Commissioning
English
P14 – Charge control signal faulty
In the event of a faulty signal from the central charge
control, the storage heater is charged to its maximum
level.
If this is to be changed to no charge, proceed as set
out below.
Call up the installer menu.
Confirm the PIN code four times with the ENTER
key. Display P9 flashes.
Use the
keys to select P14. Display flashes.
Press the ENTER key. ON flashes.
Use the
keys to select OFF. OFF flashes.
Press the ENTER key. Setting is complete.
P15 - adjustment of the charge rate
Adjustment (increase or lowering) of the specified
charging in increments of 10%.
Call up the installer menu.
Confirm the PIN code four times with the ENTER
key. Display P9 flashes.
Use the
keys to select P15. Display flashes.
Press the ENTER key. 00 flashes.
Use the
keys to carry out the adjustment
(range -50% to +50%). Value flashes.
Press the ENTER key. Setting complete.