EN-6

English

6.3

NOTE

The use of an overflow valve is only recommended for panel heating and
a max. heating water flow of 1.3 m³/h. System faults may result if this is
not observed.

Antifreeze (frost protection)

A method of manual drainage (see illustration) should be pro-
vided for heat pumps which are exposed to frost. The antifreeze
function of the heat pump manager is active whenever the heat
pump manager and the heat circulating pump are ready for oper-
ation. If the heat pump is taken out of service or in the event of a
power failure, the system has to be drained. The heating circuit
should be operated with a suitable antifreeze if heat pump sys-
tems are implemented in buildings where a power failure can not
be detected (holiday home).

6.3 Electrical Connection

A standard three-core cable is used for connecting the heat
pump to the power supply.
The cable must be provided by the customer. The conductor
cross section is selected in accordance with the power consump-
tion of the heat pump (see Appendix Device Information) and the
applicable VDE (EN) and VNB regulations.
A disconnecting device with a contact gap of at least 3 mm (e.g.
utility blocking contactor or power contactor) as well as a 1-pole
circuit breaker must be installed in the power supply of the heat
pump by the customer (tripping current in compliance with the
Device Information). 
The control voltage is supplied via the heat pump manager.
The heat pump manager has a 230 V AC-50 Hz power supply.
Connect the controller in compliance with its own operating in-
structions (16 A fuse).
The control line (not included in scope of supply) is connected to
the heat pump manager using a multipole plug connector. Use
the plug connector located on the base of the heat pump adja-
cent to the cable gland in the base plate. More detailed informa-
tion can be found in the operating instructions of the heat pump
manager.
See Appendix Circuit Diagrams for detailed information.

7 Start-up

7.1 General Information

To ensure that start-up is performed correctly, it should only be
carried out by an after-sales service technician authorized by the
manufacturer. Only then can an extended warranty period of
3 years in total be granted (see Warranty Service). Start-up
should be carried out in heating operation.

7.2 Preparation

The following items need to be checked prior to start-up:

„

All of the heat pump connections must be established as de-
scribed in Chapter 6.

„

All valves that could impair the proper flow of the heating
water in the heating circuit must be open.

„

The air intake and air outlet paths must not be blocked in any
way.

„

The ventilator must turn in the direction indicated by the ar-
row.

„

The settings of the heat pump manager must be adapted to
the heating system in accordance with the controller’s oper-
ating instructions.

„

The condensate outflow must not be impaired.

7.3 Procedure

The heat pump is started up via the heat pump manager. Adjust-
ments should be made in compliance with the instructions. 
If  an  overflow  valve  is  fitted  to  maintain  the  minimum  heat-
ing water flow rate, the valve must be adapted to the require-
ments of the heating system. Incorrect adjustment can lead to
faulty operation and increased energy consumption. We recom-
mend carrying out the following procedure to correctly adjust the
overflow valve:
Close all of the heating circuits that may also be closed during
operation (depending on the type of heat pump usage) so that
the most unfavorable operating state - with respect to the water
flow rate - is achieved. This normally means the heating circuits
of the rooms on the south and west sides of the building. At least
one heating circuit must remain open (e.g. bathroom).
The overflow valve should be opened far enough to produce the
maximum temperature spread between the heating flow and re-
turn flow listed in the following table for the current heat source
temperature. The temperature spread should be  measured  as
close as possible to the heat pump. The heating element of mono
energy systems should be disconnected during start up.

Summary of Contents for LA 11MSR

Page 1: ...t Pump for Outdoor Installation Pompe chaleur air eau r versible pour installation ext rieure Montage und Gebrauchsanweisung Deutsch English Fran ais Instructions d installation et d utilisation Insta...

Page 2: ......

Page 3: ...2 Schaltkasten DE 4 3 3 W rmepumpenmanager DE 4 4 Transport DE 5 5 Aufstellung DE 5 5 1 Allgemein DE 5 5 2 Kondensatleitung DE 5 6 Montage DE 6 6 1 Allgemein DE 6 6 2 Heizungsseitiger Anschluss DE 6...

Page 4: ...nden EG Richtlinien DIN und VDE Vorschriften eingehalten siehe CE Konformit tserkl rung Beim elektrischen Anschluss der W rmepumpe sind die entspre chenden VDE EN und IEC Normen einzuhalten Au erdem m...

Page 5: ...C geeignet Sie kann f r stille und dynamische K hlung verwendet werden Minimale Wassertemperatur ist 7 C ACHTUNG Das Ger t ist nicht f r Frequenzumrichterbetrieb geeignet 2 2 Arbeitsweise Heizen Umge...

Page 6: ...sich in der W rmepumpe Nach Ab nahme der unteren Frontabdeckung und dem L sen der sich rechts oben befindenden Befestigungsschraube kann der Schaltkasten herausgeklappt werden Im Schaltkasten befinde...

Page 7: ...e m glichen Transportbohrun gen eingeschnappt werden 5 Aufstellung 5 1 Allgemein Das Ger t ist grunds tzlich auf einer dauerhaft ebenen glatten und waagerechten Fl che aufzustellen Dabei sollte der Ra...

Page 8: ...rreicht werden Die Einstellung eines berstr mventiles ist in Kapitel Inbetrieb nahme erkl rt Eine drastische Unterschreitung des Mindest durchflusses kann zum Totalschaden der W rmepumpe durch ein Auf...

Page 9: ...me auf der S d und West seite Mindestens ein Heizkreis muss ge ffnet bleiben z B Bad Das berstr mventil ist so weit zu ffnen dass sich bei der aktu ellen W rmequellentemperatur die in der nachstehende...

Page 10: ...hosphors ure oder falls h ufiger gereinigt werden muss mit einer 5 igen Ameisens ure durchzuf hren In beiden F llen sollte die Reinigungsfl ssigkeit Raumtempera tur haben Es ist empfehlenswert den W r...

Page 11: ...en werden kann verst ndigen Sie bitte den zust ndigen Kundendienst ACHTUNG Arbeiten an der W rmepumpe d rfen nur vom autorisierten und sachkundigen Kundendienst durchgef hrt werden 10 Au erbetriebnahm...

Page 12: ...8 bei A27 W18 kW 10 9 3 3 10 8 3 2 bei A35 W7 kW 7 6 2 1 7 5 2 1 bei A35 W18 kW 9 5 2 5 9 5 2 5 3 6 Schall Leistungspegel dB A 63 3 7 Schall Druckpegel in 10m Entfernung Ausblasseite dB A 33 3 8 Heizw...

Page 13: ...bezogene Teile und Ger te Anlagenm ngel die auf nicht vom Lieferer bezogene Teile zur ckzuf hren sind fallen nicht unter den Garantieanspruch Sofern der Mangel nicht beseitigt werden kann oder die Na...

Page 14: ...DE 12 Deutsch 12...

Page 15: ...4 3 3 Heat pump manager EN 4 4 Transport EN 4 5 Installation EN 5 5 1 General Information EN 5 5 2 Condensed Water Pipe EN 5 6 Mounting EN 5 6 1 General Information EN 5 6 2 Heating System Connection...

Page 16: ...connecting the heat pump to the power supply the rele vant VDE EN and IEC standards are to be fulfilled Any further connection requirements stipulated by local utility companies must also be observed...

Page 17: ...sure with the aid of an electrically driven compressor It is then transferred to the heating water using the liquifier heat ex changer Electrical energy is used to raise the temperature of the heat in...

Page 18: ...er together with the necessary fixing accessories The enclosed operating instructions describe the function and use of the heat pump manager 4 Transport ATTENTION When transporting the heat pump care...

Page 19: ...ushed to remove any impurities residue from sealants etc Any accumulation of deposits in the liquifier could cause the heat pump to completely break down For systems in which the heating water flow ca...

Page 20: ...etailed information 7 Start up 7 1 General Information To ensure that start up is performed correctly it should only be carried out by an after sales service technician authorized by the manufacturer...

Page 21: ...n the formation of oxidation products rust particularly if steel components are used These products enter the heating system via the valves the circulating pumps and or plastic pipes It is therefore e...

Page 22: ...grids to ensure that the minimum air flow rate is maintained 9 Faults and Troubleshooting This heat pump is a quality product and is designed for trouble free operation In the event that a fault shou...

Page 23: ...8 8 2 8 at A27 W18 kW 10 9 3 3 10 8 3 2 at A35 W7 kW 7 6 2 1 7 5 2 1 at A35 W18 kW 9 5 2 5 9 5 2 5 3 6 Sound power level dB A 63 3 7 Sound pressure level at a distance of 10m discharge end dB A 33 3 8...

Page 24: ...EN 10 English 11...

Page 25: ...ompe chaleur FR 4 4 Transport FR 5 5 Choix de l emplacement FR 5 5 1 Remarques d ordre g n ral FR 5 5 2 Ecoulement des condensats FR 5 6 Installation FR 6 6 1 Remarques d ordre g n ral FR 6 6 2 Branch...

Page 26: ...claration de conformit CE Les normes VDE EN et CEI correspondantes sont respecter au branchement lectrique de la pompe chaleur D autre part les prescriptions de branchement des exploitants de r seaux...

Page 27: ...r des temp ratures de l air allant de 15 C 40 C Elle peut tre utilis e pour un refroidissement silencieux et dyna mique La temp rature d eau est de 7 C minimum ATTENTION L appareil ne convient pas au...

Page 28: ...bo tier lectrique peut tre rabattu apr s avoir retir l habillage fron tal inf rieur et d viss la vis de fixation se trouvant en haut droite Dans le bo tier lectrique se trouvent les bornes de branchem...

Page 29: ...5 Choix de l emplacement 5 1 Remarques d ordre g n ral Il est fondamental que l appareil soit install sur une surface du rablement plane lisse et horizontale Ici le ch ssis devrait adh rer au sol sur...

Page 30: ...mum Quel que soit l tat de fonctionnement de l installation de chauf fage un d bit d eau de chauffage minimum doit tre garanti dans la pompe chaleur Cela peut par ex tre obtenu par l installa tion d u...

Page 31: ...gag es le sens de rotation du ventilateur doit correspondre la di rection de la fl che les r glages du gestionnaire de pompe chaleur doivent tre accord s l installation de chauffage conform ment ses...

Page 32: ...8 2 Nettoyage c t chauffage L oxyg ne est susceptible d entra ner la formation de produits d oxydation rouille dans l eau de chauffage en particulier si des composants m talliques sont mis en uvre Ce...

Page 33: ...air 9 D faillances recherche de pannes Cette pompe chaleur est un produit de qualit et elle devrait fonctionner sans dysfonctionnements Si un dysfonctionnement devait quand m me survenir celui ci sera...

Page 34: ...W18 kW 10 9 3 3 10 8 3 2 pour A35 W7 kW 7 6 2 1 7 5 2 1 pour A35 W18 kW 9 5 2 5 9 5 2 5 3 6 Niveau de puissance sonore dB A 63 3 7 Niveau de pression sonore une distance de 10 m c t vacuation dB A 33...

Page 35: ...aulisches Prinzipschema Hydraulic block diagram Sch ma hydraulique A IX 4 1 Monoenergetische Anlage mit stiller K hlung und Warmwasserbereitung Mono energy system with silent cooling and domestic hot...

Page 36: ...HFWULF OLQHV DVH RI KHDW SXPS UHD RI RSHQLQJV IRU KHDWLQJ FLUFXLW FRQGHQVDWH GUDLQ HOHFWULFDO FDEOH LJQHV pOHFWULTXHV 6RFOH 3 3DVVDJHV FLUFXLW GH FKDXIIDJH pFRXOHPHQW GX FRQGHQVDW FkEOH pOHFWULTXH OHN...

Page 37: ...PDWLRQ GH SXLVVDQFH HQ N FRPSULV SDUW GH FRQVRPPDWLRQ GH OD SRPSH UXFNYHUOXVW LQ 3D 3UHVVXUH ORVV LQ 3D 3HUWH GH SUHVVLRQ HQ 3D XIWHLQWULWWVWHPSHUDWXU LQ LU LQOHW WHPSHUDWXUH LQ 7HPSpUDWXUH G HQWUpH G...

Page 38: ...PSHUDWXU LQ LU LQOHW WHPSHUDWXUH LQ 7HPSpUDWXUH G HQWUpH G DLU HQ XIWHLQWULWWVWHPSHUDWXU LQ LU LQOHW WHPSHUDWXUH LQ 7HPSpUDWXUH G HQWUpH G DLU HQ HLVWXQJV DKO LQFO 3XPSHQOHLVWXQJVDQWHLO RHIILFLHQW RI...

Page 39: ...Circuit diagrams Sch mas lectriques 3 1 Steuerung Control Commande OOH 4XHUVFKQLWWH PP OO FURVV VHFWLRQV PP 7RXWHV OHV VHFWLRQV PP 6WHXHUOHLWXQJ PP RQWURO OHDG PP LJQH GH FRPPDQGH PP SRO SROH S OHV lU...

Page 40: ...A VI Anhang Appendix Annexes 3 2 3 2 Last Load Charge 1HW 0DLQV 5pVHDX...

Page 41: ...RQWURO OHDG LJQH GH FRPPDQGH 6WHXHUOHLWXQJ RQWURO OHDG LJQH GH FRPPDQGH GHU XQG 3LQQXPPHUQ LUH DQG SLQ QXPEHUV 1XPpURV GH EULQV HW GH EURFKHV GHU XQG 3LQQXPPHUQ LUH DQG SLQ QXPEHUV 1XPpURV GH EULQV H...

Page 42: ...mepumpenmanager heat pump manager gestionnaire de pompe chaleur N7 Sanftanlaufsteuerung Soft start control Commande de d marrage progressif R2 R cklauff hler Heizwasser Return flow sensor heating wate...

Page 43: ...onoenergetische Anlage mit stiller K hlung und Warmwasserbereitung Mono energy system with silent cooling and domestic hot water preparation Installation mono nerg tique avec rafa chissement silencieu...

Page 44: ...er K hlung und Warmwasserbereitung Mono energy system with dynamic cooling and domestic hot water preparation Installation mono nerg tique avec rafa chissemant dynamique et production d eau chaude san...

Page 45: ...rvoir d eau chaude sanitaire E9 Flanschheizung Warmwasser Flange heater hot water Cartouche chauffante ECS E10 1 Tauchheizk rper Immersion heater R sistance immerg e M13 Heizungsumw lzpumpe Hauptkreis...

Page 46: ...ype s EG Richtlinien Niederspannungsrichtlinie 2006 96 EG EMV Richtlinie 2004 108 EG Druckger terichtlinie 97 23 EG EC Directives Low voltage directive 2006 95 EC EMC directive 2004 108 EC Pressure eq...

Page 47: ...www dimplex de A XIII Anhang Appendix Annexes 5...

Page 48: ...schland GmbH Gesch ftsbereich Dimplex Am Goldenen Feld 18 D 95326 Kulmbach Irrt mer und nderungen vorbehalten Subject to alterations and errors Sous r serve d erreurs et modifications 49 0 9221 709 56...

Reviews: