11
Installation
WARNING
• Ensure ceiling or wall structure is suitable for this application and capable of supporting the weight of the heater
plus any approved mounting accessories used. Always use hardware suitable for your application. Mounting
hardware is not included.
• Electrical connections/GPOs should not be located at the back of the heater. They should be located outside
the physical footprint of the units to minimize heat build-up behind the units.
• If the heater is to be mounted on an incline (such as on a vaulted ceiling), ensure the electrical connection is
located at the lowest point of the heater (
Figure 7
).
• For wall-mounted installations, ensure heater is angled downward to prevent or property damage
or fire. (
Figure 8
).
CEILING
CEILING
CEILING
CEILING
INCORRECT
INSTALLATION
CORRECT
INSTALLATION
Figure 7
Figure 8
Wall-mount Installation
The heater can also be mounted on a wall and angled downwards. In this situation, ensure the mounting height puts
the heater in the range of 96" to 105" (2.4 m to 2.7 m) and that the area to be warmed is within 98" (2.5 m) of the wall.
Mounting hardware is not included.
DO NOT ANGLE
HEATER TOWARD
CEILING