2. Specifications
6
Characteristics
(under normal operating condition at ambient temp. +35oC)
Model
20ACU/004
Capacity
Watt
600
Installation type
panel
Input
single-phase (V.)
220V+20% / -15%
frequency (Hz.)
50/60
current (A.)
1.9
Compressor
hermetic type
rotary
refrigerant type
134a
System operate
direct expand
yes
Hi-prosent ctrl1
thermostat
yes
condensor thermal detector
yes
anti-freeze detector
yes
compressor overheat detector
none
water detector
none
Protection
over drain protect system
yes
Display
thermometer (red 7 segment 19 mm.)
yes
system status (2 colour LED)
yes
Electrical equip.
safety device
7A. slow-blow fuse
Evaporator coil
face area x rows
42.5 sq.inch x 2
servo fan (r.p.m.)
2850
number of fan x cfm (0.18 inH
2
O)
1 x 135
Condenser coil
face area x rows
78.75 sq.inch x 3
servo fan (r.p.m.)
2850
number of fan x cfm (0.2 inH
2
O)
2 x 158
Physical data
approx.weight (kgs.)
31.5
dimension (mm.)
W:384 D:177 H:619
condensate drain
OD. 3/8 inch
internal casing
electro-galvanize
Air filter
width x lenth (mm.)
110 x 536
*under normal operating condition at ambient temp. +45oC