7.1 Water 

Circuit 

 

The inspection of the water circuit is limited to any filters that may have been field-installed, and the performance of 
leak tests. Dirty water filters have to be cleaned and replaced, if necessary.  

 
 

7.2    Air Circuit 

 

The maintenance activities are limited to cleaning the fin-type heat exchanger (only) as required.

 

 

Caution!

 

Hazard of injury from sharp-edged fins. Fins must not be distorted or damaged ! 
 
If air filters are used, these must be regularly checked for contamination and to be cleaned or replaced, if 
necessary. 

 
 

7.3 Sacrificial 

Anode 

 

The sacrificial anode installed in the domestic water tank for corrosion protection purposes, must be checked 
electrically on a regular basis, at least every two years after commissioning, and be replaced, if necessary. The 
electrical check is to be conducted by means of a suitable ammeter without draining the water in the tank.  

 

 

Procedure: 

 
 

n

 

Withdraw PE wire from tab of sacrificial anode. 

 

o

 

Connect ammeter (0...50 mA) between PE conductor and tab. 

 

p

 

Evaluation of wear of sacrificial anode: 

 

 

 

Measured value > 1 mA  

 sacrificial anode is okay. 

 

 

 

Measured value < 1 mA  

 sacrificial anode must be checked or replaced. 

 
If an unambiguous electrical check is not possible, it is recommended that a visual inspection by an expert be 
performed. 
(For a replacement of the sacrificial anode that may be necessary [to be performed by an expert], the water must 
be drained from the tank via the drain valve (to be provided upon installation – see appendix).  
 
Caution
:  Protective anodes that are impaired in their function will reduce the life of the unit!

         

 

The sacrificial anode is screwed into the storage tank below 
the immersion heater  
(covered with a plastic cap)  

Fig. 6: 

sacrificial anode

 

Summary of Contents for KWP 300

Page 1: ...Installation and Operating Manual Heat Pump for Cooling of Domestic Water with Airduct Connection KWP 300 451902 67 39 FD8411...

Page 2: ...Connection 8 6 Commissioning 8 6 1 Domestic Water Circuit 8 6 2 Operation of the Heat Pump for Cooling of Domestic Water 9 7 Maintenance Service 10 7 1 Water Circuit 10 7 2 Air Circuit 10 7 3 Sacrifi...

Page 3: ...explosion hazard due to gases vapours or dust The operation of the unit is not permitted with empty storage tank during the construction phase In the design and construction of the HPCDW all relevant...

Page 4: ...ted from the domestic water at a low evaporation temperature and transferred to the refrigerant The vaporous refrigerant is drawn in by an electrically driven compressor and compressed to a higher pre...

Page 5: ...ing STL 2 3 3 Temperature controller for immersion heater TC The temperature controller for the immersion heater controls the temperature of the water for domestic use during the immersion heater mode...

Page 6: ...d see Figure If transport in an inclined position cannot be avoided the HPCDW heat pump switch should be taken into operation one hour after it has been moved into final position at the earliest Cauti...

Page 7: ...ently tighten the check nuts provided on the levelling feet 5 Mounting 5 1 Connection of Water Piping The nominal pipe widths of the field installed sanitary installations must be determined on the ba...

Page 8: ...f there is a danger of the water being contaminated during operation 6 1 2 Commissioning of the domestic water system All installations at the water and air circuits as well as all electrical installa...

Page 9: ...g panel Switch position O heat pump is OFF in switch position the heat pump is in operation Heat pump switch Temperature dial for domestic water setpoint trans mitter left stop lowest cooling temperat...

Page 10: ...ontent is heated up to the maximum temperature of the immersion heater controller factory setting 65 C In switch position the immersion heater is switched off Note If the immersion heater switch is in...

Page 11: ...eplaced if necessary The electrical check is to be conducted by means of a suitable ammeter without draining the water in the tank Procedure n Withdraw PE wire from tab of sacrificial anode o Connect...

Page 12: ...he temperature of the intake air lies above the permissible limit value 45 C If the malfunction cannot be corrected based on the above questions please consult your installer or customer service 9 Dec...

Page 13: ...mers heater 16 Insulation 3 Evaporator 10 Temperature display 4 Hot water tank 11 Filter drier 5 Immersion heater 12 Expansion valve 6 Corrosion protection anode 13 Condenser 7 Temperature controller...

Page 14: ...ing valve 7 Diaphragm safety valve 3 Test valve to be mounted above tank edge 4 Check valve 8 Drain 5 Manometer connection Wasseranschlu nach DIN 1988 6 8 5 1 3 4 2 1 Wasserzulauf 7 8 1 Brauchwasseren...

Page 15: ...t Verdichter Ventilator Schalter EIN AUS W rmepumpe Schalter EIN AUS El Heizung Netzstecker Klemmleiste intern B1 B3 C1 C2 E1 F1 F2 F3 K2 K3 M1 M2 S1 S2 X1 X3 Legende 2 S1 1 T B1 4 18 26 C Verdichter...

Page 16: ...air C 20 to 45 Water temperature selectable heat pump mode C 16 to 25 Heat up time from 25 C to 65 C electr immersion heater h 9 2 Power consumption electric heating watt 1500 Average power consumpti...

Page 17: ...17 KKW Kulmbacher Klimager te Werk GmbH Subject to technical changes Department Dimplex Fax 0 92 21 709 589 Am Goldenen Feld 18 www dimplex de D 95326 Kulmbach...

Reviews: