22
3.
Calibration parameter SM3 (MAXIMUM SPEED)
Then turn the ENCODER - A knob (E1) until the PARAM-
ETER DISPLAY - A screen (D1) shows the
SM3
parame-
ter. Push and release the torch button, and then wait for the
wire to stop automatically, and the
End MiS
message to ap-
pear. Measure (in cm) the dangling wire and insert the value
shown, in the software of the welder, by means of the rota-
tion of the ENCODER knob - V (E2) appearing on the PA-
RAMETER DISPLAY screen - V (D2) is the desired value.
D1
D2
E2
E1
•
At the end of the procedure, the software present in the welder
will immediately re-calculate the characteristic curve of the en-
gine, rendering it suitable to use.
•
To exit from the CALIBRATION menu, press and release the
SAVE “MEM” key (T2).
T2
•
To interrupt measuring, push the SAVE “MEM” (T2) Key.
ARC LENGTH ADJUST
For MIG welding processes (pulsed, double pulsed, synergic,
and manual), this function allows the operator to adjust the ARC
LENGTH ADJUST (
) parameter, with the WELDING VOLTAGE
( ) or the WIRE SPEED (
).
1) Rotate the ENCODER - A (E1) knob until the DISPLAY PA-
RAMETERS - A (D1) display shows the
ArC
function, and the
DISPLAY PA-RAMETERS - V (D2) display shows the two ad-
justment methods:
U
(VOLT - WELDING VOLTAGE) and
rPM
(SPEED - WIRE SPEED).
2) Rotate the ENCODER - V (E2) knob and choose the adjust-
ment method required (this operation does not need to be con-
firmed).
D1
D2
E2
E1
3) To change the adjustment method, repeat steps 1 and 2.
4) To exit the
SEtUP
menu, push the SAVE “MEM” (T2) key.
T2
SWITCH
If enabled, this function allows the operator to have a further weld-
ing mode (SWITCH) available, in MIG (pulsed, double pulsed,
synergic and manual) welding processes, as well as the special
functions associated with it:
•
CURRENT SWITCH, SWITCH WIRE SPEED (see Table 1, Pa-
rameter F19).
•
SWITCH ARC LENGTH, SWITCH VOLTAGE (see Table 1, Pa-
rameter F20).
1) Rotate the ENCODER - A (E1) knob until the DISPLAY PA-
RAMETERS - A (D1) display shows the
CYC
function, and
the DISPLAY PARAMETERS - V (D2) display shows the two
choices available:
oFF
(SWITCH disabled) and
on
(SWITCH
enabled).
2) Rotate the ENCODER - V (E2) knob and choose whether to
enable or disable the SWITCH (this operation does not need
to be confirmed).
D1
D2
E2
E1
3) To change the mode, repeat steps 1 and 2.
4) To exit the
SEtUP
menu, push the SAVE “MEM” (T2) key twice.
T2
WATER COOLING MODE
This configuration allows the operator to set cooling (only if avail-
able), in the following ways:
•
ON DEMAND - In this case, cooling is managed in relation to
the welding done.
•
ALWAYS ON - In this case, cooling comes on when the machine
is switched on, and stays on until the machine is switched off.
Cooling only stops when an alarm is activated.
To make the setting, proceed as follows:
1) Rotate the ENCODER - A (E1) knob until the DISPLAY PA-
RAMETERS - A (D1) display shows the
H2o
function, and
the DISPLAY PARAMETERS - V (D2) display shows the two
choices available:
Dem
(ON DEMAND) and
Aon
(ALWAYS
ON).
2) Rotate the ENCODER - V (E2) knob and choose the cooling
mode required (this operation does not need to be confirmed).
D1
D2
E2
E1