Motor Mounting

Motor must be securely fastened to a rigid, flat surface to prevent vibration and minimize noise. For secure 
mounting use high-quality bolts of the largest possible diameter.

Belt-drive sheaves must be in-line. Use a straight edge to check. Do not over-tighten belts.

Direct coupled installations require a careful check of shaft and coupling alignment, shaft offset and/or angular 
misalignment should be less than .002”. Shim motor base as necessary. Do not depend on a flexible coupling to 
compensate for misalignment.

MOTOR

25 - 50 FEET

100 FEET

150 - 200 FEET

HP

200V

230V

460V

200V

230V

460V

200V

230V

460V

0.25

14 

14(16)*  14(18)* 

12

12

14(18)* 

8

10

14(18)*

0.50

14 

14(16)*  14(18)* 

12

12

14(18)* 

8

10

14(18)*

0.75

14 

14(16)*  14(18)* 

12

12

14(18)* 

8

10

14(18)*

1.00

14 

14(16)*  14(18)* 

12

12

14(18)* 

8

10

14(16)*

1.50

12

14

14(18)*

10

10

14(16)*

6

8

14

2.00

12

12

14(18)*

8

10

14(16)*

6

6

12

3.00

10

12

14(18)*

6

8

14

4

6

12

5.00

8

10

14(16)*

4

6

12

2

4

10

7.50

6

8

14

4

4

10

1

2

8

10

6

6

12

3

4

10

1/0

2/0

4

15

4

4

10

1

2

8

3/0

2/0

4

20

3

4

10

1/0

1

6

4/0

3/0

4

25

2

3

8

2/0

1/0

6

250kcmil

4/0

3

30

1

3

8

3/0

1/0

6

300kcmil

4/0

3

40

1/0

1

8

4/0

3/0

4

400kcmil

300kcmil

1

50

2/0

1

6

250kcmil

3/0

3

500kcmil

350kcmil

1

60

3/0

1/0

6

300kcmil

4/0

3

600kcmil

400kcmil

1/0

75

4/0

2/0

4

350kcmil

250kcmil

2

700kcmil

500kcmil

2/0

100

250kcmil

3/0

4

500kcmil

350kcmil

1

900kcmil

700kcmil

3/0

125

300kcmil

4/0

3

600kcmil

400kcmil

1/0

1250kcmil

800kcmil

4/0

150

350kcmil 250kcmil

2

700kcmil

500kcmil

2/0

1500kcmil

900kcmil

250kcmil

200

500kcmil 350kcmil

1/0

1250kcmil 800kcmil

4/0

1750kcmil

1250kcmil

350kcmil

250

600kcmil 400kcmil

2/0

1500kcmil 900kcmil

250kcmil 2000kcmil

1500kcmil

400kcmil

Table A - Minimum Wire Sizes for 3- Phase Motors

NOTE:

 kcmil denotes thousand circular mils. AWG sizes formerly given in MCM.

(*) Type S, SO, SJ, SJO, etc. flexible cable wire sizes. See NEC article 400 for ampacity.

Summary of Contents for D MISTER

Page 1: ...IL MIST COLLECTOR Visit our Website for more information on this product www diversitech air com www diversitech ca 1200 55th Avenue Montreal Quebec H8T 3J8 Tel 1 800 361 3733 Fax 1 514 631 9480 info...

Page 2: ...lacement Parts 6 Optional Direct Drive Replacement Parts 7 3 Phase Electrical Diagram 8 Motor Mounting 9 Connecting Power to Motor 10 Motor Troubleshooting Chart 11 Blower Operation 12 Notes 14 TERMS...

Page 3: ...of any liability if this unit is not used according to this manual Do not use the Air Cleaner for an application other than for which it was intended Consult your distributor Applicable Codes or call...

Page 4: ...8 2 9 FLA 3 0 HP 230 460 3 60 8 6 4 3 FLA 3 4 HP 3000 CFM 6 W G Direct drive BI options available 2 0 HP 3500 CFM 1 0 W G 3 0 HP 4500 CFM 85 W G 10 x 10 Forward Curve Blower Belt Drive 3 4 Direct Driv...

Page 5: ...eets all applicable building codes Each unit is supplied with a 1 1 4 NPT drain in the sump of the unit The drain must be correctly connected to the machine tool sump or external reservoir prior to op...

Page 6: ...6 REPLACEMENT PARTS FIGURE 4...

Page 7: ...7 OPTIONAL DIRECT DRIVE REPLACEMENT PARTS...

Page 8: ...single phase units motor rotation can be reversed by switching the black and red leads in the motor Three phase motors can be reversed by switching leads L1 and L2 VERIFY rotation before operating th...

Page 9: ...2 00 12 12 14 18 8 10 14 16 6 6 12 3 00 10 12 14 18 6 8 14 4 6 12 5 00 8 10 14 16 4 6 12 2 4 10 7 50 6 8 14 4 4 10 1 2 8 10 6 6 12 3 4 10 1 0 2 0 4 15 4 4 10 1 2 8 3 0 2 0 4 20 3 4 10 1 0 1 6 4 0 3 0...

Page 10: ...as possible to minimize voltage drop Long or inadequately sized cords especially on hard starting loads can cause motor failure All electrical connections in system must be secure to prevent voltage...

Page 11: ...ils to start 1 Blown fuses 2 Voltage too low at motor terminals due to line drop 3 Overload in motor starter tripped 4 Overload internal thermal protector tripped 5 Improper line connections 6 Motor m...

Page 12: ...ee lines should be balanced within 1 Balance single phase loads 5 Clean tighten or replace 6 Check voltage at motor should not be more than 10 above or below rated 7 Repair or replace Motor Troublesho...

Page 13: ...er s Unit fails to operate 1 Blown fuse or open circuit breaker 2 Broken fan belt 3 Defective motor and or capacitor 1 Replace or reset 2 Replace 3 Replace Motor overheats while running under load 1 B...

Page 14: ...14 NOTES...

Page 15: ...15 NOTES...

Page 16: ...16 NOTES...

Page 17: ...17 NOTES...

Page 18: ...spect of Units or a Third Party Product caused or arising directly or indirectly as a result of the integration with or use of Units in connection with any Third Party Product 2 5 You hereby expressly...

Page 19: ...ll be subject to and governed by the laws of the Province of Quebec and the laws of Canada applicable therein 6 2 The parties hereto expressly submit attorn and consent to the exclusive jurisdiction o...

Page 20: ...1200 55th Avenue Montreal Quebec H8T 3J8 Email info diversitech ca An Absolent Group Company For full product support visit our website https bit ly 2q7UC4v Scan above on mobile...

Reviews: