background image

www.dimplex.de

E-8

English

10

8 Maintenance / Cleaning

8.1

Maintenance

To protect the paintwork, avoid leaning or putting objects on the
device. External heat pump parts can be wiped with a damp cloth
and domestic cleaner.

ATTENTION!

Never use cleaning agents containing sand, soda, acid or chloride as
these can damage the surfaces.

To prevent faults due to sediment in the heat exchanger of the
heat pump, ensure that the heat exchanger in the heating system
can not be contaminated. We recommend protecting the evapo-
rator by installing a bird guard in the inlet duct. At least 80 % of
the cross section of the grating should be open. In the event that
operating malfunctions due to contamination still occur, the sys-
tem should be cleaned as described below.

8.2

Cleaning the Heating System

The ingress of oxygen into the heating water circuit may result in
the formation of oxidation products (rust), particularly if steel
components are used. These products enter the heating system
via the valves, the circulating pumps and/or plastic pipes. It is
therefore essential - in particular with respect to the piping of un-
derfloor heating systems - that only diffusion-proof materials are
used.

ATTENTION!

We recommend the installation of a suitable corrosion protection system
to prevent the formation of deposits (e.g. rust) in the condenser of the
heat pump.

Residue from lubricants and sealants may also contaminate the
heating water.

In the case of severe contamination leading to a reduction in the
performance of the liquifier in the heat pump, the system must be
cleaned by a heating technician.

According to today's state of knowledge, we recommend using a
5 % phosphoric acid solution for cleaning purposes. However, if
cleaning needs to be performed more frequently, a 5 % formic
acid solution should be used.

In either case, the cleaning fluid should be at room temperature.
We recommend flushing the heat exchanger in the direction op-
posite to the normal flow direction.

To prevent acidic cleaning agents from entering the heating sys-
tem circuit, we recommend connecting the flushing device di-
rectly to the flow and return flow of the liquifier of the heat pump.

It is important that the system be thoroughly flushed using appro-
priate neutralising agents to prevent any damage from being
caused by cleaning agent residue remaining in the system.

Acids must be used with great care and all relevant regulations of
the employers' liability insurance associations must be adhered
to.

If in doubt, contact the manufacturer of the chemicals!

The buffer tank is drained using the filling and drain cocks on the
lower left of the device. Also open the ball valve on the pressure
expansion vessel to vent the buffer tank.

8.3

Cleaning the Air System

Air ducts, evaporator, ventilator and condensate outflow should
be cleaned of contamination (leaves, twigs, etc.) before the heat-
ing period. Do this by opening the left and front sides of the heat
pump. The bottom should be opened first followed by the top.

ATTENTION!

Before opening the device, ensure that all circuits are isolated from the
power supply.

Remove and rehang the side panel assemblies as described in
Chapter 4.

To prevent the evaporator and the condensate tray from being
damaged, do not use hard or sharp objects for cleaning.

9 Faults / Trouble-

Shooting

This heat pump is a quality product and is designed for trouble-
free and maintenance-free operation. In the event that a fault
should occur, it will be shown on the heat pump manager display.
Simply consult the Faults and Trouble-shooting page in the oper-
ating instructions of the heat pump manager. If you cannot cor-
rect the fault yourself, please contact your after-sales service
technician.

ATTENTION!

Work on the heat pump may only be carried out by authorised and
qualified after-sales service technicians. 

10 Decommissioning/

Disposal

Before removing the heat pump, disconnect it from the power
source and close all valves. Observe all environmentally-relevant
requirements regarding the recovery, recycling and disposal of
materials and components in accordance with all applicable
standards. Particular attention should be paid to the proper dis-
posal of refrigerants and refrigeration oils.

Summary of Contents for LIK 8MER

Page 1: ...at Pump for Indoor Installation Pompe à chaleur air eau réversible pour installation intérieure Montage und Gebrauchsanweisung Deutsch English Français Instructions d installation et d utilisation Installation and Operating Instructions Bestell Nr Order no No de commande 452160 66 23 FD 8611 ...

Page 2: ...ansport E 4 5 Set UP E 5 5 1 General Information E 5 5 2 Condensed Water Pipe E 5 5 3 Sound E 5 6 Installation E 5 6 1 General Information E 5 6 2 Air Connection E 5 6 3 Heating System Connection E 6 6 4 Electrical Connection E 6 7 Start UP E 7 7 1 General Information E 7 7 2 Preparation E 7 7 3 Start Up Procedure E 7 8 Maintenance Cleaning E 8 8 1 Maintenance E 8 8 2 Cleaning the Heating System E...

Page 3: ...apable of operating the device safely due to their physical sensory or mental abilities or their inexperience or lack of knowledge must not operate this device without supervision or instruction by the person in charge Children must be supervised to ensure that they do not play with the device 1 3 Energy Efficient Use of the Heat Pump With the purchase of this heat pump you are helping to protect ...

Page 4: ...transferred to the heating water using the liquifier heat ex changer Electrical energy is used to raise the temperature of the heat in the environment to a higher level Because the energy extracted from the air is transferred to the heating water this type of device is called an air to water heat pump The air to water heat pump consists of the main components evaporator ventilator and expansion va...

Page 5: ...2 Sealing rings for duct connection 3 1 connecting hoses 3 1 double nipples 6 1 flat gaskets 1 1 sealing plug 1 Hose nozzle for filling and drain cock 2 Fixing brackets 2 10 mm dowels 2 8 x 80 screws 4 M4 x 8 screws 1 External sensor 1 6 mm dowels 1 4 5 x 50 screws 4 Transport ATTENTION When transporting the heat pump ensure that it is not tilted more than 45 in any direction Use a wooden pallet f...

Page 6: ...o prevent solid borne sound from being transmitted to the heat ing system a vibration damped connection should be used for connecting the heat pump with the heating system install the supplied hose connections free of strain Installed air ducts should be sound isolated from the heat pump to prevent the transmission of solid borne sound to the ducts If both air openings are connected directly to a ...

Page 7: ...be filled de aerated and pressure tested The integrated expansion vessel has a volume of 24 litres This volume is suitable for buildings with a living space area to be heated of maximum 200 m The volume should be checked by the heating system engineer If necessary an additional expansion vessel must be installed according to DIN 4751 Part 1 The tables listed in the manufac turers catalogues simpli...

Page 8: ... and west sides of the building At least one heating circuit must remain open e g bathroom The overflow valve should be opened far enough to produce the maximum temperature spread between the heating flow and re turn flow listed in the following table for the current heat source temperature The temperature spread should be measured as close as possible to the heat pump The heating element of mono ...

Page 9: ...from entering the heating sys tem circuit we recommend connecting the flushing device di rectly to the flow and return flow of the liquifier of the heat pump It is important that the system be thoroughly flushed using appro priate neutralising agents to prevent any damage from being caused by cleaning agent residue remaining in the system Acids must be used with great care and all relevant regulat...

Page 10: ...eating water flow with an internal pressure differential of 2 m h Pa 2 The heat circulating pump is integrated 0 8 2700 1 6 11900 3 9 Free pressure heating circulating pump heating max stage Pa 45000 27000 3 10 Cooling water flow with an internal pressure differential of m h Pa 0 8 2700 1 2 6500 3 11 Free pressure circulating pump cooling max stage Pa 45000 37000 3 12 Air flow rate with an externa...

Page 11: ...roller Commande régulateur standard A VI 3 2 Steuerung Kühlregler Control of the cooling controller Commande régulateur standard A VII 3 3 Last Load Charge A VIII 3 4 Anschlussplan Standardregler Terminal diagram for the standard controller Schéma électrique du régulateur standard A IX 3 5 Anschlussplan Kühlregler Terminal diagram for the cooling controller Schéma électrique du régulateur refroidi...

Page 12: ...DJH LQWpULHXU H WpULHXU 5HIOX FRPPXQ QWUpH GDQV OD 3 LOHWDJHV LQW H W 5RELQHW GH UHPSOLVVDJH HW GH YLGDJH pSDUW HDX FKDXGH 6RUWLH GH OD 3 LOHWDJH LQW H W DVVHU DQVFKO VVH DWHU FRQQHFWLRQV 5DFFRUGHPHQWV HDX RQGHQVDWDEODXI VFKODXFK RQGHQVDWH RXWIORZ KRVH 7X DX HDX GH FRQGHQVDWLRQ XIWULFKWXQJ LUHFWLRQ RI DLU IORZ 6HQV G pFRXOHPHQW DLU HGLHQVHLWH 2SHUDWLQJ VLGH Wp GH FRPPDQGH QQHQJHZLQGH 0 LQWHUQDO WK...

Page 13: ...Q DFFHVVRU RQGXLW G DpUDWLRQ GLVSRQLEOH HQ DFFHVVRLUH 8PODXIHQGH EVFKUlJXQJ EDXVHLWV XU EGLFKWXQJ GHU 6WR NDQWH XQG 9HUEHVVHUXQJ GHU XIWI KUXQJ RQWLQXRXV FKDPIHU WR EH SURYLGHG E WKH FXVWRPHU WR VHDO WKH ERUGHU DQG WR IDFLOLWDWH DLU FLUFXODWLRQ KDQIUHLQ SpULSKpULTXH j IRXUQLU SDU OH FOLHQW DVVXUDQW O pWDQFKpLWp GX ERUG HW DPpOLRUDQW OD FRQGXLWH GH O DLU HL LQVDW HLQHV lPPVWUHLIHQV XQWHU GHU lUPHSX...

Page 14: ...Q 3D 3HUWH GH SUHVVLRQ HQ 3D HLVWXQJV DKO LQFO 3XPSHQOHLVWXQJVDQWHLO RHIILFLHQW RI SHUIRUPDQFH LQFO SRZHU LQSXW WR SXPS RHIILFLHQW GH SHUIRUPDQFH FRPSULV SDUW GH FRQVRPPDWLRQ GH OD SRPSH HL ZDVVHUGXUFKIOXVV LQ P K HDWLQJ ZDWHU IORZ UDWH LQ P K pELW G HDX GH FKDXIIDJH HQ P K HGLQJXQJHQ Â RQGLWLRQV Â RQGLWLRQV HL ZDVVHUGXUFKVDW HDWLQJ ZDWHU IORZ UDWH pELW G HDX GH FKDXIIDJH P K 9HUIO VVLJHU RQGHQVHU...

Page 15: ...PDWLRQ GH SXLVVDQFH FRPSULV SDUW GH FRQVRPPDWLRQ GH OD SRPSH UXFNYHUOXVW LQ 3D 3UHVVXUH ORVV LQ 3D 3HUWH GH SUHVVLRQ HQ 3D XIWHLQWULWWVWHPSHUDWXU LQ LU LQOHW WHPSHUDWXUH LQ 7HPSpUDWXUH G HQWUpH G DLU HQ XIWHLQWULWWVWHPSHUDWXU LQ LU LQOHW WHPSHUDWXUH LQ 7HPSpUDWXUH G HQWUpH G DLU HQ HLVWXQJV DKO LQFO 3XPSHQOHLVWXQJVDQWHLO RHIILFLHQW RI SHUIRUPDQFH LQFO SRZHU LQSXW WR SXPS RHIILFLHQW GH SHUIRUPDQFH ...

Page 16: ...A VI Anhang Appendix Annexes 3 3 Stromlaufpläne Circuit Diagrams Schémas électriques 3 1 Steuerung Standardregler Control of the standard controller Commande régulateur standard ...

Page 17: ... dimplex de A VII Anhang Appendix Annexes 3 2 3 2 Steuerung Kühlregler Control of the cooling controller Commande régulateur standard HJH 8PVFKDOWYHQWLO RXU ZD UHYHUVLQJ YDOYH 6RXSDSH GH FRPPXWDWLRQ YRLHV ...

Page 18: ...A VIII Anhang Appendix Annexes 3 3 3 3 Last Load Charge ...

Page 19: ...www dimplex de A IX Anhang Appendix Annexes 3 4 3 4 Anschlussplan Standardregler Terminal diagram for the standard controller Schéma électrique du régulateur standard ...

Page 20: ...endix Annexes 3 5 3 5 Anschlussplan Kühlregler Terminal diagram for the cooling controller Schéma électrique du régulateur refroidissement 7HPSHU 7HPS 7HPS HXFKWH XPLGLW XPLGLWp 7HPSHU 7HPS 7HPS HXFKWH XPLGLW XPLGLWp ...

Page 21: ...ilateur J13 J18 Relaisausgänge zur Ansteuerung der Systemkom ponenten 230 VAC Relay outputs for controlling system components 230 V AC Sorties de relais pour la commande des compo sants du système 230 V AC N2 J1 Stromversorgung N2 24VAC Power supply N2 24 V AC Alimentation en courant N2 24 V AC J2 J3 Sensoreingänge Sensor inputs Entrées de capteurs J4 Analogausgänge werden nicht genutzt Analogue o...

Page 22: ... terminal block Bornier distributeur charge réseau L N PE 230 V AC 50 Hz commande L N PE 230 V AC 50 Hz distributeur N et PE X2 1 Klemmenleiste Verteiler für 24VAC Terminal strip terminal block for 24 V AC Bornier distributeur distributeur pour 24 V AC X2 2 Klemmenleiste Verteiler für 0VAC Terminal strip terminal block for 0 V AC Bornier distributeur distributeur pour 0 V AC X2 3 Klemmenleiste Ver...

Page 23: ...www dimplex de A XIII Anhang Appendix Annexes 4 1 4 Hydraulisches Prinzipschema Hydraulic Plumbing Diagram Schéma hydraulique 4 1 Darstellung Schematic view Représentation ...

Page 24: ...cher Buffer tank Réservoir tampon Wärmepumpenregler Heat pump controller Régulateur de pompe à chaleur Elektroverteilung Electrical distribution system Distributeur courant électrique Warmwasserspeicher Hot water cylinder Ballon d eau chaude Kondensatablauf Condensate outflow Ecoulement des condensats Überdruck Heizwasser Overpressure of the heating water Surpression eau de chauffage E8 Zusatzheiz...

Page 25: ...www dimplex de A XV Anhang Appendix Annexes 5 5 Konformitätserklärung Declaration of Conformity Déclaration de conformité ...

Page 26: ...tschland GmbH Geschäftsbereich Dimplex Am Goldenen Feld 18 D 95326 Kulmbach Irrtümer und Änderungen vorbehalten Subject to alterations and errors Sous réserve d erreurs et modifications 49 0 9221 709 565 www dimplex de ...

Reviews: