E-9
Englis
h
Menu Structure
8.1
Sets the time programs for hot water blocks
Sets the times in which DHW preparation is blocked
00:00
to
23:59
For each day of the week, it is possible to select whether Time1,
Time2, no time or both times are to be active when the
temperature is lowered. Operations to lower the temperature that
exceed a weekday are activated or deactivated at the end of each
day accordingly.
N
T1
T2
Y
To carry out a thermal disinfection, the DHW is heated up once to
the desired temperature. The heating period is terminated
automatically when the set temperature is reached or after 4 hours
at the latest.
Sets the start time for the thermal disinfection
00:00
to
23:59
Sets the desired hot water temperature which is to be reached
during thermal disinfection
60°C
to
45 °C
to
85°C
For each day of the week, it is possible to select whether thermal
disinfection is desired at the set start time.
N
Y
By setting Reset to “Yes”, the maximum calculated hot water
temperatures in HP operation are reset to a value of 65 °C. The
setting is automatically reset to “No”.
No
Yes
Sets the preparation of swimming pool water
Sets the desired swimming pool temperature
5°C
...
25°C
...
60°C
Sets the time programs for a priority of swimming pool water
preparation
Sets the start time for the swimming pool priority
00:00
to
23:59
Sets the desired number of hours of priority of the swimming pool
water preparation.
1
...
10
For each day of the week, it is possible to select whether a priority
is desired at the set start time.
N
Y
System-specific parameters
Setting range