www.dimplex.de
E-9
English
11
11 Device Information
Device information for air-to-water heat pumps (heating only)
1
Type and order code
LI 8MSR
2
Design
2.1
Model
Reversible
2.2
Degree of protection according to EN 60 529
IP21
2.3
Installation location
Indoors
3
Performance data
3.1
Operating temperature limits:
Heating water flow/return flow
1
°C / °C
1. See operating limits diagram
Up to 55 / above 18
Cooling, flow
°C
+7 to +20
Air (heating)
°C
-20 to +35
Air (cooling)
°C
+15 to +40
3.2
Temperature spread of heating water at A2 / W35
8.0
3.3
Heat output / COP
at A-7 / W35
2
kW / ---
2. This data indicates the size and capacity of the system. For an analysis of the economic and energy efficiency of the system, other parameters, such as, in particular, the defrosting
capacity, the bivalence point and regulation, should also be taken into consideration. The specified values, e.g. A2 / W55, have the following meaning: External temperature 2 °C
and heating water flow temperature 55 °C.
5.8 / 2.7
at A2 / W35
2
kW / ---
7.5 / 3.3
at A2 / W50
2
kW / ---
7.0 / 2.5
at A7 / W35
2
kW / ---
9.3 / 3.9
at A10 / W35
2
kW / ---
9.8 / 4.1
3.4
Cooling capacity / COP
at A27 / W7
kW / ---
7.8 / 2.7
at A27 / W18
kW / ---
9.6 / 3.2
at A35 / W7
kW / ---
7.0 / 2.0
at A35 / W18
kW / ---
8.5 / 2.4
3.5
Sound power level device / outdoors
dB(A)
- / -
3.6
Heating water flow with an internal pressure differential of m³/h / Pa
0.8 / 2700
3.7
Air flow rate with an external static pressure differential of m³/h / Pa
2500 / 0
m³/h / Pa
2500 / 25
3.8
Refrigerant; total filling weight
type / kg
R404A / 3.3
4
Dimensions, connections and weight
4.1
Device dimensions
H x W x L cm
190 x 75 x 65
4.2
Device connections to heating system
Inch
G 1'' internal/external
4.3
Air duct inlet and outlet (min. internal dimensions)
L x W cm
44 x 44
4.4
Weight of the transportable unit(s) incl. packing
kg
250
5
Electrical Connection
5.1
Nominal voltage; fuse protection
V / A
230 / 20
5.2
Nominal power consumption
2
A2 W35
kW
2.3
5.3
Starting current with soft starter
A
30
5.4
Nominal current A2 W35 / cos
ϕ
A / ---
12.5 / 0.8
6
Complies with the European safety regulations
3
3. See CE declaration of conformity
7
Additional model features
7.1
Defrosting
Automatic
Type of defrosting
Reverse cycle
Defrosting tray included
Yes (heated)
7.2
Heating water in device protected against freezing
Yes
4
4. The heat circulating pump is integrated.
7.3
Performance levels
1
7.4
Controller internal/external
Internal