background image

                                                        DTK-120X12

(Wiring Diagram-Low Voltage Surge Modules With Dry Contact Circuit)

DTK-2MHTP (2-Pair Modular Hybrid Telco Protector)

1. Connect the tele-communication circuit(s) from the field to the side marked 

UN-PROTECTED

. The first pair is connected to the  

    terminals marked 1+ and 1- . If a second pair is used, connect to the terminals marked 2+ and 2-  . 

2. Connect the tele-communication circuits(s) for the alarm panel supply wiring, for the dialer circuit, to the side marked 

PROTECTED

.

1. Connect the SLC, IDC, PIV

*

 or NAC

*

 loop circuit wiring from the field to the side marked 

UN-PROTECTED

. The first pair is  connected   

    to the terminals  marked 3+ and 3- . If a second pair is used, connect to the terminals marked 4+ and 4- . If  additional  circuits need 

    to be protected, continue with 5+, 5- and 6+, 6- through 12+, 12-. 

    

* Do not use DTK-2MHLPxxF for PIV or NAC circuits.

2. Connect the SLC, IDC, PIV or NAC loop circuit wiring, for the alarm panel inputs, to the side marked 

PROTECTED

.

3. After all connections have been made and no hazards exist, replace cover, and proceed to the surge module installation sections.

DTK-2MHLPXXB, DTK-2MHLPXXF (2-Pair Modular Hybrid Line Protector)

Notes: 

Connect this device in series between the field wiring and the control panel supply wiring.

• These Low Voltage protection circuits are equipped with a removable plug and header assembly. Simply remove the plug from the  

  header, terminate your wires, then replace the plug making sure it seats and snaps into place.

• There are up to 6 positions for surge modules available for protection of any combination of Dialer Circuit, SLC (Signaling),

  IDC (Initiating), PIV (Valve) or NAC (Notifying) circuits. Each module will protect 2 pairs or circuits of the same voltage.

• All modules have been factory pre-wired for ground.  It is not necessary to make any additional ground connections.

• Allow for sufficient reaction time by providing a minimum of 3 wire feet between the DTK-120X12 and the alarm panel inputs.

• Use separate conduit feeds to isolate the unprotected “INPUT” wiring from the protected “OUTPUT” wiring.

• Use appropriately sized conduit fittings and conduit (not included). 

-FIELD WIRING

-INPUT*

-UNPROTECTED 

    -SUPPLY

    -OUTPUT*

    -PROTECTED 

#30-12 AWG

DITEK

Surge Protection

R

1-2

3-4

5-6

7-8

9-10

11-12

EARTH

NEUT

LINE IN

EARTH

NEUT

LINE OUT

2-

2+

1-

1+

4-

4+

3-

3+

6-

6+

5-

5+

12

-12

+

11

-1

1+

10

-

10

+

9-

9+

8-

8+

7-

7+

2-

2+

1-

1+

4-

4+

3-

3+

6-

6+

5-

5+

12

-1

2+

11

-11

+

10

-

10

+

9-

9+

8-

8+

7-

7+

NC C NO

LOAD

LINE

UN-PROTECTED

PROTECTED

WHEN USING 

THE DRY CONTACT 

CIRCUIT, USE THIS 

1/2” CONDUIT

SOLELY FOR THE 

DRY CONTACT 

CONDUCTORS

Summary of Contents for Deflector Series

Page 1: ...TK DFXXXM SPD TYPE 2CA Electrical Ratings XXXVAC 20A 50 60 Hz Single Phase Nominal Discharge Current Rating In 10kA SCCR 10kA MCOV Rating 150 L N 150 L G VPR 600 L N 600 L G Suitable for use on a circ...

Page 2: ...isant au plus 10 000 A eff WARNING SHOCK HAZARD DO NOT OPEN AVERTISSEMENT RISQUE DE CHOC NE PAS OUVRIR C U R US DITEK R DTK 2MHLP DTK 2MHTP 5 12 24 36 48 75 130 MODULAR SURGE PROTECTION VOICE DATA SIG...

Page 3: ...pply wire to the LINE IN lug at the LINE side 6 Connect the Ground Neutral and Phase wires from the LOAD side to the control panel or your equipment s AC inputs Note Tightening torque for the 120VAC p...

Page 4: ...this device in series between the field wiring and the control panel supply wiring These Low Voltage protection circuits are equipped with a removable plug and header assembly Simply remove the plug...

Page 5: ...ng These Low Voltage protection circuits are equipped with a removable plug and header assembly Simply remove the plug from the header terminate your wires then replace the plug making sure it seats a...

Page 6: ...odule is installed the audible alarm will be cancelled The red polarizing keys insure that the correct voltage module will mate with its correct base WARNING When the DTK 120M module has gone end of l...

Page 7: ...ow voltage surge module into the corresponding position according to your connection circuits When a DTK 2MHTP tele communications surge module has expired gone end of life there will be interference...

Page 8: ...Center 1720 Starkey Road Largo Fl 33771 1 800 753 2345 www diteksurgeprotection com Doc INT 100190 001 Part No 191635 Rev 2 DTK 120X12 THIS PAGE LEFT INTENTIONALLY BLANK Drawn By B Aycock 5 7 2020 Rev...

Reviews: