All aspects of the installation must 
conform to requirements of the NEC, 
and any applicable local codes.

The pump safety switch should be used 
on 24V Class II control circuits only.  The 
pump safety switch connections are 
available on standard ¼” quick connect 
terminals located on the top cover.    
Two wires with pre-crimped connectors may be plugged onto the 
COMMON and RUN terminals and wired into the 24 Volt thermostat circuit 
to shut off A/C systems should an overflow condition occur.    The Safety 
Switch operates with or without power provided to the pump.  An optional 
alarm or remote trouble light may be connected.

The third terminal of the safety switch closes when the water exceeds the 
high level limit.   This terminal be connected to a light or buzzer to indicate 
system trouble.

Apply power by plugging in the pump. Check for green LED indication the 
power is available.  Test float and safety switch by manually filling the tank 
or manually operating the float.  (see disassembly below)

Test Safety Switch operation (if used) to be sure that the A/C system shuts 
down and the red ALARM LED lights when the pump has reached an 
overflow condition.

Leak Check: Operate the pump by filling tank to trigger operation.  Pump 
RUN will be indicated by the yellow RUN LED.

Homeowner Instruction:  Instruct the homeowner about the pump's general 
operation, how to add Pro-Treat tablets, and to look for the ALARM LED if 
they think that there is system trouble.

Always disconnect power before performing maintenance.  Pump and 
deck may be removed from the tank by pushing tabs located on the tank 
sides away from the deck while lifting on the pump cover.

Periodically inspect the Pump tank to assure it is free of accumulated dirt or 
sludge.  Do not use solvent cleaners. Clean Tank with soap and warm 
water only.   The check valve may be removed for cleaning or replace-
ment by unscrewing with a 9/16 wrench. (illustration)

Clean inlet and outlet piping.  Tubing may be cleared 
of slime or debris instantly with a Wagner brand
Gallo Gun tool and Swoosh cartridges. 

Add Pro-Treat Tabs to the tablet tray.

Reassemble system and check 
for correct operation.

Safety Switch

Pump Operation

Pump Maintenance and Disassembly

Summary of Contents for CP-22

Page 1: ...Installation and Safety Instructions Condensate Pump CP 22 CP 22 230 CP 22LP CP 22LP 230 ...

Page 2: ...Shutoff Leads with Insulated Terminals Polyethelene Inlet Covers 3 Black Live Hot White Neutral Green Ground All installations must conform to NEC requirements 220 Volts 60 Hz 208 230 1 0 Amps NEMA 6 15 plug 22 ft maximum 1 6 GPM Continuous duty 140F Max inlet temperature 160F Not suitable for contact with steam or gasses that exceed 160F 11 8 x 5 9 x 6 7 4 9 H low profile 5 lbs 4 7 lbs low profil...

Page 3: ...r warranties that extend beyond the description of the face hereof The liability of the Company arising out of it s supply of said products or their use shall not in any case exceed the cost of correcting defects in the products as set forth above The Company shall not be liable for any costs or damage incurred by its customers in the removal or replacement of defective products from units in whic...

Page 4: ...remote indicator light to indicate a trouble condition Pump should be stored indoors The chosen location should be clean and dry Carefully open the carton to avoid damage to the pump Do not use a knife or other sharp object that may scratch the pump s cover After opening the carton look for damage If damage is found file a claim with the freight carrier CAUTION Be sure to remove the cardboard inse...

Page 5: ...ks the flow of air from the AC unit which is wasteful and can cause other prob lems such as accelerated algae growth The pump is equipped with a combination barb type fitting and check valve The fitting allows the connection of 3 8 flexible vinyl tubing such as DiversiTech CVT clear vinyl Attach the tubing by pressing it over the barb fitting and secure with a screw type hose clamp Route the tubin...

Page 6: ...Safety Switch operation if used to be sure that the A C system shuts down and the red ALARM LED lights when the pump has reached an overflow condition Leak Check Operate the pump by filling tank to trigger operation Pump RUN will be indicated by the yellow RUN LED Homeowner Instruction Instruct the homeowner about the pump s general operation how to add Pro Treat tablets and to look for the ALARM ...

Reviews: