XLH360 

14/16 

NOTE 

the message “

Err

” is displayed for failed programming. In this case turn the unit off and then on if you want to restart the download again or 

remove the “

Hot key

” to abort the operation. 

15.

 

ALARM SIGNALLING 

Message  Cause 

Outputs 

“P1”   Thermostat probe failure 

Compressor and heating outputs off 

“P2”   Evaporator probe failure 

Defrost and by time 

“P3” 

Humidity  probe failure 

Humidity regulation off 

“HA” 

High temperature alarm 

Outputs unchanged 

“LA” 

Low temperature alarm 

Outputs unchanged 

“HHA”  High humidity alarm 

Outputs unchanged 

“HLA”  Low humidity alarm 

Outputs unchanged 

“dA” 

Door switch alarm 

Outputs depending on the odC parameter 

“EAL”  External alarm 

Other outputs unchanged 

“BAL”  Serious external alarm 

Outputs OFF 

“PAL” Pressure 

switch alarm 

Outputs OFF

 

 
The alarm message is displayed until the alarm condition recoveries. 
All the alarm messages are showed alternating with the room temperature except for the “

P1

” which is flashing. To reset the “EE” alarm and restart 

the normal functioning press any key, the “

rSt

” message is displayed for about 3s. 

15.1

 

SILENCING BUZZER 

Once the alarm signal is detected the buzzer, if present, can be silenced by pressing any key.  

15.2

 

ALARM RECOVERY 

Probe alarms

 : “

P1

” (probe1 faulty), “

P2

”, “

P3

”; they automatically stop 10s after the probe restarts normal operation. Check connections before 

replacing the probe. 

Temperature alarms

 “

HA

” and “

LA

” automatically stop as soon as the thermostat temperature returns to normal values or when the defrost starts. 

Humidity alarms

 “

HHA

” and “

LHA

” automatically stop as soon as the humidity returns to normal values. 

Door switch alarm

 “

dA

”  stop as soon as the door is closed. 

External alarms

 “

EAL

”, “

BAL

”  stop as soon as the external digital input is disabled  

Pressure switch alarm 

PAL” alarm is recovered by switching OFF the instrument

10.

 

TECHNICAL DATA 

Housing: 

self extinguishing ABS; 

Case: 

frontal 210x230 mm; depth 87mm; 

Mounting:

 See par. 11; 

Protection:

 IP65  

Connections: 

Screw terminal block 

 2,5 mm

2

 wiring. 

Power supply: 

230Vac 50/60Hz 

±

 10% or 110Vac 50/60Hz 

±

 10%; 

Power absorption: 10

VA max.

 

Display

:3 digits, red LED, 30.5 mm high. 3 digits, yellow LED low. 

Inputs

: 2 NTC, 1 input 4 ÷ 20mA; 

Digital inputs : 

Door switch and configurable, free voltage. Max. distance 10m;

 

Relay outputs:

 

compressor:

 relay SPST 20(8) A, 250Vac; 

defrost or extraction fans:

 relay SPDT 16(3) A, 250Vac  

fans:

 relay SPST 8(3) A, 250Vac;

 

heater control:

 relay SPDT 20 A, 250Vac; 

 Humidifying:

 relay SPST 8 A, 250Vac 

 

Light / De- humidifying: 

relay SPST 16 A, 250Vac  

Other output : 

 

Alarm buzzer

 (Standard) 

 

Direct RS485 

(optional)

 

Serial output :

 TTL standard  

Communication protocol:

 Modbus - RTU

 

Data storing

: on the non-volatile memory (EEPROM). 

Internal clock back-up:

 24 hours 

Kind of action: 

1B; 

Pollution grade: 

normal; 

Software class: 

A.

 

Operating temperature: 

0÷60 °C. 

Storage temperature: 

-25÷60 °C.  

Relative humidity:

 20

÷

85% (no condensing) 

Measuring and regulation range: NTC probe: 

-40÷110°C (-58÷230°F) 

Resolution: 

0,1 °C or 1°C or 1 °F (selectable). 

Accuracy (ambient temp. 25°C)

:  ±0,5 °C ±1 digit 

Summary of Contents for COOL MATE XLH360

Page 1: ...XEL Operating Instructions cod 1592017410 1592017410 XLH360 GB r1 0 15 04 2005 doc XLH360 1 16 Temperature and humidity controller for seasoning maturing cabinets XLH360 COOL MATE Operating Instructio...

Page 2: ...SPLAY________________________________________________________________ 6 9 PARAMETER LIST ____________________________________________________________ 8 10 DIGITAL INPUT _______________________________...

Page 3: ...It has 2 NTC inputs one for thermostat the other one for defrost It s also present a 4 20mA input for humidity There is one digital input free contact configurable by parameter An output allows the u...

Page 4: ...ay By setting the parameter tHu db the de humidifying action is performed by enabling the de humidifier relay when the humidity is higher than SET RH dbH The relay is switch off when humidity comes ba...

Page 5: ...time and pass to the setting of the stopping phase the oFF message is displayed 7 Push the CLOCK key to see its duration and use the UP and DOWN keys to set it 8 Confirm the value by pushing again th...

Page 6: ...nd modify target humidity set point SET RH of the running SH1 phase in programming mode it selects a parameter or confirm an operation In programming mode it browses the parameter codes or increases t...

Page 7: ...con starts flashing 2 To change the Set value push the o or n arrows within 10s 3 To memorise the new set point value push the SET key again or wait 10s 8 3 TO START A MANUAL DEFROST 1 Push the DEF ke...

Page 8: ...MP dbt value and disabled when the SET TEMP is reached dbH half dead band width for humidity 0 5 25 5RH this band is place below and above the humidity set point SET RH The dehumidifying action is ena...

Page 9: ...e alarm setting ALC rE 0 50 C or 90 F ALC Ab 50 C or 58 F ALU when this temperature is reached and after the ALd delay time the LA alarm is enabled ALU High temperature alarm setting ALC rE 0 50 C or...

Page 10: ...dEF defrost relay Adt RS485 serial address for temperature loads 0 247 identifies the instrument within a control or supervising system AdH RS485 serial address for humidity loads 0 247 identifies the...

Page 11: ...s on the i1P parameters CL the digital input is activated by closing the contact OP the digital input is activated by opening the contact 11 INSTALLATION AND MOUNTING The temperature range allowed for...

Page 12: ...s or pipepresses using the centres signed in the bottom cover of the Cool Mate Fig 3 H I Then make 3 holes in the wall as indicated in Fig 3 L M N to fix the Cool Mate 4 Fix the cablepresses and the p...

Page 13: ...supply complies with the instrument s requirements Separate the probe cables from the power supply cables from the outputs and the power connections Do not exceed the maximum current allowed on each r...

Page 14: ...he probe Temperature alarms HA and LA automatically stop as soon as the thermostat temperature returns to normal values or when the defrost starts Humidity alarms HHA and LHA automatically stop as soo...

Page 15: ...cF C Pr2 Measurement unit C F rES dE Pr2 Resolution for C in integer dE decimal rEH Hd Pr2 Resolution for RH in integer Hd half digit trC co Pr2 Instrument behaviour at the end of the cycle co start h...

Page 16: ...o3 0 0 Pr1 Humidity probe calibration 10 10 P2P YES Pr2 Evaporator probe presence no absent YES present P3P YES Pr2 Humidity probe presence no absent YES present Lci 0 0 Pr2 Readout with 4 mA 999 999...