5.1 Tools

•  Insulated tools sized to match nuts, bolts and cables in use
•  Voltmeter
•  Post cleaner and wire brush
•  Personal protective equipment

5.2 Securing Battery

•  Battery can be strapped in place with non-conductive nylon straps

5.3 Installation

•  Check that battery is switched off
•  If battery circuit has disconnect, open disconnect to isolate battery
•  Clean cable connections. Broken, frayed, brittle, kinked or cut     
   cables should be replaced 
•  Install and secure new battery. Be careful not to ground the      
   terminals to any metal mounting, fixture, or body part
•  Connect battery cables. Connect ground cable last to avoid sparks
•  Recommended terminal torque is 7.0 – 7.7 Nm (5.1 – 5.7 ft-lb)
•  Close circuit disconnect (if open)
•  Turn battery switch on

▲ 

NOTE!

All cables ends must be connected to battery terminals 

without any washers between terminal bushings and 

cable ends.

Terminal burnout is caused by:

•  Discharge currents exceeding allowable limits
•  Improper cable installation
•  Improper cable sizing
•  Improper terminal torque

▲ 

NOTE!

Without exception, product experiencing terminal burn 

out will not be warranted.

6. Operation

▲ 

NOTE!

Review operating limits.

6.1 On–Off

•  To turn the battery on press and hold switch for 2-3 seconds
•  To turn the battery off press and hold switch for 2-3 seconds

6.2 Charging 

Before operating the charger make sure to read and understand the instructions that come with the charger. Never attempt to 
charge a battery without first reviewing and understanding the instructions for the charger being used.

▲ 

CAUTION!

Always make sure the chargers charging curve meets the 

battery’s charging requirement; never charge a visibly 

damaged battery; never charge a frozen battery.

1. Connect the charger leads to the battery.
2. Make sure that the charger lead, both at the charger and the battery side, connections are tight.
3. Turn the charger on.
4. Turn the battery on (if required).

M6” bolt (supplied)

Copper compression lug

Shrink-wrap to 

color-code the cable

Terminal surface

Lock washer (supplied)

Flat washer (supplied)
Battery cable lug 
Ensure nothing is between 

the terminal surface and the 

battery cable lug

5

Summary of Contents for 15-24-1000

Page 1: ...1 Battery Operating Limits 3 3 Design Features Components 4 3 1 Battery Management System BMS 4 3 2 Fuse 4 3 3Terminals 4 4 Handling 4 5 Installation Single Battery 4 5 1Tools 5 5 2 Securing Battery 5...

Page 2: ...the battery Read all the instructions before installation operation and maintenance This product must be recycled and is made of recycled products CAUTION Do not disassemble or modify the battery If t...

Page 3: ...s Do not expose battery to high temperatures Do not install with other battery types or brands 1 8 DC Motor Connection Direct connection to DC motors without proper safety protection motor controllers...

Page 4: ...ult events cause switch to open and battery to shut down after a 120s delay Communication Ports BMS has an isolated RS232 communication port for service technician use only 3 2 Fuse Fuse provides back...

Page 5: ...llation Improper cable sizing Improper terminal torque NOTE Without exception product experiencing terminal burn out will not be warranted 6 Operation NOTE Review operating limits 6 1 On Off To turn t...

Page 6: ...Qualification phase for auto on feature optional 2 Charge at constant current to 3 4Vdc per cell module Bulk 3 Maintain constant voltage 3 4Vdc per cell module Absorption 4 Terminate when charge curre...

Page 7: ...ver Voltage Stop charge Over Current Reduce current Over Temperature Stop using let cool Short Circuit Check external circuits FLASHING LED 7 FAULT LEVELS Parameter Trigger Point High Temperature in D...

Page 8: ...ymptom Does the battery turn on for a short time then turns itself off Description The battery is likely in a low voltage or low SOC state Check to see if the blue light is blinking This indicates a l...

Page 9: ...Shipping Dimensions HxWxD 248 x 250 x 340 mm Shipping Weight 13 kg Terminal A2 M6 Terminal Hardware M6 Stainless Steel Bolt Flat Washer Lock Washer Supplied TerminalTorque 7 0 7 7 Nm Case Material PC...

Page 10: ...t 12 4 kg Shipping Dimensions HxWxD 248 x 250 x 340 mm Shipping Weight 13 kg Terminal A2 M6 Terminal Hardware M6 Stainless Steel Bolt Flat Washer Lock Washer Supplied TerminalTorque 7 0 7 7 Nm Case Ma...

Reviews: