7.5.2 Electrical installation work 

1)

The four-core electrical supply cable for the heat pump
power part is fed from the heat pump electricity meter into
the heat pump via the utility company blocking contactor (if
required) (for supply voltage, see heat pump manual).
The mains cable is connected to the heat pump contact
plate via terminals X1: L1/L2/L3/PE.

ATTENTION!

Ensure that there is a clockwise rotating field: With incorrect wiring the
starting of the heat pump is prevented. A corresponding warning is
indicated on the display of the heat pump manager (adjust wiring).

An all-pole disconnecting device with a contact gap of at least
3 mm (e.g. utility company blocking contactor or power contac-
tor) and an all-pole circuit breaker with common tripping for all
external conductors must be installed in the power supply for the
heat pump (tripping current and characteristic in compliance with
the device information).
2)

The three-core supply cable for the heat pump manager
(heating controller N1) is fed into the heat pump. Connection
of the control cable to the contact plate of the heat pump via
terminal X2: L/N/PE.
The (L/N/PE~230 V, 50 Hz) supply cable for the heat pump
manager must have a continuous voltage. For this reason, it
should be tapped upstream from the utility company block-
ing contactor or be connected to the household current, as
important protection functions could otherwise be lost during
a utility block.

3)

The utility company blocking contactor (K22) with main con-
tacts and an auxiliary contact must be designed and pro-
vided by the customer in accordance with the heat pump
output.
The NO contact of the utility company blocking contactor is
looped from the terminal strip X3/G to the plug-in terminal
X3/ID3. 

CAUTION! Extra-low voltage

!

4)

The contactor (K20) for the immersion heater (E10) of mono
energy systems (HG2) should be dimensioned according to
the radiator output and must be supplied by the customer. It
is controlled (230 V AC) by the heat pump manager via ter-
minals X2/N and X2/K20.

5)

The contactor (K21) for the flange heater (E9) in the domes-
tic hot water cylinder should be dimensioned according to
the radiator output and must be supplied by the customer. It
is controlled (230 V AC) by the heat pump manager via ter-
minals X2/N and X2/K21.

6)

The contactors mentioned above in points 3, 4 and 5 are in-
stalled in the electrical distribution system. 

7)

All installed electric cables must have permanent wiring.

8)

The heat circulating pump (M13) is activated via the contact
N1-J13/NO5. The connection points for the pump are X2/
M13 and X2/N. When using pumps where the switching ca-
pacity exceeds the output, a coupling relay must be inter-
posed.

9)

The auxiliary circulating pump (M16) is activated via the con-
tact N1-J16/NO9. The connection points for the pump are
X2/M16 and X2/N. A coupling relay is already integrated in
this output.

10) The domestic hot water circulating pump (M18) is activated

via the contact N1-J13/NO6. The connection points for the
pump are X2/M18 and X2/N. When using pumps where the
switching capacity exceeds the output, a coupling relay must
be interposed.

11) The brine or well pump (M11) is activated via the contact N1-

J12/NO3. The connection points for the pump are X2/M11
and X2/N. A coupling relay is already integrated in this out-
put.

12) The return sensor (R2) is integrated in the heat pumps for in-

door installation. 
The heat pump manager is connected via the following ter-
minals: X3/GND and X3/R2.

13) The external sensor (R1) is connected to terminals X3/GND

and X3/R1.

14) The domestic hot water sensor (R3) is included with the do-

mestic hot water cylinder and is connected to terminals GND
and X3/R3.

7.5.3 Connection of electronically 

regulated circulating pumps

Electronically regulated circulating pumps have high starting cur-
rents, which may shorten the service life of the heat pump man-
ager. For this reason, a coupling relay is installed or must be in-
stalled between the output of the heat pump manager and the
electronically regulated circulating pump. This is not necessary if
the permissible operating current of 2 A and a maximum starting
current of 12 A are not exceeded in the electronically regulated
circulating pump or if express approval has been issued by the
pump manufacturer. 

ATTENTION!

It is not permitted to connect more than one electronically regulated
circulating pump via a relay output.

Summary of Contents for SI 26TU

Page 1: ...ation Installation and Operating Instructions Sole Wasser W rmepumpe f r Innenaufstellung SI 26TU SI 35TU Brine to Water Heat Pump for Indoor Installation Pompe chaleur eau glycol e eau pour installat...

Page 2: ......

Page 3: ...r Anschluss DE 6 7 4 Temperaturf hler DE 6 7 5 Elektrischer Anschluss DE 7 8 Inbetriebnahme DE 9 8 1 Allgemeine Hinweise DE 9 8 2 Vorbereitung DE 9 8 3 Vorgehensweise bei Inbetriebnahme DE 9 9 Pflege...

Page 4: ...mpe ist der beiliegende Schmutz f nger zu montieren um den Verdampfer gegen Verunreinigungen zu sch tzen ACHTUNG Vor ffnen des Ger tes sind alle Stromkreise spannungsfrei zu schalten 1 2 Bestimmungsge...

Page 5: ...das K ltemittel im K ltekreislauf abgegeben Dabei k hlt sich die Sole wieder ab so dass sie im Solekreis wieder W rmeenergie aufnehmen kann Das K ltemittel wird vom elektrisch angetriebenen Verdichte...

Page 6: ...n dungen m glich Modbus EIB KNX Ethernet ACHTUNG Bei einer externen Ansteuerung der W rmepumpe bzw der Umw lzpum pen ist ein Durchflussschalter vorzusehen der das Einschalten des Ver dichters bei fehl...

Page 7: ...er heizungsseitiger Installation ist die Heizungsan lage zu f llen zu entl ften und abzudr cken ACHTUNG Der maximale Pr fdruck betr gt heiz und soleseitig 6 0 bar Dieser Wert darf nicht berschritten w...

Page 8: ...s mindestens zu 25 aus einem Frostschutz auf Monoethy lenglykol oder Propylenglykolbasis bestehen und ist vor dem Bef llen zu mischen HINWEIS Bei Bedarf kann der Einsatzbereich bis zu einer Soleeintri...

Page 9: ...h vorhandene Hohlraum zwischen F hler und Tauchh lse muss mit W rmeleitpaste voll st ndig ausgef llt sein Doppelt differenzdruckloser Verteiler Der R cklauff hler muss in die Tauchh lse des doppelt di...

Page 10: ...tung auszu legen und bauseits beizustellen Die Ansteuerung 230 V AC erfolgt aus dem WPM ber die Klemmen X2 N und X2 K21 6 Die Sch tze der Punkte 3 4 5 werden in die Elektrovertei lung eingebaut 7 Alle...

Page 11: ...Heizungsseite Sauerstoff kann im Heizwasserkreis insbesondere bei Verwen dung von Stahlkomponenten Oxidationsprodukte Rost bilden Diese gelangen ber Ventile Umw lzpumpen oder Kunststoff rohre in das...

Page 12: ...andesspezifischen Gesetze k nnen eventuell von der Verordnung EG 842 2006 abweichen Die jeweiligen Landesgesetze zur Dichtheitspr fung von W rmepumpen sind zu beachten 10 St rungen Fehlersuche Diese W...

Page 13: ...4000 6 4 82000 Mindestsoledurchfluss m h Pa 4 9 54000 6 4 82000 4 3 Schall Leistungspegel nach EN 12102 dB A 57 58 4 4 Schalldruck Pegel in 1 m Entfernung3 dB A 41 42 5 Abmessungen Gewicht und F llmen...

Page 14: ...s zu einer Soleeintrittstemperatur von 35 C m glich Bei Soleeintrittstemperaturen von 25 C bis 35 C Vorlauftemperatur von 62 C bis 58 C fallend 3 Der angegebene Schalldruckpegel entspricht dem Betrieb...

Page 15: ...Lieferer bezogene Teile und Ger te Anlagen m ngel die auf nicht vom Lieferer bezogene Teile zur ckzuf h ren sind fallen nicht unter den Garantieanspruch Bei endg ltig fehlgeschlagener Nachbesserung w...

Page 16: ...DE 14 452237 66 01 FD 9603 www dimplex de Deutsch SI 26TU SI 35TU...

Page 17: ...source connection EN 6 7 4 Temperature sensor EN 6 7 5 Electrical connection EN 7 8 Commissioning EN 9 8 1 General Information EN 9 8 2 Preparation EN 9 8 3 Commissioning procedure EN 9 9 Cleaning ma...

Page 18: ...ns of the heat pump manager ATTENTION The supplied dirt trap must be inserted in the heat source inlet of the heat pump to protect the evaporator against the ingress of impurities ATTENTION Disconnect...

Page 19: ...ant in the refriger ation circuit This cools the brine so that it can once again absorb thermal energy in the brine circuit The refrigerant is drawn in by the electrically driven compressor compressed...

Page 20: ...an be made on the heat pump manager Modbus EIB KNX Ethernet ATTENTION If the heat pump or circulating pumps are controlled externally a flow rate switch is required to prevent the compressor from bein...

Page 21: ...must be filled de aerated and pressure tested ATTENTION The maximum test pressure in the heating circuit and the brine circuit is 6 0 bar This value must not be exceeded The following points must be...

Page 22: ...monoethylene glycol or propylene glycol based antifreeze which must be mixed before filling NOTE If necessary the operating range can be extended to a brine inlet temperature of 10 C In this case the...

Page 23: ...stalled in the immersion sleeve The remaining empty space be tween the sensor and the immersion sleeve must be filled com pletely with heat transfer compound Dual differential pressureless manifold In...

Page 24: ...ater E9 in the domes tic hot water cylinder should be dimensioned according to the radiator output and must be supplied by the customer It is controlled 230 V AC by the heat pump manager via ter minal...

Page 25: ...sion re sistant installation is therefore essential especially with regard to the piping of underfloor heating systems NOTE We recommend the installation of a suitable corrosion protection system to p...

Page 26: ...signed for trouble free operation In the event that a fault should occur it will be in dicated on the heat pump manager display In this case consult the Faults and troubleshooting page in the operatin...

Page 27: ...ccording to EN 12102 dB A 57 58 4 4 Sound pressure level at a distance of 1m3 dB A 41 42 5 Dimensions weight and filling quantity 5 1 Device dimensions 4 H x W x L mm 885 x 1000 x 810 885 x 1000 x 810...

Page 28: ...tures of 25 C to 35 C flow temperature decreasing from 62 C to 58 C 3 The specified sound pressure level corresponds to the operating noise of the heat pump in heating operation at 55 C flow temperatu...

Page 29: ...dement c t source de chaleur FR 6 7 4 Sonde de temp rature FR 6 7 5 Branchements lectriques FR 7 8 Mise en service FR 9 8 1 Remarques d ordre g n ral FR 9 8 2 Pr paratifs FR 9 8 3 Proc dures suivre lo...

Page 30: ...relais ATTENTION La mise en service doit s effectuer conform ment aux instructions de montage et d utilisation du gestionnaire de pompe chaleur ATTENTION Avant d ouvrir l appareil tous les circuits le...

Page 31: ...e la pompe chaleur o la chaleur est transmise au fluide frigorig ne du circuit frigorifique Par cette op ration l eau glycol e se refroidit et peut donc nouveau absorber de l nergie thermique dans le...

Page 32: ...ur sont les suivantes Modbus EIB KNX Ethernet ATTENTION En cas de commande externe de la pompe chaleur ou des circulateurs pr voir un commutateur de d bit servant emp cher la mise en marche du compres...

Page 33: ...tre remplie purg e et prouv e la pression ATTENTION La pression d preuve maximale s l ve c t chauffage et c t eau glycol e 6 0bars Cette valeur ne doit pas tre d pass e Respecter les consignes suivant...

Page 34: ...ycol e en produit antigel base de mono thyl ne glycol ou propyl ne glycol doit tre d au moins 25 et le m lange doit tre effectu avant le remplissage REMARQUE En cas de besoin la plage d exploitation p...

Page 35: ...le doigt de gant L espace restant entre la sonde et le doigt de gant doit tre enti rement combl avec de la p te thermoconductrice Distributeur double sans pression diff rentielle La sonde retour doit...

Page 36: ...via les bornes X2 N et X2 K20 5 Le contacteur K21 de la cartouche chauffante E9 mont e dans le ballon d eau chaude sanitaire doit tre dimensionn en fonction de la puissance de la r sistance et fourni...

Page 37: ...er la formation de produits d oxydation rouille dans le circuit d eau de chauffage notam ment lorsque des composants en acier sont utilis s Ces produits d oxydation gagnent le syst me de chauffage par...

Page 38: ...ger du r glement CE 842 2006 Respecter les lois en vigueur dans le pays en ce qui concerne l essai d tanch it des pompes chaleur 10 D fauts recherche de pannes Cette pompe chaleur est un produit de qu...

Page 39: ...e puissance acoustique selon EN 12102 dB A 57 58 4 4 Niveau de pression sonore 1m de distance3 dB A 41 42 5 Dimensions poids et capacit 5 1 Dimensions de l appareil4 H x l x L mm 885 x 1000 x 810 885...

Page 40: ...de l eau glycol e de 35 C une temp rature d entr e de l eau glycol e comprise entre 25 C et 35 C temp rature d part d croissante de 62 C 58 C 3 Le niveau de pression sonore indiqu correspond au bruit...

Page 41: ...XIII 3 8 Steuerung Control Commande SI 35TU A XIV 3 9 Last Load Charge SI 35TU A XV 3 10 Anschlussplan Connection Plan Sch ma de connexion SI 35TU A XVI 3 11 Anschlussplan Connection Plan Sch ma de c...

Page 42: ...VLJQDOLVDWLRQ IDLEOH WHQVLRQ HL XQJVYRUODXI XVJDQJ DXV lUPHSXPSH HL XQJVU FNODXI LQJDQJ LQ lUPHSXPSH lUPHTXHOOH LQJDQJ LQ lUPHSXPSH lUPHTXHOOH XVJDQJ DXV lUPHSXPSH HDW VRXUFH HDW SXPS LQOHW H WHUQDO...

Page 43: ...3UHVVXUH ORVV LQ 3D 3HUWH GH SUHVVLRQ HQ 3D 9HUGDPSIHU YDSRUDWRU YDSRUDWHXU UXFNYHUOXVW LQ 3D 3UHVVXUH ORVV LQ 3D 3HUWH GH SUHVVLRQ HQ 3D 6ROHHLQWULWWVWHPSHUDWXU LQ ULQH LQOHW WHPSHUDWXUH LQ 7HPSpUDW...

Page 44: ...WH GH SUHVVLRQ HQ 3D 9HUGDPSIHU YDSRUDWRU YDSRUDWHXU UXFNYHUOXVW LQ 3D 3UHVVXUH ORVV LQ 3D 3HUWH GH SUHVVLRQ HQ 3D 6ROHHLQWULWWVWHPSHUDWXU LQ ULQH LQOHW WHPSHUDWXUH LQ 7HPSpUDWXUH G HQWUpH G HDX JO FR...

Page 45: ...e des seuils d utilisation HL ZDVVHUWHPSHUDWXU HDWLQJ ZDWHU WHPSHUDWXU H 7HPSpUDWXUH G HDX FKDXIIDJH lUPHTXHOOHQHLQWULWWVWHPSHUDWXU HDW VRXUFH LQOHW WHPSHUDWXUH 7HPSpUDWXUH G HQWUpH GH OD VRXUFH GH FK...

Page 46: ...A VI 452237 66 01 FD 9603 Anhang Appendix Annexes SI 26TU SI 35TU 3 Stromlaufpl ne Circuit Diagrams Sch mas lectriques 3 1 Steuerung Control Commande SI 26TU...

Page 47: ...www dimplex de 452237 66 01 FD 9603 A VII Anhang Appendix Annexes SI 26TU SI 35TU 3 2 Steuerung Control Commande SI 26TU...

Page 48: ...A VIII 452237 66 01 FD 9603 Anhang Appendix Annexes SI 26TU SI 35TU 3 3 Last Load Charge SI 26TU...

Page 49: ...www dimplex de 452237 66 01 FD 9603 A IX Anhang Appendix Annexes SI 26TU SI 35TU 3 4 Anschlussplan Connection Plan Sch ma de connexion SI 26TU...

Page 50: ...A X 452237 66 01 FD 9603 Anhang Appendix Annexes SI 26TU SI 35TU 3 5 Anschlussplan Connection Plan Sch ma de connexion SI 26TU...

Page 51: ...gaz chaud F10 1 Durchflussschalter Prim rkreis Flow rate switch for primary circuit Commutateur de d bit circuit primaire F10 2 Durchflussschalter Sekund rkreis Flow rate switch for secondary circuit...

Page 52: ...pression pO R26 Drucksensor K ltekreis Hochdruck pc Pressure sensor for refrigerating circuit high pressure pc Capteur de pression circuit r frig rant haute pression pc R27 Sauggasf hler Suction gas s...

Page 53: ...www dimplex de 452237 66 01 FD 9603 A XIII Anhang Appendix Annexes SI 26TU SI 35TU 3 7 Steuerung Control Commande SI 35TU...

Page 54: ...A XIV 452237 66 01 FD 9603 Anhang Appendix Annexes SI 26TU SI 35TU 3 8 Steuerung Control Commande SI 35TU...

Page 55: ...www dimplex de 452237 66 01 FD 9603 A XV Anhang Appendix Annexes SI 26TU SI 35TU 3 9 Last Load Charge SI 35TU...

Page 56: ...A XVI 452237 66 01 FD 9603 Anhang Appendix Annexes SI 26TU SI 35TU 3 10 Anschlussplan Connection Plan Sch ma de connexion SI 35TU...

Page 57: ...www dimplex de 452237 66 01 FD 9603 A XVII Anhang Appendix Annexes SI 26TU SI 35TU 3 11 Anschlussplan Connection Plan Sch ma de connexion SI 35TU...

Page 58: ...haud F10 1 Durchflussschalter Prim rkreis Flow rate switch for primary circuit Commutateur de d bit circuit primaire F10 2 Durchflussschalter Sekund rkreis Flow rate switch for secondary circuit Commu...

Page 59: ...basse pression pO R26 Drucksensor K ltekreis Hochdruck pc Pressure sensor for refrigerating circuit high pressure pc Capteur de pression circuit r frig rant haute pression pc R27 Sauggasf hler Suctio...

Page 60: ...ente W rmepumpenanlage mit 3 Heizkreisen und Warmwasserbereitung Monovalent heat pump system with three heating circuits and domestic hot water preparation Installation monovalente de pompe chaleur av...

Page 61: ...lage mit zwei Heizkreisen und Warmwasserbereitung Bivalent system with two heating circuits and domestic hot water preparation Installation bivalente avec deux circuits de chauffage et production d ea...

Page 62: ...ampon en s rie Warmwasserspeicher Hot water cylinder Ballon d eau chaude sanitaire E9 Flanschheizung Warmwasser Flange heater hot water Cartouche chauffante ECS E10 2 l Gaskessel Oil gas boiler Chaudi...

Page 63: ...SI 26TU Type s SI 35TU Type s EG Richtlinien Niederspannungsrichtlinie 2006 95 EG EMV Richtlinie 2004 108 EG Druckger terichtlinie 97 23 EG EC Directives Low voltage directive 2006 95 EC EMC directiv...

Page 64: ...rigorig ne F llmenge in kg __________________________________________ Total content weight in kg Quantit de remplissage en kg Hermetisch geschlossen ja nein hermetically sealed yes no Herm tiquement f...

Page 65: ...www dimplex de 452237 66 01 FD 9603 A XXV Anhang Appendix Annexes SI 26TU SI 35TU...

Page 66: ...A XXVI 452237 66 01 FD 9603 Anhang Appendix Annexes SI 26TU SI 35TU...

Page 67: ...www dimplex de 452237 66 01 FD 9603 A XXVII Anhang Appendix Annexes SI 26TU SI 35TU...

Page 68: ...schland GmbH Gesch ftsbereich Dimplex Am Goldenen Feld 18 D 95326 Kulmbach Irrt mer und nderungen vorbehalten Subject to alterations and errors Sous r serve d erreurs et modifications 49 0 9221 709 56...

Reviews: