Installing and Operating Instructions 

1592026000 

 

1592026000 XW20K GB R1.0 22.02.2008.doc 

                       

XW20K 

1/5 

 

XW20K AND T620 – V620 – CX620 

1. GENERAL WARNING 

PLEASE READ BEFORE USING THIS MANUAL 

 

This manual is part of the product and should be kept near the instrument for easy and quick 

reference. 

 

The instrument shall not be used for purposes different from those described hereunder. It 

cannot be used as a safety device. 

 

Check the application limits before proceeding. 

 SAFETY PRECAUTIONS 

 

Check the supply voltage is correct before connecting the instrument. 

 

Do not expose to water or moisture: use the controller only within the operating limits avoiding 

sudden temperature changes with high atmospheric humidity to prevent  formation of 

condensation 

 

Warning: disconnect all electrical connections before any kind of maintenance. 

 

Fit the probe where it is not accessible by the End User. The instrument must not be opened. 

 

In case of failure or faulty operation send the instrument back to the distributor or to “Dixell 

S.p.A.” (see address) with a detailed description of the fault. 

 

Consider the maximum current which can be applied to each relay (see Technical Data). 

 

Ensure that the wires for probes, loads and the power supply are separated and far enough from 

each other, without crossing or intertwining. 

 

In case of applications in industrial environments, the use of mains filters (our mod. FT1) in 

parallel with inductive loads could be useful. 

2.  General description  

Model 

XW20K

 is microprocessor based controller suitable for applications on normal or medium 

temperature refrigerating units. It has to be connected by means of a two-wire cable (

 1mm) at a 

distance of up to 30 meters to the keyboard 

T620 

or 

V620

 or 

CX620

.  

It is provided with two relay outputs to control compressor and light. It is also provided with 3 NTC 

probe inputs, one for temperature control, one to control the defrost end temperature of the evaporator 

and the third to control condenser  temperature or to display another temperature. 

The HOT KEY output allows to connect the unit, by means of the external module XJ485-CX,  to a 

network line 

ModBUS-RTU

 compatible such as the 

dIXEL 

monitoring units  of X-WEB family. It 

allows to program the controller by means the HOT KEY programming  keyboard.  

The instrument is fully configurable through special parameters that can be easily programmed 

through the keyboard. 

3. Controlling loads 

3.1

 

THE COMPRESSOR 

The regulation is performed according to the temperature measured by the thermostat probe with a 

positive differential from the set point: if the temperature increases and reaches set point plus 

differential the compressor is started and then turned off when the temperature reaches the set point 

value again. 

In case of fault in the thermostat probe the start and stop of the compressor are timed through 

parameters “

COn

” and “

COF

”. 

The relay of the second compressor is activated in parallel with the relay of the first compressor, with a 

possible delay set in the 

AC1 

parameter. Both the compressors are switched off at the same time. 

3.2

 

FAST FREEZING 

When defrost is not in progress, it can be activated by holding the “

o

” key pressed for about 3 

seconds. The compressor operates to maintain the “

ccS

” set point for the time set through the “

CCt

” 

parameter. The cycle can be terminated before the end of the set time using the same activation key 

o

” for 3 seconds. 

DEFROST  

Defrost is performed through a simple stop of the compressor. Parameter “

IdF

” controls the interval 

between defrost cycles, while its length is controlled by parameter “

MdF

”. 

3.3

 

DEFROST 

Defrost is performed through a simple stop of the compressor. The parameters involved are: to control 

the interval between defrost cycles (IdF), its maximum length (MdF) and two defrost modes: timed or 

controlled by the evaporator’s probe (dFP and P3P). At the end of defrost dripping time is started, its 

length is set in the FSt parameter. With FSt =0 the dripping time is disabled. 

4.  Relay 22-23 configuration- special functions 

By means of the parameter 

oA3

, it’s possible to configure the functions of the light relay (22-23), as 

described in the following paragraphs: 

OA3 = LIG: LIGHT RELAY (FACTORY SETTING) 

By setting oA3 = Lig the relay will work as light relay, it is switched on and off by the light button on the 

keyboard and is affected by status of the digital input when i1F = dor. 

 

OA3 = CP2 2

ND

 COMPRESSOR MANAGEMENT  

By setting oA3 = cP2, the relay at terminals 22-23 will operate as “second compressor”.  It will be 

activated in parallel with the relay of the first compressor, with a possible delay set in the 

AC1 

parameter (seconds). Both the compressors are switched off at the same time. 

 

OA3 = ONF: ON –OFF   RELAY  

By setting oA3 =onF, the relay will operate as “on-off” relay: it will be activated when the controller is 

switched on and it will be switched off when the controller is in stand-by status. 

 

OA3 = AUS: AUXILIARY RELAY 

By setting oA3 = AUS, the relay 22-23 will work as auxiliary thermostat (I.E.. anti condensing heater). 

Parameters involved:  

-

 

ACH (cL, Ht): 

Kind of regulation for the auxiliary relay: 

Ht =

 heating /

 CL = 

cooling

-

 

SAA (-50÷150) 

Set point for auxiliary relay  

-

 

SHy (0÷25.5°C)

 Differential for auxiliary output.  

o

 

With ACH = CL: aux relay 

cut in

 is SAA+SHy, cut out SAA. 

o

 

With ACH = Ht: aux relay 

cut in

 is SAA-SHy, cut out SAA. 

-

 

ArP (nP, P1, P2, P3, P4) 

Probe for auxiliary relay  

-

 

Sdd (n, Y) 

Auxiliary output working during defrost

 

OA3 = ALR: ALARM RELAY 

By setting oA3 = ALr the relay will work as alarm relay, it is switched on when an alarm happens. 

Parameters involved:  

-

 

tbA (n, y) 

Alarm relay silencing 

-

 

AoP (cL; oP) 

  Alarm relay polarity 

OA3 = DB: NEUTRAL ZONE 

By setting 

oA3 = db

 the controller will perform a 

“neutral zone” regulation. 

The heating element has to be connected to the 

oA3 relay (22-23) 

If the temperature increases and reaches set 

point plus differential (

+HY

) the 

compresso

r is 

started and then turned off when the 

temperature reaches the set point value again.  

If the temperature decreases and reaches the 

set point minus differential( 

-HY

) the oA3 output 

(

heater

) is switched on and then turned OFF 

when the temperature reaches again the set 

point.   

 

 

5. Keyboards 

T620 

 

 

V620 

 

CX620 

 

 

 

To display and modify target set point; in programming mode it selects a parameter 

or confirm an operation. By holding it pressed for 3s when max or min temperature 

is displayed it will be erased. 

 

 

To see the max. stored temperature; in programming mode it browses the 

parameter codes or increases the displayed value.  

By holding it pressed for 3s the fast freezing  cycle is started. 

 

 

 

To see the min stored temperature; in programming mode it browses the parameter 

codes or decreases the displayed value. 

 

  

 

 

By holding it pressed for 3s the defrost is started. 

 

 

 

 

Switch ON and OFF the cold room light. 

 

 

 

Switch ON and OFF the instrument. 

 

KEY COMBINATIONS 

 

 

 

 

To lock and unlock the keyboard.

 

Summary of Contents for CX620

Page 1: ...e terminated before the end of the set time using the same activation key o for 3 seconds DEFROST Defrost is performed through a simple stop of the compressor Parameter IdF controls the interval between defrost cycles while its length is controlled by parameter MdF 3 3 DEFROST Defrost is performed through a simple stop of the compressor The parameters involved are to control the interval between d...

Page 2: ...OFF for 5 sec and the ON OFF LED is switched ON During the OFF status all the relays are switched OFF and the regulations are stopped if a monitoring system is connected it does not record the instrument data and alarms When the instrument is in stand by the keyboard displays oFF N B During the OFF status the Light and AUX buttons are active 5 11 TO SEE THE PROBE VALUES 1 Enter in Pr1 level 2 Para...

Page 3: ...cycle 30 0 C 30 0 C 22 86 F it sets the increasing value of the set point during the Energy Saving cycle OTHER Adr RS485 serial address 1 247 Identifies the instrument address when connected to a ModBUS compatible monitoring system PbC Type of probe it allows to set the kind of probe used by the instrument PbC PBC probe ntc NTC probe onF on off key enabling nu disabled oFF enabled ES to start a en...

Page 4: ...y Alarm EE flashes when a failure in the memory data occurs In such cases the alarm output is enabled 12 3 ALARM RECOVERY Probe alarms P1 probe1 faulty P3 and P4 they automatically stop 10s after the probe restarts normal operation Check connections before replacing the probe Temperature alarms HA LA HA2 and LA2 automatically stop as soon as the temperature returns to normal values Alarms EA and C...

Page 5: ...alarm n 0 Y 1 n Pr2 AC2 Compr off for condenser high temperature alarm n 0 Y 1 n Pr2 AUXILIARY OUTPUT tbA Alarm relay disabling n no y yes y Pr2 oA3 Fourth relay configuration ALr alarm dEF do not select it Lig Light AUS AUX onF always on Fan do not select it db do not select it dF2 do not select it Lig Pr2 AoP Alarm relay polarity oA3 ALr oP cL cL Pr2 DIGITAL INPUT i1P Digital input polarity oP o...

Reviews: