Dimplex DPRC29ECO-B Instruction Manual Download Page 7

7

•  Repair to intrinsically safe components

 

 Do not apply any permanent inductive or capacitance loads to the circuit without 

ensuring that this will not exceed the permissible voltage and current permitted 

for the equipment in use. Intrinsically safe components are the only types that 

can be worked on while live in the presence of a flammable atmosphere. The test 

apparatus shall be at the correct rating. Replace components only with parts 

specified by the manufacturer. Other parts may result in the ignition of refrigerant 

in the atmosphere from a leak.

• Cabling

 

 Check that cabling will not be subject to wear, corrosion, excessive pressure, 

vibration, sharp edges or any other adverse environmental effects. The check shall 

also take into account the effects of aging or continual vibration from sources such 

as compressors or fans.

•  Detection of flammable refrigerants

 

 Under no circumstances shall potential sources of ignition be used in the searching 

for or detection of refrigerant leaks. A halide torch (or any other detector using a 

naked flame) shall not be used.

•  Leak detection methods

 

 The following leak detection methods are deemed acceptable for systems containing 

flammable refrigerants. Electronic leak detectors shall be used to detect flammable 

refrigerants, but the sensitivity may not be adequate, or may need re-calibration. 

(Detection equipment shall be calibrated in a  refrigerant-free area.) Ensure that the 

detector is not a potential source of ignition and is suitable for the refrigerant used. 

Leak detection equipment shall be set at a percentage of the LFL of the refrigerant  

and shall be calibrated to the refrigerant employed and the appropriate percentage 

of gas (25 %maximum) is confirmed. Leak detection fluids are suitable for use with 

most refrigerants but the use of detergents containing chlorine shall be avoided as 

the chlorine may react with the refrigerant and corrode the copper pipe-work. If a 

leak is suspected, all naked flames shall be removed/ extinguished. If a leakage of 

refrigerant is found which requires brazing, all of the refrigerant shall be recovered 

from the system, or isolated (by means of shut off valves) in a part of the system 

remote from the leak. Oxygen free nitrogen (OFN) shall then be purged through the 

system both before and during the brazing process.

•  Removal and evacuation

 

 When breaking into the refrigerant circuit to make repairs or for any other purpose 

conventional procedures shall be used. However, it is important that best practice 

is followed since flammability is a consideration. The following procedure shall be 

adhered to: Remove refrigerant; Purge the circuit with inert gas; Evacuate; Purge 

again with inert gas; Open the circuit by cutting or brazing. The refrigerant charge 

shall be recovered into the correct recovery cylinders. The system shall be flushed 

with OFN to render the unit safe. This process may need to be repeated several 

times. Compressed air or oxygen shall not be used for this task. Flushing shall be 

achieved by breaking the vacuum in the system with OFN and continuing to fill until 

the working pressure is achieved, then venting to atmosphere, and finally pulling 

down to a vacuum. This process shall be repeated until no refrigerant is within the 

system. When the final OFN charge is used, the system shall be vented down to 

atmospheric pressure to enable work to take place. This operation is absolutely vital if 

brazing operations on the pipe-work are to take place. Ensure that the outlet for the 

vacuum pump is not close to any ignition sources and there is ventilation available.

15429_Dimplex DPRC29ECO-B Manual.indd   7

15429_Dimplex DPRC29ECO-B Manual.indd   7

7/09/20   4:27 PM

7/09/20   4:27 PM

Summary of Contents for DPRC29ECO-B

Page 1: ...table Air Conditioner Model DPRC29ECO B For domestic household use only INSTRUCTION MANUAL 15429_Dimplex DPRC29ECO B Manual indd 1 15429_Dimplex DPRC29ECO B Manual indd 1 7 09 20 4 27 PM 7 09 20 4 27...

Page 2: ...t place on soft unstable or non horizontal angled surfaces Never operate the appliance if a cable or connector has been damaged after appliance malfunction or if the appliance was dropped or is otherw...

Page 3: ...witch off the unit and take the plug out of the socket If you are not using the unit Before you clean or carry out maintenance on the unit If a fault occurs In the event of an electrical storm Avoid e...

Page 4: ...ption the description on label shall prevail Compliance with national gas regulations shall be observed Keep ventilation openings clear of obstruction The appliance shall be stored so as to prevent me...

Page 5: ...e checked with an appropriate refrigerant detector prior to and during work to ensure the technician is aware of potentially flammable atmospheres Ensure that the leak detection equipment being used i...

Page 6: ...uate temporary solution shall be used This shall be reported to the owner of the equipment so all parties are advised Initial safety checks shall include That capacitors are discharged this shall be d...

Page 7: ...able for use with most refrigerants but the use of detergents containing chlorine shall be avoided as the chlorine may react with the refrigerant and corrode the copper pipe work If a leak is suspecte...

Page 8: ...em electrically c Before attempting the procedure ensure that Mechanical handling equipment is available if required for handling refrigerant cylinders All personal protective equipment is available a...

Page 9: ...hall be available and in good working order Hoses shall be complete with leak free disconnect couplings and in good condition Before using the recovery machine check that it is in satisfactory working...

Page 10: ...igh Capacity in a compact size with cooling heating dehumidifying and ventilating function Temperature setting and display LED Digital display Electronic control with built in timer sleep mode Self ev...

Page 11: ...pening with sealing plug 1 2 3 4 5 6 7 Note The appearance is only for reference Please see the real product for detailed information Accessories 1 Exhaust hose 2 Hose connector 3 Window kit adapter 4...

Page 12: ...ves or other products that products that produce heat Direct sunlight Mechanical vibration or shock Excessive dust Lack of ventilation such as cabinet or bookcase Uneven surface WARNING Install the un...

Page 13: ...duct tape if required It is recommended that the gap between the adapter and the sides of the window should be sealed off for maximum efficiency Step 5 Attach the hose connector to the exhaust air ou...

Page 14: ...setting 5 Indicators LED for fan speed High Low 6 TIMER Press to set a time for the unit to automatically start or stop 7 Speed Press to switch the fan speed between HIGH and LOW 8 Digital Display Di...

Page 15: ...ture 2 Heating your room Optional for Heating Function Unit only Press MODE button repeatedly until the LED of HEAT operation lights up Press UP DOWN button to set the temperature higher than the room...

Page 16: ...es in the cooling operation or drying operation and the ambient temperature sensor senses the evaporator coil temperature is below 1 C then the compressor will stop operating for 10 minutes or until t...

Page 17: ...nit before operating Remove the plug of the water outlet opening and keep it in safe area Securely and properly connect the drain hose and make sure it is not kinked and clear of obstruction Place the...

Page 18: ...unit and unplug the power cord 2 Remove the filter mesh from the unit 3 Use a vacuum cleaner to suck dust from the filter 4 Turn the filter over and rinse the air filter under running water Let the wa...

Page 19: ...olate and ventilate area 5 Do not get in eyes on skin or on clothing Do not breathe vapors or gas 6 Prevent entry to sewers and public waters 7 Stop the source of the release if safe to do so Consider...

Page 20: ...s securely attached Water Leakage Overflow while moving the unit Empty the water tank before transport Check if the drain hose is kinked or bends Straighten the hose to avoid a trap existing Excessive...

Page 21: ...rving the machine in ventilating dry non corrosive gas and safe place indoor ATTENTION The evaporator inside the machine has to be dried out before the unit is packed to avoid component damage and mol...

Page 22: ...22 15429_Dimplex DPRC29ECO B Manual indd 22 15429_Dimplex DPRC29ECO B Manual indd 22 7 09 20 4 27 PM 7 09 20 4 27 PM...

Page 23: ...3179 Victoria Australia Ph 1300 556 816 Glen Dimplex New Zealand Ltd 38 Harris Road East Tamaki Auckland 2013 New Zealand Ph 0800 666 2824 Maintenance Warranty Recycling Do not dispose of electrical...

Page 24: ...co nz www dimplex co nz Glen Dimplex New Zealand Ltd All rights reserved Material contained in this publication may not be reproduced in whole or in part without prior permission in writing of Glen Di...

Reviews: