background image

                              DTK-DF120M 

          (120VAC Surge Module Installation)

The DTK-120X12 is a series connected Surge Protective Device, for 120VAC power plus up to 12 

individual low voltage circuits,  with a replaceable surge module for the 120VAC power and  every 

2-Pairs of  low voltage circuits.  The  LED  indicators  on the  top face of the  DTK-DF120M  surge 

module provide  power,  ground and surge module health  status. When the  DTK-DF120M  surge 

module has gone end of  life,   the large  “REPLACE”  RED LED will  illuminate  and the  “GOOD” 

Green LED  will turn off.   Also,  the audible alarm will sound to provide an  extra alert  to  indicate 

the  surge module’s health. To silence the alarm,  remove the  dead module and  replace it with a 

new, unused module. If a new module is not available, the alarm can be silenced by  pressing the 

tactile switch, located at the end of the enclosure, into BYPASS  mode for 24 hours.  When a new  

DTK-DF120M  surge module is installed,  the audible alarm will be cancelled. The  red  polarizing 

keys insure that the correct voltage module will mate with its correct base. 

WARNING:  When the DTK-120M module has gone end of life, or is missing, the base is 

susceptible to damage from surge energy. Make sure you always have a spare module 

available. No substitutions shall be permitted.

DITEK

Surge Protection

MODULE

STATUS

DTK-DF120M

120VAC

R

ENERGIZED

GROUNDED

GOOD

REPLACE

MADE IN USA

DEFLECTOR

SERIES

Pat. www.diteksurgeprotection.com/patents

Model: DTK-DF120M     SPD TYPE 2CA

Electrical Ratings: 120VAC, 20A, 50/60 Hz, Single Phase  
Nominal Discharge Current Rating: (In): 10kA, SCCR: 10kA
MCOV Rating: 150 L-N, 150 L-G
VPR: 600 L-N, 600 L-G
Suitable for use on a circuit capable of delivering not more than
10,000 rms symmetrical amperes, 120 Volts maximum when pro-
tected by a 20 ampere circuit breaker rated 120 volts minimum.
Convient a des circuits produisant au plus 10,000 A eff.

WARNING - SHOCK HAZARD - DO NOT OPEN

AVERTISSEMENT - RISQUE DE CHOC

NE PAS OUVRIR

C

UR

US

Front

Back

MODULE

STATUS

ENERGIZED

GROUNDED

GOOD

REPLACE

Summary of Contents for Deflector Series

Page 1: ...TK DFXXXM SPD TYPE 2CA Electrical Ratings XXXVAC 20A 50 60 Hz Single Phase Nominal Discharge Current Rating In 10kA SCCR 10kA MCOV Rating 150 L N 150 L G VPR 600 L N 600 L G Suitable for use on a circ...

Page 2: ...isant au plus 10 000 A eff WARNING SHOCK HAZARD DO NOT OPEN AVERTISSEMENT RISQUE DE CHOC NE PAS OUVRIR C U R US DITEK R DTK 2MHLP DTK 2MHTP 5 12 24 36 48 75 130 MODULAR SURGE PROTECTION VOICE DATA SIG...

Page 3: ...pply wire to the LINE IN lug at the LINE side 6 Connect the Ground Neutral and Phase wires from the LOAD side to the control panel or your equipment s AC inputs Note Tightening torque for the 120VAC p...

Page 4: ...this device in series between the field wiring and the control panel supply wiring These Low Voltage protection circuits are equipped with a removable plug and header assembly Simply remove the plug...

Page 5: ...ng These Low Voltage protection circuits are equipped with a removable plug and header assembly Simply remove the plug from the header terminate your wires then replace the plug making sure it seats a...

Page 6: ...odule is installed the audible alarm will be cancelled The red polarizing keys insure that the correct voltage module will mate with its correct base WARNING When the DTK 120M module has gone end of l...

Page 7: ...ow voltage surge module into the corresponding position according to your connection circuits When a DTK 2MHTP tele communications surge module has expired gone end of life there will be interference...

Page 8: ...Center 1720 Starkey Road Largo Fl 33771 1 800 753 2345 www diteksurgeprotection com Doc INT 100190 001 Part No 191635 Rev 2 DTK 120X12 THIS PAGE LEFT INTENTIONALLY BLANK Drawn By B Aycock 5 7 2020 Rev...

Reviews: