background image

E-8

English

8

8 Maintenance / Cleaning

8.1

Maintenance

To protect the paintwork, avoid leaning or putting objects on the
device. External heat pump parts can be wiped with a damp cloth
and domestic cleaner.

ATTENTION!

Never use cleaning agents containing sand, soda, acid or chloride as
these can damage the surfaces.

To prevent faults due to sediment in the heat exchanger of the
heat pump, ensure that the heat exchanger in the heating system
can not be contaminated. We recommend protecting the evapo-
rator by installing a bird guard in the inlet duct. At least 80% of the
cross section of the grating should be open. In the event that op-
erating malfunctions due to contamination still occur, the system
should be cleaned as described below.

8.2

Cleaning the Heating System

The ingress of oxygen into the heating water circuit may result in
the formation of oxidation products (rust), particularly if steel
components are used. These products enter the heating system
via the valves, the circulating pumps and/or plastic pipes. It is
therefore essential - in particular with respect to the piping of un-
derfloor heating systems - that only diffusion-proof materials are
used.

ATTENTION!

We recommend the installation of a suitable corrosion protection system
to prevent the formation of deposits (e.g. rust) in the condenser of the
heat pump.

Residue from lubricants and sealants may also contaminate the
heating water.

In the case of severe contamination leading to a reduction in the
performance of the liquifier in the heat pump, the system must be
cleaned by a heating technician.

According to today's state of knowledge, we recommend using a
5 % phosphoric acid solution for cleaning purposes. However, if
cleaning needs to be performed more frequently, a 5 % formic
acid solution should be used.

In either case, the cleaning fluid should be at room temperature.
We recommend flushing the heat exchanger in the direction op-
posite to the normal flow direction.

To prevent acidic cleaning agents from entering the heating sys-
tem circuit, we recommend connecting the flushing device di-
rectly to the flow and return flow of the liquifier of the heat pump.

It is important that the system be thoroughly flushed using appro-
priate neutralising agents to prevent any damage from being
caused by cleaning agent residue remaining in the system.

Acids must be used with great care and all relevant regulations of
the employers' liability insurance associations must be adhered
to.

If in doubt, contact the manufacturer of the chemicals!

8.3

Cleaning the Air System

Air ducts, evaporator, ventilator and condensate outflow should
be cleaned of contamination (leaves, twigs, etc.) before the heat-
ing period. Do this by opening the front of the heat pump. The
bottom should be opened first followed by the top.

ATTENTION!

Before opening the device, ensure that all circuits are isolated from the
power supply.

Remove and rehang the side panel assemblies as described in
Chapter 4.

To prevent the evaporator and the condensate tray from being
damaged, do not use hard or sharp objects for cleaning.

9 Faults / Trouble-

Shooting

This heat pump is a quality product and is designed for trouble-
free and maintenance-free operation. In the event that a fault
should occur, it will be shown on the heat pump manager display.
Simply consult the Faults and Trouble-shooting page in the oper-
ating instructions of the heat pump manager. If you cannot cor-
rect the fault yourself, please contact your after-sales service
technician.

ATTENTION!

Any work on the heat pump may only be performed by authorised and
qualified after-sales service technicians. 

10 Decommissioning/

Disposal

Before removing the heat pump, disconnect it from the power
source and close all valves. Observe all environmentally-relevant
requirements regarding the recovery, recycling and disposal of
materials and components in accordance with all applicable
standards. Particular attention should be paid to the proper dis-
posal of refrigerants and refrigeration oils.

Summary of Contents for LI 11MER

Page 1: ...at Pump for Indoor Installation Pompe à chaleur air eau réversible pour installation intérieure Montage und Gebrauchsanweisung Deutsch English Français Instructions d installation et d utilisation Installation and Operating Instructions Bestell Nr Order no No de commande 452160 66 24 FD 8611 ...

Page 2: ...ansport E 4 5 Set UP E 5 5 1 General Information E 5 5 2 Condensed Water Pipe E 5 5 3 Sound E 5 6 Installation E 5 6 1 General Information E 5 6 2 Air Connection E 5 6 3 Heating System Connection E 6 6 4 Electrical Connection E 6 7 Start UP E 7 7 1 General Information E 7 7 2 Preparation E 7 7 3 Procedure E 7 8 Maintenance Cleaning E 8 8 1 Maintenance E 8 8 2 Cleaning the Heating System E 8 8 3 Cl...

Page 3: ...specially children who are not capable of operating the device safely due to their physical sensory or mental abilities or their inexperience or lack of knowledge must not operate this device without supervision or instruction by the person in charge Children must be supervised to ensure that they do not play with the device 1 3 Energy Efficient Use of the Heat Pump With the purchase of this heat ...

Page 4: ...er temperature level by increasing its pressure with the aid of an electrically driven compressor It is then transferred to the heating water using the liquifier heat ex changer Electrical energy is used to raise the temperature of the heat in the environment to a higher level Because the energy extracted from the air is transferred to the heating water this type of device is called an air to wate...

Page 5: ... accessories The enclosed operating instructions describe the function and use of the heat pump manager 4 Transport ATTENTION When transporting the heat pump ensure that it is not tilted more than 45 in any direction Use a wooden pallet for transporting the heat pump to the final in stallation location The basic device can be transported with a lift truck hand truck or by means of 3 4 pipes fed th...

Page 6: ...use the aggressive vapours could destroy the evaporator 5 3 Sound To prevent solid borne sound from being transmitted to the heat ing system we recommend connecting the heat pump to the heating system using a flexible hose Installed air ducts should be sound isolated from the heat pump to prevent the transmission of solid borne sound to the ducts 6 Installation 6 1 General Information The followin...

Page 7: ...ure for adjusting an overflow valve is described in the Chapter Start Up Antifreeze A method of manual drainage see illustration should be pro vided for heat pumps which are exposed to frost The antifreeze function of the heat pump controller is active whenever the con troller and the heat circulating pump are ready for operation If the heat pump is taken out of service or in the event of a power ...

Page 8: ...rn flow listed in the following table for the current heat source temperature The temperature spread should be measured as close as possible to the heat pump The heating element of mono energy systems should be disconnected Any faults occurring during operation are also displayed on the heat pump controller and can be corrected as described in the operating instructions of the heat pump controller...

Page 9: ...he direction op posite to the normal flow direction To prevent acidic cleaning agents from entering the heating sys tem circuit we recommend connecting the flushing device di rectly to the flow and return flow of the liquifier of the heat pump It is important that the system be thoroughly flushed using appro priate neutralising agents to prevent any damage from being caused by cleaning agent resid...

Page 10: ...at A35 W18 kW 9 5 2 5 9 5 2 5 3 6 Sound power level device outdoors dB A 55 61 3 7 Sound pressure level at a distance of 1 m indoors dB A 50 3 8 Heating water flow with an internal pressure differential of m h Pa 1 0 3000 1 9 10900 3 9 Cooling water flow with an internal pressure differential ofm h Pa 1 0 3000 1 3 5900 3 10 Air flow rate with an external static pressure differential of m h Pa 4200...

Page 11: ...hlregler Control of the cooling controller Commande régulateur standard A VI 3 3 Last Load Charge A VII 3 4 Anschlussplan Standardregler Terminal diagram for the standard controller Schéma électrique du régulateur standard A VIII 3 5 Anschlussplan Kühlregler Terminal diagram for the cooling controller Schéma électrique du régulateur refroidissement A IX 3 6 Legende Legend Légende A X 4 Hydraulisch...

Page 12: ... HDX GH FKDXIIDJH 6RUWLH GH OD 3 LOHWDJH H WpULHXU HL XQJVU FNODXI LQJDQJ LQ GLH 3 X HQJHZLQGH HDWLQJ ZDWHU UHWXUQ IORZ HDW SXPS LQOHW H WHUQDO WKUHDG 5HWRXU HDX GH FKDXIIDJH QWUpH GDQV OD 3 LOHWDJH H WpULHXU RQGHQVDWDEODXI QQHQ PP RQGHQVDWH RXWIORZ LQVLGH PP FRXOHPHQW GX FRQGHQVDW LQW PP RQGHQVDWDEODXIVFKODXFK RQGHQVDWH RXWIORZ KRVH 7X DX HDX GH FRQGHQVDWLRQ HL XQJVDQVFKOXVV HDWLQJ FRQQHFWLRQ 5DF...

Page 13: ...DWLRQ GH SXLVVDQFH FRPSULV SDUW GH FRQVRPPDWLRQ GH OD SRPSH UXFNYHUOXVW LQ 3D 3UHVVXUH ORVV LQ 3D 3HUWH GH SUHVVLRQ HQ 3D XIWHLQWULWWVWHPSHUDWXU LQ LU LQOHW WHPSHUDWXUH LQ 7HPSpUDWXUH G HQWUpH G DLU HQ XIWHLQWULWWVWHPSHUDWXU LQ LU LQOHW WHPSHUDWXUH LQ 7HPSpUDWXUH G HQWUpH G DLU HQ HLVWXQJV DKO LQFO 3XPSHQOHLVWXQJVDQWHLO RHIILFLHQW RI SHUIRUPDQFH LQFO SRZHU LQSXW WR SXPS RHIILFLHQW GH SHUIRUPDQFH F...

Page 14: ...SRZHU LQSXW WR SXPS RQVRPPDWLRQ GH SXLVVDQFH FRPSULV SDUW GH FRQVRPPDWLRQ GH OD SRPSH UXFNYHUOXVW LQ 3D 3UHVVXUH ORVV LQ 3D 3HUWH GH SUHVVLRQ HQ 3D XIWHLQWULWWVWHPSHUDWXU LQ LU LQOHW WHPSHUDWXUH LQ 7HPSpUDWXUH G HQWUpH G DLU HQ XIWHLQWULWWVWHPSHUDWXU LQ LU LQOHW WHPSHUDWXUH LQ 7HPSpUDWXUH G HQWUpH G DLU HQ HLVWXQJV DKO LQFO 3XPSHQOHLVWXQJVDQWHLO RHIILFLHQW RI SHUIRUPDQFH LQFO SRZHU LQSXW WR SXPS R...

Page 15: ...www dimplex de A V Anhang Appendix Annexes 3 1 3 Stromlaufpläne Circuit Diagrams Schémas électriques 3 1 Steuerung Standardregler Control of the standard controller Commande régulateur standard ...

Page 16: ...A VI Anhang Appendix Annexes 3 2 3 2 Steuerung Kühlregler Control of the cooling controller Commande régulateur standard ...

Page 17: ...www dimplex de A VII Anhang Appendix Annexes 3 3 3 3 Last Load Charge ...

Page 18: ...A VIII Anhang Appendix Annexes 3 4 3 4 Anschlussplan Standardregler Terminal diagram for the standard controller Schéma électrique du régulateur standard RGHU RU RX ...

Page 19: ...hang Appendix Annexes 3 5 3 5 Anschlussplan Kühlregler Terminal diagram for the cooling controller Schéma électrique du régulateur refroidissement 7HPSHU 7HPS 7HPS HXFKWH XPLGLW XPLGLWp 7HPSHU 7HPS 7HPS HXFKWH XPLGLW XPLGLWp ...

Page 20: ...e rafraîchissement M1 Verdichter Compressor Compresseur M2 Ventilator Ventilator Ventilateur M13 Heizungsumwälzpumpe Hauptkreis Heat circulating pump of the main circuit Circulateur de chauffage circuit principal M14 Heizungsumwälzpumpe 1 Heizkreis Heat circulating pump of heating circuit 1 Circulateur de chauffage 1er circuit de chauffage M15 Heizungsumwälzpumpe 2 Heizkreis Heat circulating pump ...

Page 21: ...www dimplex de A XI Anhang Appendix Annexes 4 1 4 Hydraulische Prinzipschemen Hydraulic Plumbing Diagrams Schémas hydrauliques 4 1 Darstellung Schematic View Représentation ...

Page 22: ...lateur de chauffage M14 Umwälzpumpe für Heiz und Kühlbetrieb elektronisch geregelt Circulating pump for heating and cooling operation electronically regulated Circulateur pour mode chauffage et re froidissem à régulation électronique M15 Heizungspumpe 2ter Heizkreis elektronisch geregelt Heating pump for heating circuit 2 electronically regulated Pompe chauffage circuit chauffage 2 à régulation él...

Page 23: ...www dimplex de A XIII Anhang Appendix Annexes 5 5 Konformitätserklärung Declaration of Conformity Déclaration de conformité ...

Page 24: ...tschland GmbH Geschäftsbereich Dimplex Am Goldenen Feld 18 D 95326 Kulmbach Irrtümer und Änderungen vorbehalten Subject to alterations and errors Sous réserve d erreurs et modifications 49 0 9221 709 565 www dimplex de ...

Reviews: