EN-10 452232.66.23 · FD 9204
www.dimplex.de
English
SIH 6ME - SIH 11ME
12 Device Information
1
Type and order code
SIH 6ME
SIH 9ME
SIH 11ME
2
Design
2.1
Degree of protection according to EN 60 529
IP 20
IP 20
IP 20
2.2
Installation Location
Indoors
Indoors
Indoors
3
Performance data
3.1
Operating temperature limits:
Heating water flow
1
°C
1. For brine temperatures between -5 °C and 0 °C, flow temperature increasing from 65 °C to 70 °C
70±2
70±2
70±2
Brine (heat source)
°C
-5 to +25
-5 to +25
-5 to +25
Antifreeze
Mono-ethylene glycol
Mono-ethylene glycol
Mono-ethylene glycol
Minimum brine concentration (-13 °C freezing temperature)
25%
25%
25%
3.2
Temperature spread of heating water (flow/return flow)
at B0 / W35
K
10.,6
5.0
10.3
5.0
9.3
5.0
3.3
Heat output / COP
at B-5 / W55
2
kW / ---
2. This data indicates the size and capacity of the system. For an analysis of the economic and energy efficiency of the system, both the bivalence point and the regulation should
also be taken into consideration. The specified values, e.g. B10 / W55, have the following meaning: Heat source temperature 10 °C and heating water flow temperature 55 °C.
4.9 / 2.2
7.9 / 2.2
8.9 / 2.5
at B0 / W45
2
kW / ---
5,8 / 3,4
8,6 / 3,4
10.0 / 3.5
at B0 / W50
2
kW / ---
5.8 / 3.0
8.9 / 3.1
10.3 / 3.3
at B0 / W35
2
kW / ---
6.2 / 4.3
6.0 / 4.1
9.1 / 4.2
8.9 / 4.0
10.8 / 4.6
10.7 / 4.5
3.4
Sound power level to EN 12102
dB(A)
56
56
57
3.5
Heating water flow with an internal pressure differential of m³/h / Pa
0.5 / 1200 1.0 / 4100 0.76 /1700 1.55 / 6400 1.0 / 1600 1.9 / 7000
3.6
Brine throughput with an internal pressure
differential (heat source) of
m³/h / Pa
1.30 /8900 1.30 /8900 2.0 / 7500 2.0 / 7500 2.45 /8000 2.45 / 8000
3.7
Refrigerant; total filling weight
type / kg
R134a / 1.8
R134a / 2.2
R134a / 2.4
3.8
Lubricant; total filling weight
type / litres
Polyolester (POE) /
1.1
Polyolester (POE) /
1.95
Polyolester (POE) /
1.90
4
Dimensions, connections and weight
4.1
Device dimensions without connections
3
H x W x L mm
3. Note that additional space is required for pipe connections, operation and maintenance.
805
650
462
805
650
462
805
650
462
4.2
Device connections to heating system
Inch
G 1¼" a
G 1¼" a
G 1¼" a
4.3
Device connections to heat source
Inch
G 1¼" a
G 1¼" a
G 1¼" a
4.4
Weight of the transportable unit(s) incl. packing
kg
118
130
133
5
Electrical Connection
5.1
Nominal voltage; fuse protection
V / A
230 / 20
230 / 25
230 / 32
5.2
Nominal power consumption
2
B0 W35
kW
1.44
1.47
2.17
2.22
2.34
2.36
5.3
Starting current with soft starter
A
38
43
45
5.4
Nominal current B0 W35 / cos
A / ---
9.2 / 0.8
9.3 / 0.8
11.1 / 0.8
11.2 / 0.8
12.4 / 0.8
12.4 / 0.8
6
Complies with the European safety regulations
4
4. See CE declaration of conformity
4
4
7
Additional model features
7.1
Water in device protected against freezing
5
5. The heat circulating pump and the heat pump manager must always be ready for operation.
Yes
Yes
Yes
7.2
Performance levels
1
1
1
7.3
Controller internal/external
Internal
Internal
Internal
7.4
Max. operating overpressure (heat source/heat sink) bar
3,0
3,0
3,0
Summary of Contents for SIH 11ME
Page 2: ......
Page 14: ...DE 12 452232 66 23 FD 9204 www dimplex de Deutsch SIH 6ME SIH 11ME ...
Page 49: ...www dimplex de 452232 66 23 FD 9204 A XV Anhang Appendix Annexes SIH 6ME SIH 11ME ...
Page 50: ...A XVI 452232 66 23 FD 9204 www dimplex de Anhang Appendix Annexes SIH 6ME SIH 11ME ...
Page 51: ...www dimplex de 452232 66 23 FD 9204 A XVII Anhang Appendix Annexes SIH 6ME SIH 11ME ...