Operating Instructions 

cod. 1592017410 

 

1592017410  XLH360 GB r1.0  15.04.2005.doc 

XLH360 

5/16 

7.

 

MATURING CYCLE WITH DRIPPING, RUNNING AND STOPPING PHASE. 

Dripping

Running

Stopping

Running

Stopping

 

The diagrams displays a typical maturing cycle with the starting dripping phase. 

DRIPPING PHASE

 lasts for the “

dri

” time, without  humidity control, temperature set is SETG 

RUNNING PHASE

 lasts for the 

“on”

 time, both temperature and humidity are controlled.  

STOPPING PHASE

 lasts for the 

“off”

 time, without any control of temperature and humidity.  

The end of the stopping phase is signalled by the internal buzzer and by the “End” message on the display. 

After 

the 

STOPPING PHASE

 the behaviour of the controller depends on the parameter 

trc, 

 according to the following settings: 

trc

 = 

co 

controller maintains the set points of the running phase 

trc

 = 

in 

controller stop the regulation at all. 

trc

 = 

cL 

controller performs the running and stopping phase till is stopped manually. 

trc

 = 

cLE 

 as (

trc

 = 

cL

) plus at the end of each cycle the 

End

 label is displayed and the buzzer is switched on. 

7.1

 

 HOW TO SET THE DURATION OF THE DRIPPING, RUNNING AND STOPPING PHASES 

1.

 

Push the 

CLOCK

 key, the display shows on the bottom display the “dri” message, while the “hourglass” start flashing. 

2.

 

Push again the 

CLOCK

 the duration of the dipping phase is shown, hh:mm. 

3.

 

To set the duration push the 

UP 

 and 

DOWN

 keys.  

4.

 

Push again the 

CLOCK

 to confirm the time and pass to the setting of the running phase: the “on” message is displayed. 

5.

 

Push the 

CLOCK

 key to see its duration and use the 

UP

 and 

DOWN

 keys to set it. 

6.

 

Push again the 

CLOCK

 to confirm the time and pass to the setting of the stopping phase: the “oFF” message is displayed. 

7.

 

Push the 

CLOCK

 key to see its duration and use the 

UP

 and 

DOWN

 keys to set it. 

8.

 

Confirm the value by pushing again the 

CLOCK 

key and pass to the humidity display. 

7.2

 

HOW TO SET THE TARGET HUMIDITY OF THE RUNNING CYCLE 

1.

 

Push the 

SET %RH

 key, the display shows on the bottom display the “SH1” message, while the “set” icon starts flashing. 

2.

 

Push again the 

SET %RH

 the humidity set point of the running phase is shown. Set it using the 

UP 

 and 

DOWN

 keys. To 

disable

 the 

humidity control during the freezing phase set it to “

nu

”. 

3.

 

Push again the 

SET %RH

 to confirm the value and pass to the humidity display. 

7.3

 

HOW TO SET THE TARGET TEMPERATURE OF THE DRIPPING AND RUNNING PHASES 

1.

 

Push the 

SET TEMP

 key, the display shows on the upper display the “StG” message, while the “set ” icon starts flashing. 

2.

 

Push again the 

SET TEMP

 the temperature set point of the 

running

 phase is shown. Set it using the 

UP 

 and 

DOWN

 keys.  

3.

 

Push again the 

SET TEMP

 to confirm the value and pass to the setting of the 

dripping

 phase: the “St1” message is displayed. 

4.

 

Push the 

SET TEMP

 key to see its value and use the 

UP

 and 

DOWN

 keys to set it. 

7.4

 

HOW TO START THE CYCLE 

Push and release 

START 

 key: the led 

 will be turned ON. 

The 

 led flashes during the proving phase 

7.5

 

END OF THE CYCLE   

When the timer has expired, the buzzer starts sounding and the bottom display shows the “

End

” message. 

To mute the buzzer push a key: The display come back to show the humidity and the LED of the START key is turned off. 

7.6

 

HOW TO STOP THE CYCLE MANUALLY 

To stop the cycle manually push the 

ON/OFF 

key

7.7

 

HOW TO MODIFY THE SETTING OF THE CURRENT CYCLE WHILE IT’S RUNNING 

To modify the setting of the running cycle temperature (SET TEMP), humidity (SET %RH) or remaining time (CLOCK): 

Summary of Contents for COOL MATE XLH360

Page 1: ...XEL Operating Instructions cod 1592017410 1592017410 XLH360 GB r1 0 15 04 2005 doc XLH360 1 16 Temperature and humidity controller for seasoning maturing cabinets XLH360 COOL MATE Operating Instructio...

Page 2: ...SPLAY________________________________________________________________ 6 9 PARAMETER LIST ____________________________________________________________ 8 10 DIGITAL INPUT _______________________________...

Page 3: ...It has 2 NTC inputs one for thermostat the other one for defrost It s also present a 4 20mA input for humidity There is one digital input free contact configurable by parameter An output allows the u...

Page 4: ...ay By setting the parameter tHu db the de humidifying action is performed by enabling the de humidifier relay when the humidity is higher than SET RH dbH The relay is switch off when humidity comes ba...

Page 5: ...time and pass to the setting of the stopping phase the oFF message is displayed 7 Push the CLOCK key to see its duration and use the UP and DOWN keys to set it 8 Confirm the value by pushing again th...

Page 6: ...nd modify target humidity set point SET RH of the running SH1 phase in programming mode it selects a parameter or confirm an operation In programming mode it browses the parameter codes or increases t...

Page 7: ...con starts flashing 2 To change the Set value push the o or n arrows within 10s 3 To memorise the new set point value push the SET key again or wait 10s 8 3 TO START A MANUAL DEFROST 1 Push the DEF ke...

Page 8: ...MP dbt value and disabled when the SET TEMP is reached dbH half dead band width for humidity 0 5 25 5RH this band is place below and above the humidity set point SET RH The dehumidifying action is ena...

Page 9: ...e alarm setting ALC rE 0 50 C or 90 F ALC Ab 50 C or 58 F ALU when this temperature is reached and after the ALd delay time the LA alarm is enabled ALU High temperature alarm setting ALC rE 0 50 C or...

Page 10: ...dEF defrost relay Adt RS485 serial address for temperature loads 0 247 identifies the instrument within a control or supervising system AdH RS485 serial address for humidity loads 0 247 identifies the...

Page 11: ...s on the i1P parameters CL the digital input is activated by closing the contact OP the digital input is activated by opening the contact 11 INSTALLATION AND MOUNTING The temperature range allowed for...

Page 12: ...s or pipepresses using the centres signed in the bottom cover of the Cool Mate Fig 3 H I Then make 3 holes in the wall as indicated in Fig 3 L M N to fix the Cool Mate 4 Fix the cablepresses and the p...

Page 13: ...supply complies with the instrument s requirements Separate the probe cables from the power supply cables from the outputs and the power connections Do not exceed the maximum current allowed on each r...

Page 14: ...he probe Temperature alarms HA and LA automatically stop as soon as the thermostat temperature returns to normal values or when the defrost starts Humidity alarms HHA and LHA automatically stop as soo...

Page 15: ...cF C Pr2 Measurement unit C F rES dE Pr2 Resolution for C in integer dE decimal rEH Hd Pr2 Resolution for RH in integer Hd half digit trC co Pr2 Instrument behaviour at the end of the cycle co start h...

Page 16: ...o3 0 0 Pr1 Humidity probe calibration 10 10 P2P YES Pr2 Evaporator probe presence no absent YES present P3P YES Pr2 Humidity probe presence no absent YES present Lci 0 0 Pr2 Readout with 4 mA 999 999...

Reviews: