Thermostatic control

A capillary type thermostat is factory fi tted within the unit, as per 

‘C’ in

 Fig. 8

, giving a selection scale of 0-40ºC. When the ther-

mostat operates, the power output will reduce depending on the 

switch setting.

- Fan only - No effect

- Half Heat - Heater will reduce to Fan only

- Full Heat - Heater will reduce to Half Heat

Door switch control (Electric models)

By including a door switch in the circuit (as per ‘D’ in Fig. 8) the 

air curtain will respond to door openings as follows:
(1)  

Door opening will energise the air curtain at the set condi-

tions (switch box settings).

(2)  

On door closure operation will continue at the set condi-

tions for a further 1 minute.

(3)  

Between 1 minute and 2 minutes from door closure, set 

back operation, ½ heat (if heat selected) and ½ fan will 

activate.

(4)  

Between 2 minutes and 3 minutes, the fan only (½ speed) 

shut down cycle will be engaged.

(5)  

After 3 minutes, the air curtain will return to a dormant 

state until the door is re-opened.

 

If the door re-opens during this 3 minute run on cycle, the  

process will restart at (1).

Thermal Safety cut outs

The power supply to the heating elements will be interrupted if 

one or a combination of the following abnormal events occur:
1.  

Air inlet or outlet grilles are obstructed.

2.  

Internal ventilation is impaired due to build up of dust and 

fl uff.

3.  

Blower unit stalls.

Before resetting the thermal safety cut-outs you must turn 

the power OFF

.  Unlock the grille by moving the two sliders 

into the open position 

‘x’ as shown in Fig. 2A

, using a small 

screw driveror other suitable tool.  With the grille partially open 

disconnect the safety cord to allow the grille to fully open. Then 

access the reset buttons as shown in 

‘y’ in Fig. 2B

. Before 

re-setting the reason for activation must be determined and 

corrective action taken.

Low Pressure Hot Water (LPHW) heated
Ambient (fan only) variants 
Operation using switch box - CABC6

Switch on electrical supply to the air curtain. Rotate the switch to 

the desired heat setting. Settings available are;

 

 

OFF

 

 

Low Fan

 

 

High Fan

The rocker (auto / manual) switch allows for manual over-ride of

a door switch if fi tted. Manual allows the appliance to run at the

desired setting, while Auto provides an energy saving feature by

shutting down the appliance while the door is closed.
The unit should always be switched OFF using the switch box 

control, and not by mains power supply interruption. When 

fi rst turned on the control will run through a system check. The 

selected settings will be reached and maintained after a 30 

second period.

Thermostatic control (optional)

1)

 A thermostatic regulation valve with a remote sensing bulb 

(not supplied) can be positioned in the supply water pipe-work to 

regulate the heat output.

2)

 An electrical 3-Port Solenoid Valve can also be connected into 

the system. Please contact your sales or service agent using the 

contact details provided.

Door switch control (Water heated & Ambient 

models)

 

By including a door switch in the circuit (as per ‘D’ in 

Fig. 9

 the 

air curtain will respond to door openings as follows:
(1) Door opening will energise the air curtain at the set conditions 

(switch box settings).
(2) On door closure operation will continue at the set conditions 

for a further 1 minute.
(3) Between 1 minute and 2 minutes from door closure ½ fan set 

back operation will activate.
(4) After 2 minutes, the air curtain will return to a dormant state 

until the door is re-opened. If the door re-opens during this 2 

minute run on cycle, the process will re-start at (1).

Wiring Diagrams

CAB & DAB ‘E’ - Electric models - see Fig. 8
CAB & DAB ‘W’ / ‘A’ - Water heated & Ambient

 models - see 

Fig. 9
C - Thermostat
D - Door Switch (Optional)
E - Thermal Safety Cut-out Circuit
F - Elements
-    BMS Switches (Optional)(S0,S1,S2)
M - Motor

Remote (BMS / BEMS) Operation

Connection to Building Energy Management Control Systems 

(BEMS) is possible so that remote control of the air curtain can 

be carried out in conjunction with other equipment. Please refer 

to the table in Fig. 8 & 9 to make the appropriate connections to 

the PCB.

Modular Connection

Refer to instructions provided with the modular linking kit.

De-rating the unit to operate at ½ heat setting

Please contact your sales or service agent using the contact 

details provided.

Operation on a Single Phase Supply

Please contact your sales or service agent using the contact 

details provided.

Summary of Contents for CAB10AR

Page 1: ...Direct website See website for further details Multi AwArd winning CoMpAny FamilyBusinessAwards DIY Big brands small prices co uk CABR CAB10AR CAB10ER CAB10WR CAB15AR CAB15ER CAB15WR DABR DAB10AR DAB1...

Page 2: ...co uk is a Love Shopping Direct website See website for further details Multi AwArd winning CoMpAny FamilyBusinessAwards DIY Big brands small prices co uk 1 2A A B C D E F G H J K L CAB10 E A W R 122...

Page 3: ...roducts at unbeatable prices Price Promise Guarantee we won t be beaten on price 250 000 Happy Customers five star customer reviews BigOnDIY co uk is a Love Shopping Direct website See website for fur...

Page 4: ...35 10 000 DIY Products at unbeatable prices Price Promise Guarantee we won t be beaten on price 250 000 Happy Customers five star customer reviews BigOnDIY co uk is a Love Shopping Direct website See...

Page 5: ...Children aged from 3 years and less than 8 years shall only switch on off the appliance provided that it has been placed or installed in its intended normal operating position and they have been given...

Page 6: ...cted settings will be reached and maintained after a 30 second period Electrical The installation of this appliance should be carried out by a competent electrician and be in accordance with the curre...

Page 7: ...an only variants Operation using switch box CABC6 Switch on electrical supply to the air curtain Rotate the switch to the desired heat setting Settings available are OFF Low Fan High Fan The rocker au...

Page 8: ...g occasionally with a damp cloth for stain removal a weak soap solution can be applied with a cloth and the surface wiped dry Care must be taken to avoid any moisture ingress into the product After Sa...

Reviews: