7.4.4 Hydraulic distribution system

The compact manifold and the dual differential pressureless
manifold function as an interface between the heat pump, the
heating distribution system, the buffer tank and, in some cases,
even the hot water cylinder. A compact system is used to sim-
plify the installation process, so that a lot of different compo-
nents do not have to be installed individually. Further informa-
tion can be found in the relevant installation instructions.

Compact manifold

The return sensor can remain in the heat pump, or should be in-
stalled in the immersion sleeve. The remaining empty space be-
tween the sensor and the immersion sleeve must be filled com-
pletely with heat transfer compound.

Dual differential pressureless manifold

In order for the heating circuit pumps of the generator and con-
sumer circuits to supply the flow to the return sensor, this must
be installed in the immersion sleeve of the dual differential
pressureless manifold.

7.5 Electrical connection 

7.5.1 General

All electrical connection work must be carried out by a trained
electrician or a specialist for the specified tasks in accordance
with the 

installation and operating instructions, 

country-specific installation regulations (e.g. VDE 0100),

technical connection conditions of the energy suppliers
and supply grid operators (e.g. TAB) and

local conditions.

To ensure that the frost protection function of the heat pump
works properly, the heat pump manager must remain con-
nected to the power supply and the flow must be maintained
through the heat pump at all times.
The switching contacts of the output relay are interference-
suppressed. Therefore, depending on the internal resistance of
the measuring instrument, a voltage can also be measured
when the contacts are open. However, this will be much lower
than the line voltage.
Extra-low voltage is connected to controller terminals N1-J1 to
N1-J11; N1-J19; N1-J20; N1-J23 to N1-J26; N17-J1 to N17-
J4; N17-J9; N17-J10 and terminal strip X3 and X5.1. If, due to a
wiring error, the line voltage is mistakenly connected to these
terminals, the heat pump manager will be destroyed

7.5.2 Electrical installation 

1) The supply cable (with up to 5 cores) for the power element

of the heat pump or the primary pump is routed from the
heat pump's electricity meter to the heat pump.
The cable for the heat pump is routed via the utility contac-
tor (if required). Connection of the mains cable is at the
control panel of the heat pump via the terminals: X1: L1/
L2/L3/N/PE or X1: L11/L21/L31/PE. 
If no utility contactor is used, the electrical loads are sup-
plied via a shared feed cable (bridge feeds using bridges
supplied). The power supplies are fitted with an all-phase
disconnection with at least 3 mm contact opening dis-
tance (e.g. utility protection contactor, power contactor), as

well as an all-phase cutout switch, with shared activation of
all external  conductors (release currents and characteris-
tics in accordance with device information; see circuit dia-
gram for further details). 

ATTENTION!

!!

Ensure the rotary field is clockwise when connecting the
mains cables (if the rotary field is not clockwise, the heat
pump will not work properly, is very loud and may cause
damage to the compressor).

2) The three-core electric supply cable for the heat pump

manager (heating controller N1) is fed into the heat pump .
Connection of the control line to the control panel of the
heat pump via terminal X2: L/N/PE. 
Details on the power consumption of the heat pump are
listed on both the product information sheet and the type
plate.
The (L/N/PE~230 V, 50 Hz) supply cable for the heat pump
manager must have a constant voltage. For this reason, it
should be tapped upstream from the utility blocking con-
tactor or be connected to the household current, as impor-
tant protection functions could otherwise be lost during a
utility block.

3) The utility blocking contactor(K22) with 3 main contacts

(1/3/5 // 2/4/6) and an auxiliary contact (NO contact 13/
14) should be dimensioned according to the heat pump
output and must be supplied by the customer.
The NO contact of the utility blocking contactor (13/14) is
looped from terminal strip X3/G to connector terminal X3/
A1. 

CAUTION! Extra-low voltage!

4) The contactor (K20) for the immersion heater (E10) of

mono energy systems (HG2) should be dimensioned ac-
cording to the radiator output and must be supplied by the
customer. It is controlled (230 V AC) by the heat pump
manager via terminals X2/N and X2/K20.

5) The contactor (K21) for the flange heater (E9) in the hot

water cylinder should be dimensioned according to the ra-
diator output and must be supplied by the customer. It is
controlled (230 V AC) by the heat pump manager via termi-
nals X2/N and X2/K21.

6) The contactors mentioned above in points 3, 4 and 5 are

installed in the electrical distribution system. Mains cables
for the installed heaters must be laid and secured in ac-
cordance with the valid standards and regulations.

7) All installed electric cables must have permanent wiring.
8) The heat circulating pump (M13) is activated via the con-

tact N1-J13/NO5. The connection points for the pump are
X2/M13 and X2/N. When using pumps where the switch-
ing capacity exceeds the output, a coupling relay must be
interposed.

9) The auxiliary circulating pump (M16) is activated via the

contact N1-J16/NO9. The  connection points for the pump
are X2/M16 and X2/N. When using pumps where the
switching capacity exceeds the output, a coupling relay
must be interposed.

10) The domestic hot water circulating pump (M18) is acti-

vated via the contact N1-J13/NO6. The connection points
for the pump are X2/M13 and X2/N. When using pumps
where the switching capacity exceeds the output, a cou-
pling relay must be interposed.

11) The brine or well pump (M11) is activated via the contact

N1-J12/NO3. The connection point for the pump is on
contactor  K5:2/4/6. A coupling relay is already integrated
in this output.. If an additional well pump is used, the pro-

Summary of Contents for WI 140TUR+

Page 1: ...Gebrauchsanweisung Wasser Wasser W rmepumpe f r Inenaufstellung Installation and Operating Instruction Water to Water Heat Pump for Indoor Installation Instuctionsd installation et d utilisation Pomp...

Page 2: ......

Page 3: ...2 Heizungs und warmwasserseitiger Anschluss DE 7 7 3 W rmequellenseitiger Anschluss DE 7 7 4 Temperaturf hler DE 8 7 5 Elektrischer Anschluss DE 9 8 Inbetriebnahme DE 10 8 1 Allgemein DE 10 8 2 Vorber...

Page 4: ...nder Gebrauch gilt als nicht bestimmungsgem Dazu z hlt auch die Beachtung der zugeh rigen Projektierungsun terlagen nderungen oder Umbauten am Ger t sind zu unter lassen 1 3 Gesetzliche Vorschriften u...

Page 5: ...rmepumpen zu finden ACHTUNG Das Brunnenwasser muss der geforderten Wasserqualit t entsprechen 2 2 Arbeitsweise Heizen Eine Brunnenpumpe f rdert das Wasser in den Verdampfer der W rmepumpe Dort gibt e...

Page 6: ...12 erm glicht einen f r Heizen und K hlen optimierten Betrieb der reversiblen Was ser Wasser W rmepumpe Durch die Umschaltung der Fluss richtung wird der W rmetauscher auf der Sekund rseite so wohl im...

Page 7: ...ge zu erfassen Er ist als Zubeh r erh ltlich Durch den vorhandenen Zusatzw rmetauscher werden f r die Erfassung der W rmemenge zwei W rmemengenz hler ben tigt Sensoren im Vor und R cklauf der W rmetau...

Page 8: ...rmepumpe muss in einem frostfreien und trockenen Raum auf einer ebenen glatten und waage rechte Fl che aufgestellt werden Dabei sollte der Rahmen rundum dicht am Boden anliegen um eine ausreichende S...

Page 9: ...zul ssiger Wert f r Kupfer nicht unterschritten wird Eine Unterschreitung kann zur Zerst rung der W rmepumpe f hren Es wird empfohlen das optional erh ltliche 4 Wege Umschalt ventil zu verwenden Eine...

Page 10: ...stern T ren Abluft ffnungen Au enleuchten oder W rmepumpen anbringen zu keiner Jahreszeit direkter Sonneneinstrahlung ausset zen 7 4 3 Montage der Anlegef hler Die Montage der Anlegef hler ist nur not...

Page 11: ...li ger Sicherungsautomat mit gemeinsamer Ausl sung aller Au enleiter vorzusehen Ausl sestr me und Charakteristi ken gem Ger teinformation weitere Details siehe Schalt plan ACHTUNG Beim Anschluss der L...

Page 12: ...e pumpenmanagers verk rzen k nnen Aus diesem Grund ist zwischen dem Ausgang des W rmepumpenmanagers und der elektronisch geregelten Umw lzpumpe ein Koppelrelais zu ins tallieren bzw installiert Dies i...

Page 13: ...chgesp lt werden um Besch digungen durch eventuell im System verbliebene Reinigungsmittelreste zu verhindern Die S uren sind mit Vorsicht anzuwenden und es sind die Vor schriften der Berufsgenossensch...

Page 14: ...hine spannungsfrei zu schalten und abzuschiebern Der Ausbau der W rmepumpe muss durch Fachpersonal erfolgen Umweltrelevante Anforderungen in Bezug auf R ckgewinnung Wiederverwendung und Entsorgung von...

Page 15: ...kW 6 72 5 4 4 bei W10 W35 kW 5 143 3 5 2 kW 6 77 4 5 4 4 3 Mindestk hlwasserdurchfluss interne Druckdifferenz m h Pa 24 27 21100 4 4 K hlleistung Leistungszahl 8 9 bei W20 W9 kW 5 131 0 5 5 bei W20 W7...

Page 16: ...zw rmetauscher im Parallelbetrieb die Abw rmeleistung bzw erreichte Speichertemperatur ist vom jeweiligen Betriebspunkt Temperatur niveau Leistungsstufe abh ngig Mit steigender Speichertemperatur sink...

Page 17: ...kWh Angegebenes Lastprofil Warmwasserbereitungs Energieeffizienz wh T glicher Stromverbrauch Qelec kWh T glicher Brennstoffverbrauch Qfuel kWh Kontakt Wird der Cdh Wert nicht durch Messung bestimmt g...

Page 18: ...eile zur ckzu f hren sind fallen nicht unter den Garantieanspruch Bei endg ltig fehlgeschlagener Nachbesserung wird der Hersteller entweder kostenfreien Ersatz liefern oder den Minderwert verg ten Im...

Page 19: ...mbly EN 6 7 1 General EN 6 7 2 Connection on heating and hot water side EN 7 7 3 Connection on heat source side EN 7 7 4 Temperature sensor EN 8 7 5 Electrical connection EN 9 8 Start Up EN 10 8 1 Gen...

Page 20: ...the manu facturer Any other use beyond that intended by the manufac turer is prohibited This requires the user to abide by the rele vant project planning documents Please refrain from tampering with...

Page 21: ...with the required water quality standards 2 2 Operation principle Heating A well pump conveys the water to the evaporator of the heat pump There the heat is transferred to the refrigerant in the re fr...

Page 22: ...eversing valve Y12 enables optimised heating and cooling operation of the reversible water to water heat pump The reversal of the flow direction ensures an opti mum flow through the heat exchanger on...

Page 23: ...ed It is available as an ac cessory Due to the additional heat exchanger two thermal en ergy meters are required for measuring the quantity of thermal energy Sensors in the flow and return of the heat...

Page 24: ...nstallation 6 1 General The water to water heat pump must be installed in a frost free dry room on an even smooth and horizontal surface The entire frame should lie directly on the floor to ensure an...

Page 25: ...7 5 minimum permissible value for copper is complied with Failure to comply with this value can result in the heat pump being destroyed Use of the optionally available four way reversing valve is rec...

Page 26: ...balcony Not in the vicinity of windows doors exhaust air vents ex ternal lighting or heat pumps Not to be exposed to direct sunlight at any time of year 7 4 3 Installing the strap on sensor It is onl...

Page 27: ...t switch with shared activation of all external conductors release currents and characteris tics in accordance with device information see circuit dia gram for further details ATTENTION Ensure the rot...

Page 28: ...mp manager For this reason a coupling relay is installed or must be installed between the output of the heat pump manager and the electronically regulated circulating pump This is not neces sary if th...

Page 29: ...appropriate neutralising agents to prevent any damage from being caused by cleaning agent residue remaining in the sys tem Acids must be used with care and the regulations of the em ployers liability...

Page 30: ...wer source and close all valves The deinstallation of the heat pump must be performed by technical personnel Observe all environ mentally relevant requirements regarding the recovery recy cling and di...

Page 31: ...43 3 5 2 kW 6 77 4 5 4 4 3 Minimum cooling water flow rate internal pressure differential m h Pa 24 27 21100 4 4 Cooling capacity COP 8 9 at W20 W9 kW 5 131 0 5 5 at W20 W7 kW 6 63 4 5 5 at W20 W18 kW...

Page 32: ...allel operation The waste heat output and or the cylinder temperature attained is dependent on the present operating point temperature level performance level The waste heat output falls when the cyli...

Page 33: ...missions of nitrogen oxides NOx mg kWh Declared load profile Water heating energy efficiency wh Daily electricity consumption Qelec kWh Daily fuel consumption Qfuel kWh Contact details If Cdh is not d...

Page 34: ...EN 16 452234 66 76 FD 9912 www gdts one English WI 140TUR...

Page 35: ...6 7 1 G n ralit s FR 6 7 2 Raccordement chauffage et circuit d eau chaude FR 7 7 3 Raccordement c t source de chaleur FR 7 7 4 Sonde de temp rature FR 8 7 5 Branchements lectriques FR 9 8 Mise en serv...

Page 36: ...accompagnant les projets doit galement tre prise en compte Toute modification ou transformation sur l appareil est proscrire 1 3 Dispositions l gales et directives Cette pompe chaleur est con ue pour...

Page 37: ...e projet et d installation des pompes chaleur de chauffage ATTENTION L eau de puits doit tre conforme la qualit de l eau requise 2 2 Fonctionnement Chauffage Une pompe de puits am ne l eau vers l vapo...

Page 38: ...un fonction nement optimis pour le chauffage et le rafra chissement des pompes chaleur eau eau r versibles Gr ce la commutation de flux l changeur thermique du c t pompe secondaire est travers de man...

Page 39: ...me acces soire Deux calorim tres sont requis pour la mesure de la quan tit de chaleur du fait de la pr sence d un changeur ther mique Des capteurs situ s dans les circuits de d part et de retour des c...

Page 40: ...e et horizontale Le ch ssis doit adh rer au sol et tre tanche sur tout son pourtour afin de garantir une insonorisation correcte et d emp cher Si tel n est pas le cas des mesures d absorption acoustiq...

Page 41: ...ATTENTION Il faut veiller dans le cas d eau enti rement d min ralis e ce que le seuil inf rieur admis pour la valeur pH minimale de 7 5 valeur minimale admise pour le cuivre ne soit pas d pass Un tel...

Page 42: ...ne pas installer proximit de fen tres portes ouvertures d a ration clairage ext rieur ou pompes chaleur ne pas exposer aux rayons directs du soleil quelle que soit la saison 7 4 3 Montage des sondes d...

Page 43: ...alimentations au moyen des ponts fournis Sur l alimentation de puissance de la pompe chaleur pr voir une coupure omnipolaire avec au moins 3 mm d cartement d ouverture de contact p ex contac teur de...

Page 44: ...dans l appareil par l ar ri re et fix s sur le bo tier lectrique l aide d attache c bles Ils doivent galement tre s curis s l aide de colliers de fixation 7 5 3 Branchement du circulateur r gulation l...

Page 45: ...rcuit de l installation de chauffage nous vous recommandons de raccorder l appareil de nettoyage directe ment sur le d part et le retour du condenseur de la pompe chaleur Il faut ensuite soigneusement...

Page 46: ...11 Mise hors service Elimination Avant de d monter la pompe chaleur il faut mettre la ma chine hors tension et fermer toutes les vannes Le d montage de la pompe chaleur doit tre ex cut par du personne...

Page 47: ...3 5 2 kW 6 77 4 5 4 4 3 D bit d eau de chauffage min diff de pression int m h Pa 24 27 21100 4 4 Capacit de rafra chissement coef de performance 8 9 pour W20 W9 kW 5 131 0 5 5 pour W20 W7 kW 6 63 4 5...

Page 48: ...de fonctionnement respectif niveau de temp rature niveau de puissance Lorsque la temp rature du ballon augmente la puissance thermique perdue diminue 3 Les coefficients de performance sont galement at...

Page 49: ...sommation journali re de combustible Qfuel kWh Coordonn es de contact Si le Cdh n est pas d termin par des mesures le coefficient de d gradation par d faut est Cdh 0 9 non applicable Pour les disposit...

Page 50: ...FR 16 452234 66 76 FD 9912 www gdts one Fran ais WI 140TUR...

Page 51: ...plan Standardregler Terminal diagram for standard controller Sch ma de branchement du r gulateur standard A XI 3 6 Anschlussplan Standardregler Terminal diagram for standard controller Sch ma de branc...

Page 52: ...rn Input into HP 1 1 2 internal external thread Hot water flow Output from HP 3 external thread Heat flow Output from HP 3 external thread Heat source Input into HP 1 1 2 internal external thread Hot...

Page 53: ...water or cold water flow rate in m h D bit l eau chauffage et l eau froide en m h Druckverlust in Pa Pressure loss in Pa Perte de pression en Pa Leistungszahl incl Pumpenleistungsanteil Coefficient of...

Page 54: ...C Bedingungen Conditions Conditions K hlwasserdurchsatz Cooling water throughput D bit de l eau de rafra chissement 24 2 m h Kaltwasserdurchsatz Cold water flow D bit d eau froide 33 5 m h 1 Verdicht...

Page 55: ...peratur C Heating water temperature C Temp rature d eau de chauffage C W rmequelleneintrittstemperatur C Heat source inlet temperature C Temp rature d entr e de la source de chaleur C Wasseraustritt 2...

Page 56: ...issement 0 5 10 15 20 25 0 5 10 15 20 25 30 35 K hlwassertemperatur C Cooling water temperature C Temp rature d eau de rafra chissement C W rmesenkeneintrittstemperatur C Heat sink inlet temperature C...

Page 57: ...ne 452234 66 76 FD 9912 A VII WI 140TUR Anhang Appendix Annexes 3 Stromlaufpl ne Circuit diagrams Sch mas lectriques 3 1 Steuerung Standardregler Control via the standard controller Commande r gulateu...

Page 58: ...A VIII 452234 66 76 FD 9912 www gdts one Anhang Appendix Annexes WI 140TUR 3 2 Steuerung Standardregler Control via the standard controller Commande r gulateur standard...

Page 59: ...www gdts one 452234 66 76 FD 9912 A IX WI 140TUR Anhang Appendix Annexes 3 3 Steuerung K hlmodul Cooling module control Commande module de rafra chissement...

Page 60: ...A X 452234 66 76 FD 9912 www gdts one Anhang Appendix Annexes WI 140TUR 3 4 Last Load Charge...

Page 61: ...www gdts one 452234 66 76 FD 9912 A XI WI 140TUR Anhang Appendix Annexes 3 5 Anschlussplan Standardregler Terminal diagram for standard controller Sch ma de branchement du r gulateur standard...

Page 62: ...A XII 452234 66 76 FD 9912 www gdts one Anhang Appendix Annexes WI 140TUR 3 6 Anschlussplan Standardregler Terminal diagram for standard controller Sch ma de branchement du r gulateur standard...

Page 63: ...www gdts one 452234 66 76 FD 9912 A XIII WI 140TUR Anhang Appendix Annexes 3 7 Anschlussplan K hlmodul Circuit diagram of cooling module Sch ma lectrique module de rafra chissement...

Page 64: ...on moteur M1 F19 Motorschutz M3 Motor protection M3 Protection moteur M3 F20 Thermostat Schaltkasten Thermostat for switch box Thermostat bo tier lectrique F21 Sicherung f r Ausg nge N17 1 und N17 2 5...

Page 65: ...eis Flow sensor primary circuit Sonde d part circuit primaire R7 Codierwiderstand Coding resistor R sistance de codage R9 Vorlauff hler Heizkreis Flow sensor for heating circuit Sonde aller circuit de...

Page 66: ...heating cooling domestic hot water and swimming pool water preparation Installation mono nerg tique optimis e pour le chauffage et le rafra chissement la production d eau chaude sanitaire et d eau de...

Page 67: ...on Installation mono nerg tique pour le chauffage et le rafra chissement la production d eau chaude sanitaire et d eau de piscine X3 R1 T R1 X2 K20 E10 1 K21 E9 N1 N011 M15 X3 R5 R5 N1 N012 N013 M22 X...

Page 68: ...rchflussschalter Sekund rkreis Flow rate switch secondary circuit Commutateur de d bit circuit secon K20 Sch tz 2 W rmeerzeuger Contactor for HG2 Contacteur du 2 me g n rateur de chaleur K21 Sch tz Fl...

Page 69: ...ature sensor for heating circuit 2 Sonde de temp rature 2 me circuit de chauffage R13 F hler 3 Heizkreis F hler regenerativ Sensor for heating circuit 3 renewable sensor Sonde 3 me circuit de chauffag...

Page 70: ...rkl rung Declaration of Conformity D claration de conformit Die aktuelle CE Konformit tserkl rung finden sie als Download unter You can find and download the current CE conformity declaration at Vous...

Page 71: ...www gdts one 452234 66 76 FD 9912 A XXI WI 140TUR Anhang Appendix Annexes...

Page 72: ...tschland GmbH Gesch ftsbereich GDTS Am Goldenen Feld 18 D 95326 Kulmbach Irrt mer und nderungen vorbehalten Subject to alterations and errors Sous r serve d erreurs et modifications 49 0 9221 709 9245...

Reviews: