DIVERSITECH TOUCH SCREEN THERMOSTAT CONFIGURATION
ADVANCED SETTINGS – TIMER FEATURE
•
Specify the number of minutes for which Stage 1 will function until Stage 2 is
activated to help raise (or cool) temperature (if the temperature set point is not
reached). This unique function avoids excess compressor wear in the case where
the necessary temperature set point is not met through setting of the Staging
Differentials. Set to “00” to disable.
DIVERSITECH TOUCH SCREEN THERMOSTAT CONFIGURATION
ADVANCED SETTINGS – HEAT PUMP
•
HP “ON” when Furnace On: Heat Pump and Furnace can operate together when
2nd stage furnace is required. HP “OFF” when Furnace On: turns off the Heat Pump
when the furnace is On (required on some gas or oil furnaces).