6.2

5 Set-UP

5.1

General Information

The unit must be installed indoors on a level, smooth and hori-
zontal surface. The entire base of the frame should lie directly on
the floor to ensure a good soundproof seal. If this is not the case,
additional sound insulation measures may be necessary. If the
device is installed on top of a built-under buffer tank, a surface
that fully supports the base is required. The heat pump must be
installed so that maintenance work can be carried out without
being hindered. This can be ensured by maintaining a clearance
of 1 m in front and to the left and right of the heat pump.

Never install the device in rooms subject to high humidity. Con-
densation can form on the heat pump and air circuit if the humid-
ity exceeds 50% and the external temperature is below O °C.

If the heat pump is installed on an upper storey, the load-bearing
capacity of the ceiling should be checked. On account of the
acoustics, measures for isolating possible vibrations should also
be very carefully planned in advance as well. Installation on a
wooden floor is not recommended.

5.2

Condensed Water Pipe

Condensed water that forms during operation must be drained
off frost-free. The heat pump must be mounted on a level plane
to guarantee proper drainage. The condensed water pipe must
have a minimum diameter of 50 mm and should be fed frost-free
into a sewer. Condensate should not be discharged directly into
clearing tanks and cesspits because the aggressive vapours
could destroy the evaporator. 

5.3

Sound

To prevent solid-borne sound from being transmitted to the heat-
ing system, we recommend connecting the heat pump to the
heating system using a flexible hose.

Installed air ducts should be sound-isolated from the heat pump
to prevent the transmission of solid-borne sound to the ducts.

6 Installation

6.1

General Information

The following connections need to be established on the heat
pump:

- Fresh and exhaust air

- Flow and return flow of the heating system

- Condensate outflow

- Power supply

6.2

Air Connection

ATTENTION!

Do not restrict or block the area around the air intake or outlet.

ATTENTION!

Only operate the heat pump with the air ducts connected.

The glass fibre reinforced concrete air ducts offered as accesso-
ries are moisture-resistant and diffusion-free.

The sealing collar is used to seal the air ducts on the heat pump.
The air ducts are not screwed directly onto the heat pump. Only
the rubber seal comes into direct contact with the heat pump
when the system is installed correctly. This guarantees easy as-
sembly and disassembly of the heat pump and also ensures that
solid-borne sound is well insulated. 

If another type of air duct is used, observe the external and inter-
nal dimensions as specified in the figure. Also ensure that the vi-
bration and duct insulation are adequate.

If flange-mounted air ducts are used, connecting stubs are se-
cured on the air inlet and air outlet sides of the evaporator with 4
M8 x 16 hexagon bolts in the threaded holes provided. When
doing this, ensure that both air duct stubs only touch the insula-
tion. There should be no contact with the external sheeting.

P

 P

 P

P

Summary of Contents for LI 11MER

Page 1: ...at Pump for Indoor Installation Pompe à chaleur air eau réversible pour installation intérieure Montage und Gebrauchsanweisung Deutsch English Français Instructions d installation et d utilisation Installation and Operating Instructions Bestell Nr Order no No de commande 452160 66 24 FD 8611 ...

Page 2: ...ansport E 4 5 Set UP E 5 5 1 General Information E 5 5 2 Condensed Water Pipe E 5 5 3 Sound E 5 6 Installation E 5 6 1 General Information E 5 6 2 Air Connection E 5 6 3 Heating System Connection E 6 6 4 Electrical Connection E 6 7 Start UP E 7 7 1 General Information E 7 7 2 Preparation E 7 7 3 Procedure E 7 8 Maintenance Cleaning E 8 8 1 Maintenance E 8 8 2 Cleaning the Heating System E 8 8 3 Cl...

Page 3: ...specially children who are not capable of operating the device safely due to their physical sensory or mental abilities or their inexperience or lack of knowledge must not operate this device without supervision or instruction by the person in charge Children must be supervised to ensure that they do not play with the device 1 3 Energy Efficient Use of the Heat Pump With the purchase of this heat ...

Page 4: ...er temperature level by increasing its pressure with the aid of an electrically driven compressor It is then transferred to the heating water using the liquifier heat ex changer Electrical energy is used to raise the temperature of the heat in the environment to a higher level Because the energy extracted from the air is transferred to the heating water this type of device is called an air to wate...

Page 5: ... accessories The enclosed operating instructions describe the function and use of the heat pump manager 4 Transport ATTENTION When transporting the heat pump ensure that it is not tilted more than 45 in any direction Use a wooden pallet for transporting the heat pump to the final in stallation location The basic device can be transported with a lift truck hand truck or by means of 3 4 pipes fed th...

Page 6: ...use the aggressive vapours could destroy the evaporator 5 3 Sound To prevent solid borne sound from being transmitted to the heat ing system we recommend connecting the heat pump to the heating system using a flexible hose Installed air ducts should be sound isolated from the heat pump to prevent the transmission of solid borne sound to the ducts 6 Installation 6 1 General Information The followin...

Page 7: ...ure for adjusting an overflow valve is described in the Chapter Start Up Antifreeze A method of manual drainage see illustration should be pro vided for heat pumps which are exposed to frost The antifreeze function of the heat pump controller is active whenever the con troller and the heat circulating pump are ready for operation If the heat pump is taken out of service or in the event of a power ...

Page 8: ...rn flow listed in the following table for the current heat source temperature The temperature spread should be measured as close as possible to the heat pump The heating element of mono energy systems should be disconnected Any faults occurring during operation are also displayed on the heat pump controller and can be corrected as described in the operating instructions of the heat pump controller...

Page 9: ...he direction op posite to the normal flow direction To prevent acidic cleaning agents from entering the heating sys tem circuit we recommend connecting the flushing device di rectly to the flow and return flow of the liquifier of the heat pump It is important that the system be thoroughly flushed using appro priate neutralising agents to prevent any damage from being caused by cleaning agent resid...

Page 10: ...at A35 W18 kW 9 5 2 5 9 5 2 5 3 6 Sound power level device outdoors dB A 55 61 3 7 Sound pressure level at a distance of 1 m indoors dB A 50 3 8 Heating water flow with an internal pressure differential of m h Pa 1 0 3000 1 9 10900 3 9 Cooling water flow with an internal pressure differential ofm h Pa 1 0 3000 1 3 5900 3 10 Air flow rate with an external static pressure differential of m h Pa 4200...

Page 11: ...hlregler Control of the cooling controller Commande régulateur standard A VI 3 3 Last Load Charge A VII 3 4 Anschlussplan Standardregler Terminal diagram for the standard controller Schéma électrique du régulateur standard A VIII 3 5 Anschlussplan Kühlregler Terminal diagram for the cooling controller Schéma électrique du régulateur refroidissement A IX 3 6 Legende Legend Légende A X 4 Hydraulisch...

Page 12: ... HDX GH FKDXIIDJH 6RUWLH GH OD 3 LOHWDJH H WpULHXU HL XQJVU FNODXI LQJDQJ LQ GLH 3 X HQJHZLQGH HDWLQJ ZDWHU UHWXUQ IORZ HDW SXPS LQOHW H WHUQDO WKUHDG 5HWRXU HDX GH FKDXIIDJH QWUpH GDQV OD 3 LOHWDJH H WpULHXU RQGHQVDWDEODXI QQHQ PP RQGHQVDWH RXWIORZ LQVLGH PP FRXOHPHQW GX FRQGHQVDW LQW PP RQGHQVDWDEODXIVFKODXFK RQGHQVDWH RXWIORZ KRVH 7X DX HDX GH FRQGHQVDWLRQ HL XQJVDQVFKOXVV HDWLQJ FRQQHFWLRQ 5DF...

Page 13: ...DWLRQ GH SXLVVDQFH FRPSULV SDUW GH FRQVRPPDWLRQ GH OD SRPSH UXFNYHUOXVW LQ 3D 3UHVVXUH ORVV LQ 3D 3HUWH GH SUHVVLRQ HQ 3D XIWHLQWULWWVWHPSHUDWXU LQ LU LQOHW WHPSHUDWXUH LQ 7HPSpUDWXUH G HQWUpH G DLU HQ XIWHLQWULWWVWHPSHUDWXU LQ LU LQOHW WHPSHUDWXUH LQ 7HPSpUDWXUH G HQWUpH G DLU HQ HLVWXQJV DKO LQFO 3XPSHQOHLVWXQJVDQWHLO RHIILFLHQW RI SHUIRUPDQFH LQFO SRZHU LQSXW WR SXPS RHIILFLHQW GH SHUIRUPDQFH F...

Page 14: ...SRZHU LQSXW WR SXPS RQVRPPDWLRQ GH SXLVVDQFH FRPSULV SDUW GH FRQVRPPDWLRQ GH OD SRPSH UXFNYHUOXVW LQ 3D 3UHVVXUH ORVV LQ 3D 3HUWH GH SUHVVLRQ HQ 3D XIWHLQWULWWVWHPSHUDWXU LQ LU LQOHW WHPSHUDWXUH LQ 7HPSpUDWXUH G HQWUpH G DLU HQ XIWHLQWULWWVWHPSHUDWXU LQ LU LQOHW WHPSHUDWXUH LQ 7HPSpUDWXUH G HQWUpH G DLU HQ HLVWXQJV DKO LQFO 3XPSHQOHLVWXQJVDQWHLO RHIILFLHQW RI SHUIRUPDQFH LQFO SRZHU LQSXW WR SXPS R...

Page 15: ...www dimplex de A V Anhang Appendix Annexes 3 1 3 Stromlaufpläne Circuit Diagrams Schémas électriques 3 1 Steuerung Standardregler Control of the standard controller Commande régulateur standard ...

Page 16: ...A VI Anhang Appendix Annexes 3 2 3 2 Steuerung Kühlregler Control of the cooling controller Commande régulateur standard ...

Page 17: ...www dimplex de A VII Anhang Appendix Annexes 3 3 3 3 Last Load Charge ...

Page 18: ...A VIII Anhang Appendix Annexes 3 4 3 4 Anschlussplan Standardregler Terminal diagram for the standard controller Schéma électrique du régulateur standard RGHU RU RX ...

Page 19: ...hang Appendix Annexes 3 5 3 5 Anschlussplan Kühlregler Terminal diagram for the cooling controller Schéma électrique du régulateur refroidissement 7HPSHU 7HPS 7HPS HXFKWH XPLGLW XPLGLWp 7HPSHU 7HPS 7HPS HXFKWH XPLGLW XPLGLWp ...

Page 20: ...e rafraîchissement M1 Verdichter Compressor Compresseur M2 Ventilator Ventilator Ventilateur M13 Heizungsumwälzpumpe Hauptkreis Heat circulating pump of the main circuit Circulateur de chauffage circuit principal M14 Heizungsumwälzpumpe 1 Heizkreis Heat circulating pump of heating circuit 1 Circulateur de chauffage 1er circuit de chauffage M15 Heizungsumwälzpumpe 2 Heizkreis Heat circulating pump ...

Page 21: ...www dimplex de A XI Anhang Appendix Annexes 4 1 4 Hydraulische Prinzipschemen Hydraulic Plumbing Diagrams Schémas hydrauliques 4 1 Darstellung Schematic View Représentation ...

Page 22: ...lateur de chauffage M14 Umwälzpumpe für Heiz und Kühlbetrieb elektronisch geregelt Circulating pump for heating and cooling operation electronically regulated Circulateur pour mode chauffage et re froidissem à régulation électronique M15 Heizungspumpe 2ter Heizkreis elektronisch geregelt Heating pump for heating circuit 2 electronically regulated Pompe chauffage circuit chauffage 2 à régulation él...

Page 23: ...www dimplex de A XIII Anhang Appendix Annexes 5 5 Konformitätserklärung Declaration of Conformity Déclaration de conformité ...

Page 24: ...tschland GmbH Geschäftsbereich Dimplex Am Goldenen Feld 18 D 95326 Kulmbach Irrtümer und Änderungen vorbehalten Subject to alterations and errors Sous réserve d erreurs et modifications 49 0 9221 709 565 www dimplex de ...

Reviews: