Commissioning
P11 – Supplementary heating Yes/No
NOTE
i
The supplementary heating is available as an acces
-
sory and is not installed at the factory.
Enter whether operation is to take place with or with
-
out supplementary heating.
Call up the installer menu.
Confirm the PIN code four times with the ENTER
key. Display P9 flashes.
Use the
keys to select P11. Display flashes.
Press the ENTER key. ON flashes.
Operation with supplementary heating:
Press the ENTER key. Setting is complete.
Operation without supplementary heating:
Use the
keys to select OFF. OFF flashes.
Press the ENTER key. Setting is complete.
P12 – Release signal
Function for future charge release directly on the stor
-
age heater. Currently without function.
NOTE
i
This menu item may be shown or not shown depend
-
ing on the version. Do not change the setting values!
P13 – Release manual
NOTE
i
Only required if there is a continuous voltage on the
terminals L1, L2, L3 and no release takes place by the
energy supplier or grid operator.
Call up the installer menu.
Confirm the PIN code four times with the ENTER
key. Display P9 flashes.
Use the
keys to select P13. Display flashes.
Press the ENTER key. A1 flashes.
Press the ENTER key. The hours display flashes.
Use the
keys to set the hour for the start of
the release.
NOTE
i
When entering the release times, always start with the
lowest hour, e.g. 00:00.
Example:
The release times 22:00 to 06:00 and 14:00 to 16:00
should be set.
Set A1 ON to 00:00 and A1 OFF to 06:00.
Set A2 ON to 14:00 and A2 OFF to 16:00.
Set A3 ON to 22:00 and A3 OFF to 23:59.
A4 ON and A4 OFF remain on 23:59.