www.dimplex.de 452235.66.09 · FD 9209
EN-5
English
WI 10TU - WI 22TU
7 Installation
7.1 General Information
The following connections need to be established on the heat
pump:
Flow and return flow of the well system
Flow and return flow of the heating system
Temperature sensor
Voltage supply
7.2 Heating System Connection
ATTENTION!
Flush the heating system prior to connecting the heat pump.
Before connecting the heating water system to the heat pump,
the heating system must be flushed to remove any impurities,
residue from sealants, etc. Any accumulation of deposits in the
liquifier could cause the heat pump to completely break down.
Once the heating system has been installed, it must be filled, de-
aerated and pressure-tested.
Consideration must be given to the following when filling the sys-
tem:
Untreated filling water and make-up water must be of drink-
ing water quality (colourless, clear, free from sediments)
Filling water and make-up water must be pre-filtered (pore
size max. 5 µm).
Scale formation in hot water heating systems cannot be com-
pletely avoided, but in systems with flow temperatures below
60 °C the problem can be disregarded.
With medium and high-temperature heat pumps, temperatures
above 60 °C can be reached.
The following standard values should therefore be adhered to
concerning the filling water and make-up water (according to VDI
2035 Sheet 1):
Minimum heating water flow rate
The minimum heating water flow rate through the heat pump
must be assured in all operating states of the heating sys-
tem. This can be accomplished, for example, by installing either
a dual differential pressureless manifold or an overflow valve.
The procedure for adjusting an overflow valve is described in the
Chapter Start-Up.
NOTE
The use of an overflow valve is only recommended for panel heating and
a max. heating water flow of 1.3 m³/h. System faults may result if this is
not observed.
The antifreeze function of the heat pump manager is active
whenever the heat pump manager and the heat circulating
pumps are ready for operation. If the heat pump is taken out of
service or in the event of a power failure, the system has to be
drained. The heating circuit should be operated with a suitable
antifreeze if heat pump systems are implemented in buildings
where a power failure can not be detected (holiday home).
7.3 Heat Source Connection
The following procedure must be observed when connecting the
heat source:
Connect the well pipes to the heat pump's flow and return.
ATTENTION!
The well water must comply with the required water quality standards.
(see Cap. 9.4 on pag. 8)
The hydraulic integration diagram must be adhered to.
7.4 Temperature sensor
The following temperature sensors are already installed or must
be installed additionally:
External temperature sensor (R1) supplied
Return temperature heating circuit (R2) installed
Return temperature primary circuit (R24) installed
Flow temperature heating circuit (R9) installed
Flow temperature primary circuit (R6) installed
7.4.1 Sensor characteristic curves
The temperature sensors to be connected to the heat pump ma-
nager must correspond to the sensor characteristic curve illustra-
ted in Fig.7.1 on pag. 5. The only exception is the external tem-
perature sensor included in the scope of supply of the heat pump
(see Fig.7.2 on pag. 6)
Fig. 7.1: Sensor characteristic curve NTC 10
Total heat
output in [kW]
Total alkaline earths
in mol/m³ and/or
mmol/l
Total
hardness in °dH
up to 200
≤
2.0
≤
11.2
200 to 600
≤
1.5
≤
8.4
> 600
< 0.02
< 0.11
Temperature in °C
-20
-15
-10
-5
0
5
10
NTC-2 in k
Ω
14.6
11.4
8.9
7.1
5.6
4.5
3.7
NTC-10 in k
Ω
67.7
53.4
42.3
33.9
27.3
22.1
18.0
15
20
25
30
35
40
45
50
55
60
2.9
2.4
2.0
1.7
1.4
1.1
1.0
0.8
0.7
0.6
14.9
12.1
10.0
8.4
7.0
5.9
5.0
4.2
3.6
3.1
7HPSHUDWXUHLQ>&@
5HVLVWDQFHYDOXHLQ
>N2KP@
Summary of Contents for I 22TU
Page 2: ......
Page 14: ...DE 12 452235 66 09 FD 9209 www dimplex de Deutsch WI 10TU WI 22TU...
Page 36: ...FR 12 452235 66 09 FD 9209 www dimplex de Fran ais WI 10TU WI 22TU...
Page 57: ...www dimplex de 452235 66 09 FD 9209 A XXI Anhang Appendix Annexes WI 10TU WI 22TU...
Page 58: ...A XXII 452235 66 09 FD 9209 www dimplex de Anhang Appendix Annexes WI 10TU WI 22TU...
Page 59: ...www dimplex de 452235 66 09 FD 9209 A XXIII Anhang Appendix Annexes WI 10TU WI 22TU...