background image

The condensate pump is equipped with metal mounting tabs which allow the 
tank to be screwed to a wall or equipment side panel.  The screw-to-screw 
distance is 8”.  When mounting into drywall or concrete walls the screws must 
have anchors which provide the necessary support in the wall material.

The pump top is reversible.  It may be turned around to allow easy access to 
the pump outlet, pan tab tray or power connection as may be required by 
the particular installation.

4 inlet holes are located in the top deck of the pump.  Flexible vinyl tubing 
or PVC may be connected to any of the pump inlets.  Pop out covers are 
provided to cover unused inlets.  Be sure to cover the unused holes to 
prevent the pump from collecting debris or insects.

Tubing installed into the inlet holes must be straight.  The tubing must not 
bend inward where it will interfere with the pump or float mechanism. 

When using rigid tubing such as PVC, be sure to cut the end at an angle. 
This will allow the condensate water to drain freely and keep the tubing 
end from being blocked by the tank bottom.

It may be desirable to use a “P” or “U” trap between the AC unit and the 
condensate pump to provide a liquid barrier to air flow from the air condi-
tioner.   These types of “traps” always contain some water which blocks the 
flow of air from the AC unit which is wasteful and can cause other prob-
lems such as accelerated algae growth.

The pump is equipped with a combination barb-type fitting and check 
valve.  The fitting allows the connection of 3/8” flexible vinyl tubing such as 
DiversiTech “CVT” clear vinyl.  Attach the tubing by pressing it over the 
barb fitting and secure with a screw type hose clamp.

Route the tubing up and away from the pump; avoid compressing or 
kinking the tubing.  The tube route should be the shortest possible distance 
from the pump to the building exterior or other drain location.  For best 
results the distance that the water must go UP should be shorter than the 
distance that it goes DOWN.  With the longer DOWN tubing, the length will 
help siphon the condensate from the tank, speeding the pump out time.

The pump features a dispenser which holds DiversiTech Pro-Treat pan 
treatment tablets.  The dispenser may be filled with multiple tablets to aid in 
keeping the pump, tank and outlet tubing slime free.  

Connect the pump power to a properly grounded outlet capable of 
providing power that exceeds the requirements listed on the pump name-
plate. Avoid the use of extension cords wherever possible.   The pump must 
be operated by a continuous source of power and must not be connected 
to switched outlets or other power supplies that may be inadvertently or 
automatically turned off.

Mounting

Inlets

Outlets and Tubing Connections

Pro-Treat

® 

 Tabs

Pump Electrical Connections

Summary of Contents for CP-22

Page 1: ...Installation and Safety Instructions Condensate Pump CP 22 CP 22 230 CP 22LP CP 22LP 230 ...

Page 2: ...Shutoff Leads with Insulated Terminals Polyethelene Inlet Covers 3 Black Live Hot White Neutral Green Ground All installations must conform to NEC requirements 220 Volts 60 Hz 208 230 1 0 Amps NEMA 6 15 plug 22 ft maximum 1 6 GPM Continuous duty 140F Max inlet temperature 160F Not suitable for contact with steam or gasses that exceed 160F 11 8 x 5 9 x 6 7 4 9 H low profile 5 lbs 4 7 lbs low profil...

Page 3: ...r warranties that extend beyond the description of the face hereof The liability of the Company arising out of it s supply of said products or their use shall not in any case exceed the cost of correcting defects in the products as set forth above The Company shall not be liable for any costs or damage incurred by its customers in the removal or replacement of defective products from units in whic...

Page 4: ...remote indicator light to indicate a trouble condition Pump should be stored indoors The chosen location should be clean and dry Carefully open the carton to avoid damage to the pump Do not use a knife or other sharp object that may scratch the pump s cover After opening the carton look for damage If damage is found file a claim with the freight carrier CAUTION Be sure to remove the cardboard inse...

Page 5: ...ks the flow of air from the AC unit which is wasteful and can cause other prob lems such as accelerated algae growth The pump is equipped with a combination barb type fitting and check valve The fitting allows the connection of 3 8 flexible vinyl tubing such as DiversiTech CVT clear vinyl Attach the tubing by pressing it over the barb fitting and secure with a screw type hose clamp Route the tubin...

Page 6: ...Safety Switch operation if used to be sure that the A C system shuts down and the red ALARM LED lights when the pump has reached an overflow condition Leak Check Operate the pump by filling tank to trigger operation Pump RUN will be indicated by the yellow RUN LED Homeowner Instruction Instruct the homeowner about the pump s general operation how to add Pro Treat tablets and to look for the ALARM ...

Reviews: