To enter the parameter list “Pr1” (user accessible parameters) operate as follows: 

 

 

1.  Enter the Programming mode by pressing the Set and DOWN key for 

few seconds (

 and 

 start blinking). 

2.  The instrument will show the first parameter present in “Pr1” 

THE HIDDEN MENU 

The hidden menu Includes all the parameters of the instrument. 

HOW TO ENTER THE HIDDEN MENU 

1.

 

Enter the Programming mode by pressing the 

Set

 + 

n

 keys for 3s (

 and 

 start blinking). 

2.

 

Released the keys, then push again the Set+

n

 keys for more than 7s. The Pr2 label will be 

displayed immediately followed from the HY parameter.  

NOW YOU ARE IN THE HIDDEN MENU.

 

3.

 

Select the required parameter. 

4.

 

Press the “

SET

” key to display its value 

5.

 

Use 

or 

n

 to change its value. 

6.

 

Press “

SET

” to store the new value and move to the following parameter. 

To exit

: Press 

SET + 

or wait 15s without pressing a key. 

NOTE1: 

if none parameter is present in Pr1, after 3s the “noP” message is displayed. Keep the keys 

pushed till the Pr2 message is displayed.  

NOTE2

: the set value is stored even when the procedure is exited by waiting the time-out to expire. 

 
HOW TO MOVE A PARAMETER FROM THE HIDDEN MENU TO THE FIRST 
LEVEL AND VICEVERSA. 

Each parameter present in the HIDDEN MENU can be removed or put into “THE FIRST LEVEL” (user 
level) by pressing 

“SET + 

n

.  

In HIDDEN MENU when a parameter is present in First Level the decimal point is on. 

5.8

 

HOW TO CHANGE THE PARAMETER VALUE 

1.

 

Enter the Programming mode. 

2.

 

Select the required parameter with 

o

 or 

n

3.

 

Press the “

SET

” key to display its value (

 and 

 LED starts blinking). 

4.

 

Use 

o

 or 

n

 to change its value. 

5.

 

Press “

SET

” to store the new value and move to the following parameter. 

To exit

: Press 

SET + UP 

or wait 15s without pressing a key. 

NOTE

: the new programming is stored even when the procedure is exited by waiting the time-out. 

5.9

 

HOW TO LOCK THE KEYBOARD 

 

 

1.  

Keep the 

o

 and 

n

 keys pressed together for more than 3 s the 

o

 and 

n

 keys. 

2.  

The “POF” message will be displayed and the keyboard is locked. At this point it is 
only possible the viewing of the set point or the MAX o Min temperature stored and 

to switch ON and OFF the light, the auxiliary output and the instrument. 

 

TO UNLOCK THE KEYBOARD 

 
Keep the 

o

 and 

n

 keys pressed together for more than 3s. 

 

5.10

 

ON/OFF FUNCTION (STAND BY) 

 

 

By pushing the 

ON/OFF

 key, the instrument shows “OFF” for 5 sec. and the ON/OFF LED 

is switched ON. 

During the OFF status, all the relays are switched OFF and the regulations are stopped; if 

a monitoring system is connected, it does not record the instrument data and alarms. 

When the instrument is in stand by the keyboard displays “oFF”. 

 

N.B. During the OFF status the Light and AUX buttons are active. 

 

5.11

 

TO SEE THE PROBE VALUES 

1. 

Enter in “

Pr1

” level. 

2.  Parameters “dP1”, “dP2” “dP3” and “dP4” display the value of probes 1, 2, 3 and 4.  

6. Parameter List 

REGULATION 
Hy Differential: 

(0,1÷25,5°C; 1÷45°F): Intervention differential for set point, always positive. 

Compressor Cut IN is Set Point Plus Differential (Hy). Compressor Cut OUT is when the 

temperature reaches the set point. 

LS  Minimum set point limit: 

(-50,0°C

÷

SET; -58°F÷SET) Sets the minimum value for the set point. 

US  Maximum set point limit: 

(SET

÷

110°C; SET÷230°F) Set the maximum value for set point. 

PROBE INPUTS 
Ot Thermostat 

probe 

calibration (term. 1-2): ( 

(-12.0

÷

12.0°C/ -21

÷

21°F) allows to adjust possible 

offset of the thermostat probe. 

P3P  Third probe presence (term. 4-5): n

= not present; 

y=

 present. 

O3  Third probe  calibration: 

(-12.0

÷

12.0°C/ -21

÷

21°F) allows to adjust offsets of the third probe. 

P4P  Fourth probe presence (term. 5-6): n

= not present; 

y=

 present. 

O4  Fourth probe  calibration: 

(-12.0

÷

12.0°C/ -21

÷

21°F) allows to adjust possible offsets of the 

fourth probe. 

OdS Outputs activation delay at start up:

 (0÷255 min) This function is enabled at the initial start up 

of the instrument and inhibits any output activation for the period of time set in the parameter. 

(AUX and Light can work) 

AC  Anti-short cycle delay: 

(0÷30 min) interval between the compressor stop and the following 

restart. 

AC1 Time delay between turning on compressor 2 :

 (0÷255 sec) allows to set the delay between 

turning on the first and the second compressor. It’s used with oA3 = cP2. 

CCt Thermostat override:

 (0min ÷23h 50min) allows to set the length of the continuous cycle. Can 

be used, for instance, when the room is filled with new products.

 

CCS Set point for continuous cycle: 

(-50÷150°C) it sets the set point used during the continuous 

cycle. 

Con Compressor ON time with faulty probe: 

(0÷255 min) time during which the compressor is 

active in case of faulty thermostat probe. With COn=0 compressor is always OFF. 

COF Compressor OFF time with faulty probe: 

(0÷255 min) time during which the compressor is off 

in case of faulty thermostat probe. With COF=0 compressor is always active. 

CH  Type of action: CL

 = cooling; 

Ht

 = heating.

 

DISPLAY 
CF  Temperature measurement unit:

 °C = Celsius; °F = Fahrenheit . When the measurement unit 

is changed the SET point and the values  of the regulation parameters have to be modified

 

rES Resolution (for °C)

: (in = 1°C; de = 0,1°C) allows decimal point display. 

dE

 = 0,1°C; 

in

 = 1 °C  

rEd  Remote display : 

select which probe is displayed by the remote display ( 

T620or CX620 or 

V620

)

 

(

P1; P2, P3, P4,  SET, dtr

): it selects which probe is displayed by the instrument: 

P1

 = 

Thermostat probe; 

P2

 = Evaporator probe; 

P3

 = Third probe(only for model with this option 

enabled); 

P4

 = Fourth probe,

 SET

 = set point;  ;  

dtr

 = not set it. 

dLy Display delay: 

(0 ÷20.0m; risul. 10s) when the temperature increases, the display is updated of 

1 °C/1°F after this time. 

DEFROST 
dFP  Probe selection for defrost termination: nP

 = no probe; 

P1

 =thermostat probe; 

P2 = 

not set it; 

P3

 =Third probe; 

P4

 = Fourth probe. 

dtE   Defrost termination temperature:

 (-50,0÷110,0°C; -58÷230°F) (Enabled only when the dFP = 

P3 or P4 and these probes are present) sets the temperature measured by the evaporator probe 

which causes the end of defrost. 

IdF Interval between defrosts: 

(1÷120h) Determines the time interval between the beginning of two 

defrost cycles. 

MdF  (Maximum) duration of defrost: 

(0÷255 min) When 

P2P = n

, no evaporator probe, it sets the 

defrost duration, when 

P2P = y

, defrost end based on temperature, it sets the maximum length 

for defrost. 

dFd  Display during defrost: rt

 = real temperature; 

it

 = temperature reading at the defrost start; 

Set

 = set point; 

dEF

 = “dEF” label;  

 dEG

 = “dEG” label;

 

dAd  Defrost display time out:

 (0

÷

255 min) Sets the maximum time between the end of defrost and 

the restarting of the real room temperature display. 

OA3 = AUS: AUXILIARY THERMOSTAT CONFIGURATION (terms. 22-23)  
ACH  Kind of regulation for auxiliary relay

Ht 

= heating; 

CL 

= cooling 

SAA  Set Point for auxiliary relay:

 (-50,0÷110,0°C; -58÷230°F) it defines the room temperature 

setpoint  to switch auxiliary relay.

 

Summary of Contents for CX620

Page 1: ...e terminated before the end of the set time using the same activation key o for 3 seconds DEFROST Defrost is performed through a simple stop of the compressor Parameter IdF controls the interval between defrost cycles while its length is controlled by parameter MdF 3 3 DEFROST Defrost is performed through a simple stop of the compressor The parameters involved are to control the interval between d...

Page 2: ...OFF for 5 sec and the ON OFF LED is switched ON During the OFF status all the relays are switched OFF and the regulations are stopped if a monitoring system is connected it does not record the instrument data and alarms When the instrument is in stand by the keyboard displays oFF N B During the OFF status the Light and AUX buttons are active 5 11 TO SEE THE PROBE VALUES 1 Enter in Pr1 level 2 Para...

Page 3: ...cycle 30 0 C 30 0 C 22 86 F it sets the increasing value of the set point during the Energy Saving cycle OTHER Adr RS485 serial address 1 247 Identifies the instrument address when connected to a ModBUS compatible monitoring system PbC Type of probe it allows to set the kind of probe used by the instrument PbC PBC probe ntc NTC probe onF on off key enabling nu disabled oFF enabled ES to start a en...

Page 4: ...y Alarm EE flashes when a failure in the memory data occurs In such cases the alarm output is enabled 12 3 ALARM RECOVERY Probe alarms P1 probe1 faulty P3 and P4 they automatically stop 10s after the probe restarts normal operation Check connections before replacing the probe Temperature alarms HA LA HA2 and LA2 automatically stop as soon as the temperature returns to normal values Alarms EA and C...

Page 5: ...alarm n 0 Y 1 n Pr2 AC2 Compr off for condenser high temperature alarm n 0 Y 1 n Pr2 AUXILIARY OUTPUT tbA Alarm relay disabling n no y yes y Pr2 oA3 Fourth relay configuration ALr alarm dEF do not select it Lig Light AUS AUX onF always on Fan do not select it db do not select it dF2 do not select it Lig Pr2 AoP Alarm relay polarity oA3 ALr oP cL cL Pr2 DIGITAL INPUT i1P Digital input polarity oP o...

Reviews: