background image

EN-2

English

1

1 Please Read 

Immediately

1.1 Important Information:

ATTENTION!

The device is not suitable for operation with a frequency converter.

ATTENTION!

When transporting the heat pump, ensure that it is not tilted more than
45° (in any direction).

ATTENTION!

Do not restrict or block the area around the air intake or outlet.

ATTENTION!

Ensure that there is a clockwise rotating field: Operating the compressor
in the wrong rotational direction could cause damage to the compressor.

ATTENTION!

Never use cleaning agents containing sand, soda, acid or chloride as
these can damage the surfaces.

ATTENTION!

We recommend the installation of a suitable corrosion protection system
to prevent the formation of deposits (e.g. rust) in the condenser of the
heat pump.

ATTENTION!

Before opening the device, ensure that all circuits are isolated from the
power supply.

ATTENTION!

Any work on the heat pump may only be performed by authorised and
qualified after-sales service technicians.

1.2 Intended Use

This device is only intended for use as specified by the manufac-
turer. Any other use beyond that intended by the manufacturer is
prohibited. This requires the user to abide by the manufacturers
product information. Please refrain from tampering with or alter-
ing the device.

1.3 Legal Regulations and 

Directives

This heat pump is designed for use in a domestic environment
according to Article 1, Paragraph 2 k) of EC directive 2006/42/EC
(machinery directive) and is thus subject to the requirements of
EC directive 2006/95/EC (low-voltage directive). It is thus also in-
tended for use by non-professionals for heating shops, offices
and other similar working environments, in agricultural establish-
ments and in hotels, guest houses and similar / other residential
buildings.
The construction and design of the heat pump complies with all
relevant EU directives, DIN/VDE regulations (see CE declaration
of conformity).
When connecting the heat pump to the power supply, the rele-
vant VDE, EN and IEC standards are to be fulfilled. Any further
connection requirements stipulated by local utility companies
must also be observed.
When connecting the heating system, all applicable regulations
must also be adhered to.
Persons, especially children, who are not capable of operating
the device safely due to their physical, sensory or mental abilities
or due to their inexperience or lack of knowledge, must not ope-
rate this device without supervision or instruction by the person in
charge.
Children must be supervised to ensure that they do not play with
the device.

1.4 Energy-Efficient Use of the 

Heat Pump

With the purchase of this heat pump you are helping to protect
the environment. A prerequisite for energy-efficient operation is
the correct design of the heat source system and heating system
(radiators and circulation pump).
It is particularly important for the efficiency of a heat pump to
keep the temperature difference between heating water and heat
source as small as possible. For this reason, it is advisable to de-
sign the heat source and heating system very carefully. 

A tem-

perature difference of approx. one Kelvin increases the
power consumption by around 2.5 %.

 When designing the

heating system, it should be borne in mind that special consum-
ers such as e.g. hot water preparation should also be considered
and dimensioned for low temperatures. 

Underfloor heating

systems (panel heating)

 are optimally suited for heat pump use

on account of the low flow temperatures (30 °C to 40 °C). 
It is important to ensure that the heat exchangers are not con-
taminated during operation because this increases the tempera-
ture difference, in turn reducing the COP.
Correct adjustment of the heat pump manager is also important
for energy-efficient use of the heat pump. Further information can
be found in the heat pump manager operating instructions.

Summary of Contents for LA 11AS

Page 1: ...Pump for Outdoor Installation Pompe chaleur air eau pour installation ext rieure Montage und Gebrauchsanweisung Deutsch English Fran ais Instructions d installation et d utilisation Installation and O...

Page 2: ......

Page 3: ...2 Schaltkasten DE 4 3 3 W rmepumpenmanager DE 4 4 Transport DE 4 5 Aufstellung DE 5 5 1 Allgemein DE 5 5 2 Kondensatleitung DE 5 6 Montage DE 5 6 1 Allgemein DE 5 6 2 Heizungsseitiger Anschluss DE 5...

Page 4: ...VDE Vorschriften eingehalten siehe CE Konformit tserkl rung Beim elektrischen Anschluss der W rmepumpe sind die entspre chenden VDE EN und IEC Normen einzuhalten Au erdem m ssen die Anschlussbedingun...

Page 5: ...Hilfe eines elektrisch angetriebenen Verdichters wird die auf genommene W rme durch Druckerh hung auf ein h heres Tem peraturniveau gepumpt und ber den Verfl ssiger W rmeaus tauscher an das Heizwasser...

Page 6: ...bei Funktionsweise und Handhabung des W rmepumpenmanagers sind in der dazu beiliegenden Gebrauchsanweisung beschrie ben 4 Transport ACHTUNG Die W rmepumpe darf beim Transport nur bis zu einer Neigung...

Page 7: ...Au engewinde versehen Die anzuschlie enden Schl uche werden nach unten aus dem Ger t gef hrt Beim Anschluss an die W rmepumpe muss an den berg ngen mit einem Schl s sel gegengehalten werden Bevor die...

Page 8: ...trischer Anschluss Der Leistungsanschluss der W rmepumpe erfolgt ber ein han dels bliches 4 adriges Kabel Das Kabel ist bauseits beizustellen und der Leitungsquerschnitt gem der Leistungsaufnahme der...

Page 9: ...West seite Mindestens ein Heizkreis muss ge ffnet bleiben z B Bad Das berstr mventil ist so weit zu ffnen dass sich bei der aktu ellen W rmequellentemperatur die in der nachstehenden Ta belle angegeb...

Page 10: ...hosphors ure oder falls h ufiger gereinigt werden muss mit einer 5 igen Ameisens ure durchzuf hren In beiden F llen sollte die Reinigungsfl ssigkeit Raumtempera tur haben Es ist empfehlenswert den W r...

Page 11: ...en werden kann verst ndigen Sie bitte den zust ndigen Kundendienst ACHTUNG Arbeiten an der W rmepumpe d rfen nur vom autorisierten und sachkundigen Kundendienst durchgef hrt werden 10 Au erbetriebnahm...

Page 12: ...10 m Entfernung Ausblasseite 3 dB A 3 Der angegebene Schalldruckpegel entspricht dem Betriebsger usch der W rmepumpe im Heizbetrieb bei 35 C Vorlauftemperatur 33 34 3 6 Heizwasserdurchfluss bei inter...

Page 13: ...bezo gene Teile und Ger te Anlagenm ngel die auf nicht vom Liefe rer bezogene Teile zur ckzuf hren sind fallen nicht unter den Garantieanspruch Sofern der Mangel nicht beseitigt werden kann oder die N...

Page 14: ...DE 12 Deutsch 12...

Page 15: ...x EN 4 3 3 Heat Pump Manager EN 4 4 Transport EN 4 5 Set UP EN 5 5 1 General Information EN 5 5 2 Condensed Water Pipe EN 5 6 Installation EN 5 6 1 General Information EN 5 6 2 Heating System Connecti...

Page 16: ...ith all relevant EU directives DIN VDE regulations see CE declaration of conformity When connecting the heat pump to the power supply the rele vant VDE EN and IEC standards are to be fulfilled Any fur...

Page 17: ...n the evaporator The heat is pumped to a higher temperature level by increasing its pressure with the aid of an electrically driven compressor It is then transferred to the heating water using the liq...

Page 18: ...tructions together with the neces sary fixing accessories The enclosed operating instructions describe the function and use of the heat pump manager 4 Transport ATTENTION When transporting the heat pu...

Page 19: ...in the liquifier could cause the heat pump to completely break down For systems in which the heating water flow can be shut off via the radiator or thermostat valves an overflow valve must be in stal...

Page 20: ...grams in the Appendix 7 Start UP 7 1 General Information To ensure that start up is performed correctly it should only be carried out by an after sales service technician authorised by the manufacture...

Page 21: ...usion proof materials are used ATTENTION We recommend the installation of a suitable corrosion protection system to prevent the formation of deposits e g rust in the condenser of the heat pump Residue...

Page 22: ...fault yourself please contact your after sales service technician ATTENTION Any work on the heat pump may only be performed by authorised and qualified after sales service technicians 10 Decommissioni...

Page 23: ...essure level at a distance of 10 m air outlet side 3 dB A 3 The specified sound pressure level corresponds to the operating noise of the heat pump in heating operation with a flow temperature of 35 C...

Page 24: ...EN 10 English 11...

Page 25: ...e pompe chaleur FR 4 4 Transport FR 4 5 Emplacement de montage FR 5 5 1 Remarques d ordre g n ral FR 5 5 2 Ecoulement des condensats FR 5 6 Installation FR 5 6 1 Remarques d ordre g n ral FR 5 6 2 Bra...

Page 26: ...rmit CE Les normes VDE EN et CEI correspondantes sont respecter lors du branchement lectrique de la pompe chaleur D autre part les prescriptions de branchement des exploitants de r seaux d alimentatio...

Page 27: ...aide d un compresseur commande lectrique la chaleur ab sorb e est pomp e un niveau de temp rature plus lev par augmentation de pression puis d livr e via le condenseur changeur de chaleur l eau de cha...

Page 28: ...structions Mode de fonctionnement et utilisation du gestionnaire de pom pes chaleur sont d crits dans les instructions d utilisation li vr es avec l appareil 4 Transport ATTENTION Lors du transport l...

Page 29: ...vus de filetages ext rieurs 1 Les flexibles raccorder sont sortis de l appareil par le bas Pour raccorder la pompe chaleur il faudra contre bloquer au niveau des travers es l aide d une cl Avant de pr...

Page 30: ...e raccordement en puissance de la pompe chaleur s effectue via un c ble 4 fils normal vendu dans le commerce Le c ble doit tre mis disposition par le client et la section du conducteur doit tre choisi...

Page 31: ...c t sud et ouest Au moins un des circuits de chauffage doit res ter ouvert par ex salle de bains La vanne de trop plein est ouvrir au maximum de telle sorte que pour la temp rature actuelle des source...

Page 32: ...Dans l tat actuel des connaissances nous conseillons de pro c der au nettoyage avec de l acide phosphorique 5 ou si le nettoyage est plus fr quent avec de l acide formique 5 Dans les deux cas le liqu...

Page 33: ...onnement veuillez vous adresser au service apr s vente comp tent ATTENTION Les travaux sur la pompe chaleur doivent tre effectu s uniquement par des techniciens qualifi s et agr s 10 Mise hors service...

Page 34: ...c d air 3 dB A 3 Le niveau de pression sonore indiqu correspond au bruit de fonctionnement de la pompe chaleur en mode chauffage une temp rature aller de 35 C 33 34 3 6 D bit d eau de chauffage avec p...

Page 35: ...n Circuit Diagram Sch ma lectrique LA 16AS A XII 3 8 Legende Legend L gende LA 16AS A XIII 4 Hydraulische Prinzipschemen Hydraulic Plumbing Diagrams Sch mas hydrauliques A XIV 4 1 Monoenergetische Anl...

Page 36: ...QGHQVDWDEODXI OHNWURNDEHO OHFWULF OLQHV DVH RI KHDW SXPS UHD RI RSHQLQJV IRU KHDWLQJ FLUFXLW FRQGHQVDWH GUDLQ HOHFWULFDO FDEOH LJQHV pOHFWULTXHV 6RFOH 3 3DVVDJHV FLUFXLW GH FKDXIIDJH pFRXOHPHQW GX FRQ...

Page 37: ...OHNWURNDEHO OHFWULF OLQHV DVH RI KHDW SXPS UHD RI RSHQLQJV IRU KHDWLQJ FLUFXLW FRQGHQVDWH GUDLQ HOHFWULFDO FDEOH LJQHV pOHFWULTXHV 6RFOH 3 3DVVDJHV FLUFXLW GH FKDXIIDJH pFRXOHPHQW GX FRQGHQVDW FkEOH...

Page 38: ...RPPDWLRQ GH SXLVVDQFH HQ N FRPSULV SDUW GH FRQVRPPDWLRQ GH OD SRPSH UXFNYHUOXVW LQ 3D 3UHVVXUH ORVV LQ 3D 3HUWH GH SUHVVLRQ HQ 3D XIWHLQWULWWVWHPSHUDWXU LQ LU LQOHW WHPSHUDWXUH LQ 7HPSpUDWXUH G HQWUpH...

Page 39: ...DWXUH G HQWUpH G DLU HQ UXFNYHUOXVW LQ 3D 3UHVVXUH ORVV LQ 3D 3HUWH GH SUHVVLRQ HQ 3D XIWHLQWULWWVWHPSHUDWXU LQ LU LQOHW WHPSHUDWXUH LQ 7HPSpUDWXUH G HQWUpH G DLU HQ XIWHLQWULWWVWHPSHUDWXU LQ LU LQOHW...

Page 40: ...H PP OO FURVV VHFWLRQV PP 7RXWHV OHV VHFWLRQV PP 6WHXHUOHLWXQJ PP RQWURO OHDG PP LJQH GH FRPPDQGH PP SRO SROH S OHV lUPHSXPSHQUHJOHU 1 HDW SXPS FRQWUROOHU 1 5pJXODWHXU GH SRPSH j FKDOHXU 1 NHLQH XQNWL...

Page 41: ...www dimplex de A VII Anhang Appendix Annexes 3 2 3 2 Last Load Charge LA 11AS 1HW 0DLQV 5pVHDX 3 9HUWHLOHU 3 GLVWULEXWRU LVWULEXWHXU 3 8 PLQ LHIHU XVWDQG V GHOLYHUHG VWDWH WDW j OD OLYUDLVRQ...

Page 42: ...FKDOHXU 1 lUPHSXPSHQUHJOHU 1 HDW SXPS FRQWUROOHU 1 5pJXODWHXU GH SRPSH D FKDOHXU 1 GHU XQG 3LQQXPPHUQ LUH DQG SLQ QXPEHUV 1XPpURV GH EULQV HW GH EURFKHV GHU XQG 3LQQXPPHUQ LUH DQG SLQ QXPEHUV 1XPpURV...

Page 43: ...ventilator Relais de puissance du ventilateur M1 Verdichter Compressor Compresseur M2 Ventilator Ventilator Ventilateur N1 W rmepumpenmanager Heat Pump Manager Gestionnaire de pompe chaleur N7 Sanftan...

Page 44: ...7RXWHV OHV VHFWLRQV PP 6WHXHUOHLWXQJ PP RQWURO OHDG PP LJQH GH FRPPDQGH PP SRO SROH S OHV lUPHSXPSHQUHJOHU 1 HDW SXPS FRQWUROOHU 1 5pJXODWHXU GH SRPSH j FKDOHXU 1 NHLQH XQNWLRQ EHL 35 HWULHE QR IXQFWL...

Page 45: ...www dimplex de A XI Anhang Appendix Annexes 3 6 3 6 Last Load Charge LA 16AS 1HW 0DLQV 5pVHDX 3 9HUWHLOHU 3 GLVWULEXWRU LVWULEXWHXU 3 8 PLQ LHIHU XVWDQG V GHOLYHUHG VWDWH WDW j OD OLYUDLVRQ...

Page 46: ...FKDOHXU 1 lUPHSXPSHQUHJOHU 1 HDW SXPS FRQWUROOHU 1 5pJXODWHXU GH SRPSH D FKDOHXU 1 GHU XQG 3LQQXPPHUQ LUH DQG SLQ QXPEHUV 1XPpURV GH EULQV HW GH EURFKHV GHU XQG 3LQQXPPHUQ LUH DQG SLQ QXPEHUV 1XPpURV...

Page 47: ...ventilator Relais de puissance du ventilateur M1 Verdichter Compressor Compresseur M2 Ventilator Ventilator Ventilateur N1 W rmepumpenmanager Heat Pump Manager Gestionnaire de pompe chaleur N7 Sanfta...

Page 48: ...inzipschemen Hydraulic Plumbing Diagrams Sch mas hydrauliques 4 1 Monoenergetische Anlage mit einem Heizkreis Mono energy system with one heating circuits Installation mono nerg tique avec un circuits...

Page 49: ...isen und Warmwasserbereitung Mono energy system with two heating circuits and domestic hot water preparation Installation mono nerg tique avec deux circuits de chauffage et production d eau chaude san...

Page 50: ...sserbereitung Bivalent system with two heating circuits and domestic hot water preparation Installation bivalente avec deux circuits de chauffage et production d eau chaude sanitaire 9 1 5 1 1 1 1 0 1...

Page 51: ...ed in series R servoir tampon en s rie Warmwasserspeicher Hot water cylinder R servoir d eau chaude sanitaire E9 Flanschheizung Warmwasser Flange heater hot water Cartouche chauffante ECS E10 1 Tauchh...

Page 52: ...96 EG EMV Richtlinie 2004 108 EG Druckger terichtlinie 97 23 EG EC Directives Low voltage directive 2006 95 EC EMC directive 2004 108 EC Pressure equipment directive 97 23 EC Directives CEE Directive...

Page 53: ...www dimplex de A XIX Anhang Appendix Annexes 5...

Page 54: ...A XX Anhang Appendix Annexes 5...

Page 55: ...www dimplex de A XXI Anhang Appendix Annexes 5...

Page 56: ...schland GmbH Gesch ftsbereich Dimplex Am Goldenen Feld 18 D 95326 Kulmbach Irrt mer und nderungen vorbehalten Subject to alterations and errors Sous r serve d erreurs et modifications 49 0 9221 709 56...

Reviews: