background image

 

8

 

 
5.2 Electrical 

Connection 

 

The HPCDW is pre-wired, ready for connection, the power is supplied via the mains cable connected to a socket 
with earthing contact (GB: "Home Office socket") (~230 V, 50 or 60 Hz). This socket must be accessible also after 
the installation has been completed. 
 

 
 
 
 
 
 
 
 

 
6. Commissioning 

 

 

6.1  Domestic Water Circuit

 

 

  

Caution!  

 

The HPCDW may only be operated with the unit filled with water!

 

 
 
6.1.1  Water circuit requirements 
 

On the consumer side, the following materials may be incorporated into the water circuit: 

Â

 copper 

 

   

Â

 stainless 

steel 

   

Â

 brass 

   

Â

 plastic  

Depending on the materials used in the hot water circuit (installation to be provided by the customer), corrosion 
damage may occur due to material incompatibilities. This must be taken into account, in particular where 
galvanised materials and those containing aluminium are used. A filter may have to be provided if there is a danger 
of the water being contaminated during operation. 

 
 
 
6.1.2  Commissioning of the domestic water system  
 

• 

All installations at the water and air circuits as well as all electrical installations must have been properly 
executed and completed. 

 

• 

Fill water circuit via external connection. The domestic water tank must be filled from below, i.e. via the 
domestic water outlet tap (see Fig. 1 and hydraulic plumbing diagram in the appendix)  (during operation, the 
top-up water enters the domestic water tank from the top). 

 

• 

Bleed the domestic water circuit (open water taps at the topmost points of use until no more air escapes, or 
open air bleed cocks in the water circuit – to be provided by the customer). 
 

• 

Perform a leak test of the entire domestic water circuit. 

 

• 

Connect the unit to the power supply

 

 

• 

Turn on the "heat pump" switch (Fig. 5). 

 

• 

The desired domestic water temperature is continuously adjustable (16° - 25 °C) by means of a temperature 
selector dial (Fig. 5). An appropriate time period (cooling period) must be allowed for until the selected 
temperature level is reached.

 

 

 

Summary of Contents for KWP 300

Page 1: ...Installation and Operating Manual Heat Pump for Cooling of Domestic Water with Airduct Connection KWP 300 451902 67 39 FD8411...

Page 2: ...Connection 8 6 Commissioning 8 6 1 Domestic Water Circuit 8 6 2 Operation of the Heat Pump for Cooling of Domestic Water 9 7 Maintenance Service 10 7 1 Water Circuit 10 7 2 Air Circuit 10 7 3 Sacrifi...

Page 3: ...explosion hazard due to gases vapours or dust The operation of the unit is not permitted with empty storage tank during the construction phase In the design and construction of the HPCDW all relevant...

Page 4: ...ted from the domestic water at a low evaporation temperature and transferred to the refrigerant The vaporous refrigerant is drawn in by an electrically driven compressor and compressed to a higher pre...

Page 5: ...ing STL 2 3 3 Temperature controller for immersion heater TC The temperature controller for the immersion heater controls the temperature of the water for domestic use during the immersion heater mode...

Page 6: ...d see Figure If transport in an inclined position cannot be avoided the HPCDW heat pump switch should be taken into operation one hour after it has been moved into final position at the earliest Cauti...

Page 7: ...ently tighten the check nuts provided on the levelling feet 5 Mounting 5 1 Connection of Water Piping The nominal pipe widths of the field installed sanitary installations must be determined on the ba...

Page 8: ...f there is a danger of the water being contaminated during operation 6 1 2 Commissioning of the domestic water system All installations at the water and air circuits as well as all electrical installa...

Page 9: ...g panel Switch position O heat pump is OFF in switch position the heat pump is in operation Heat pump switch Temperature dial for domestic water setpoint trans mitter left stop lowest cooling temperat...

Page 10: ...ontent is heated up to the maximum temperature of the immersion heater controller factory setting 65 C In switch position the immersion heater is switched off Note If the immersion heater switch is in...

Page 11: ...eplaced if necessary The electrical check is to be conducted by means of a suitable ammeter without draining the water in the tank Procedure n Withdraw PE wire from tab of sacrificial anode o Connect...

Page 12: ...he temperature of the intake air lies above the permissible limit value 45 C If the malfunction cannot be corrected based on the above questions please consult your installer or customer service 9 Dec...

Page 13: ...mers heater 16 Insulation 3 Evaporator 10 Temperature display 4 Hot water tank 11 Filter drier 5 Immersion heater 12 Expansion valve 6 Corrosion protection anode 13 Condenser 7 Temperature controller...

Page 14: ...ing valve 7 Diaphragm safety valve 3 Test valve to be mounted above tank edge 4 Check valve 8 Drain 5 Manometer connection Wasseranschlu nach DIN 1988 6 8 5 1 3 4 2 1 Wasserzulauf 7 8 1 Brauchwasseren...

Page 15: ...t Verdichter Ventilator Schalter EIN AUS W rmepumpe Schalter EIN AUS El Heizung Netzstecker Klemmleiste intern B1 B3 C1 C2 E1 F1 F2 F3 K2 K3 M1 M2 S1 S2 X1 X3 Legende 2 S1 1 T B1 4 18 26 C Verdichter...

Page 16: ...air C 20 to 45 Water temperature selectable heat pump mode C 16 to 25 Heat up time from 25 C to 65 C electr immersion heater h 9 2 Power consumption electric heating watt 1500 Average power consumpti...

Page 17: ...17 KKW Kulmbacher Klimager te Werk GmbH Subject to technical changes Department Dimplex Fax 0 92 21 709 589 Am Goldenen Feld 18 www dimplex de D 95326 Kulmbach...

Reviews: