B-
B-
B-
B-6
6
6
6
Table 3 The action property of the over current tripping gear of the breaker (used for power distribution)
Table 4 The action property of the over current release of the breaker (used for motor protection)
BAM8-100S/3P
65/10
32.5/5
BAM8-225S/3P
25
100 125 160
180 200 225
25/5
12.5/2.5
BAM8-225H/2P
50/8
25/4
BAM8-225H/3P
BAM8-225H/4P
=63A(If
≤
125A)
=In/2( if
I
n>125A
)
BAM8-225H/2P
65/10
32.5/5
BAM8-400S/3P
400
225. 250.
315. 350.
400
380/
400/
415/
690
800
35/10
17.5/5
BAM8-400S/4P
In/2
BAM8-400H/3P
50/12
25/6
BAM8-400R/3P
70/15
35/7.5
BAM8-630S/3P
630
400.
500.
630
35/12
17.5/6
BAM8-630S/4P
In/2
BAM8-630H/3P
50/13
25/6.5
BAM8-630R/3P
380/
400/
415
500
70
35
BAM8-800H/3P
800
630 700 800
60
30
BAM8-800R/3P
70
35
BAM8-1250H/3P
1250
700.800
900.1000
1250
65
32.5
No.
Test current
I/In
Specified time
Initial status
1
Specified no-trip current
1.05
2h (In>63A)
1h (In≤63A )
Cold position
2
Specified trip current
1.30
2h (In>63A)
1h (In≤63A )
Following the test No.1
No.
Test current
I/In
Specified time
Initial status
1
Specified no-trip current
1.0
2h
Cold position
2
Specified trip current
1.2
2h
Following the test No.1