3. Notification
Before, drilling, and cut. should use clean dry cloth, or the inventory doesn’t
lead the electricity, covers the equipment for protects iron dust touches the
electrical equipment while installing. (In case of machine still operate.)
Cooling unit should be installed in the good circuration area
Check vertical and horizontal level of which their error shall be allowable
/- 2 o in order to facililate efficient drainage
Should always install gasket between
Installation plate
and
Cooling Unit
before hang the cooling unit on the installation plate
Installing of drain tube (Page 17)
In order to minimize water condensation, cabinet doors should be tightly closed
during operation
Circulation fan should be installed in cabinet if various equipment is densely
installed inside
In order to obtain highest performance and durablility, repair and alteration of
cooling unit should be under care of distributor
Should not adjust temperature difference more than 10
o
C betwee
enviromental temperature and cooling space, to prevent moisture build up on
some part in the cooling area when you open the cabinet panel
If it is necessary to set temperature lower than 25
o
C, it is recommended to
use precision cooling unit or contact your Professional Maker.
The equipments that are locate in the cooling air stream have to be
obstructed by the insulator to prevent water condensation
8