Dimplex IL095 Installation And User Manual Download Page 11

 

11 

 

 

 

 

Water comes in through the inlet, via a flow switch. 
The flow switch measures how much water is passing through the unit.                                                      

If it detects more than the preset level of:- 
2.7 litres/minute for the 9.5kW model and 3.3 litres/minute for the 10.8kW and 12.0kW models 

 

The units heating elements are switched on. This is shown by the neon light glowing. 

 

The water is heated instantly as it passes through the copper heat exchanger tube. 

 

The temperature of the water coming out of the unit depends on:- 

 

The temperature of the mains water supply 

 

The water flow rate 

 

The power consumption of the unit 

 

The temperature of the main supply can vary from 5°C in winter up to about 20°C in summer, with 
an average of about 12°C. The charts below show the water temperature (°C) you can expect from 

the unit, operating at 9.5/10.8/12.0Kw for the different flow rates (in litres/minute) 

 

9.5kW IL095 

 

Flow rate (l/m) 

3.0 

4.0 

6.0 

Summer temp °C 

54° 

43° 

Winter temp °C 

50° 

39° 

28° 

 

10.8kW IL095 

 

Flow rate (l/m) 

4.0 

5.0 

6.0 

Summer temp °C 

51° 

46° 

Winter temp °C 

44° 

36° 

31° 

 

12.0kW IL095 

 

Flow rate (l/m) 

5.0 

6.0 

7.0 

Summer temp °C 

54° 

49° 

44° 

Winter temp °C 

39° 

34° 

30° 

  

This means that with the 12.0kW unit you can shower at 39°C with a flow rate of 5 litres/minute in 

the middle of winter. 

 

The unit includes a dual thermal cut-out (diagram 10) which is attached to                                                       

the heat exchanger tube. It will switch off the heater elements if the water                                                                 
flow is reduced too much and the temperature goes above a set limit. 

 

The first stage cut-out is cyclic and will automatically reset as the water                                              
temperature falls. The unit will then function normally again. 

 

The second stage cut-out when triggered needs to be reset manually inside the unit. 

This cut-out will only operate in exceptional circumstances (diagram 11) 
The unit can supply more than one outlet – for example, a shower and a basin, or two basins – but 
water from the unit will be shared between the outlets. This is particularly important if a unit supplies 
a shower and a basin, as the basin should not be used while someone is using the shower. 

 

HOW YOUR 

IL095 

WORKS 

On average 
(12°C main water supply at 4 litres/minute) 
an outlet temperature of 46°C will be achieved. 

 

On average 

(12°C main water supply at 5 litres/minute) an 
outlet temperature of 43°C will be achieved.

 

On average 
(12°C main water supply at 6 litres/minute) an 

outlet temperature of 41°C will be achieved.

 

Summary of Contents for IL095

Page 1: ...th the user after installation and demonstration It should be kept in a safe place as you may need to refer to it for general instructions or future maintenance DIMPLEX IL095 INSTANT INLINE UNVENTED W...

Page 2: ...dations All wiring and installation must be supervised by a suitably qualified person THIS APPLIANCE MUST BE EARTHED The installation must be in accordance with the current edition of BS 7671 the IEE...

Page 3: ...5 psi 1 1 bar 103 kPa 150 psi 10 3 bar 1035 kPa Up to 10 8kW 15 psi 1 1 bar 103 kPa 150 psi 10 3 bar 1035 kPa 20 psi 1 4 bar 138 kPa 150 psi 10 3 bar 1035 kPa Up to 12 0kW 20 psi 1 4 bar 138 kPa 150 p...

Page 4: ...rommet from the backplate diagram 3 Feed the cable through the grommet before you fix the unit to the wall Fixing to the wall Undo the retaining nuts and take the front cover off the unit Hold the bac...

Page 5: ...les Connecting the unit to the pipes The inlet and outlet are clearly marked on the unit They each have a 15mm straight shank connections The unit comes with a service valve diagram 5 which should be...

Page 6: ...the 10 8kW unit 50 amps for the 12 0kW unit Wire the unit using 10mm cable and a suitable Fuse MCB 45 amps Fuse MCB for the 10 8kW unit 50 amps Fuse MCB for the 12 0kW unit If the unit is fitted in a...

Page 7: ...ce valve slightly If the unit is to supply a shower turn the hot water tap on the mixer unit fully on turn the service valve anti clockwise until the neon light goes out then turn it back until the ne...

Page 8: ...have finished do not switch off the power if you are going to use the unit again shortly Shower Check that the power is switched on at the mains local isolator switch Turn on the hot or flow tap FULL...

Page 9: ...ow and the thermal cut out is operating A second outlet has been turned on Increase the supply water flow Make sure that the service valve is correctly adjusted Do not use the basin whilst using the s...

Page 10: ...n supply to the INLET marked in blue Use a pump to boost the supply from a storage tank Reset it by opening the unit and pushing the button on the cut out diagram 11 Before you do this you must remove...

Page 11: ...p C 54 49 44 Winter temp C 39 34 30 This means that with the 12 0kW unit you can shower at 39 C with a flow rate of 5 litres minute in the middle of winter The unit includes a dual thermal cut out dia...

Page 12: ...LEX UK LIMITED MILLBROOK HOUSE GRANGE DRIVE HEDGE END SOUTHAMPTON SO30 2DF We offer a technical advisory service on the telephone RING 0845 6000 5111 GUARANTEE AND CONTACT DETAILS A4 Leaflet No 579 21...

Reviews: