background image

Page 1

(Rev. 02/08)

L113

UL

C

US

R

Read and Save These Instructions

All Hoods Must Be Installed By A Qualified Installer

INSTALLATION INSTRUCTIONS

EUROLINE/EUROLINE PRO

ISLAND RANGE HOOD

Read All Instructions Thoroughly Before Beginning Installation

WARNING - TO REDUCE THE RISK OF FIRE, ELECTRIC SHOCK,

OR INJURY TO PERSONS, OBSERVE THE FOLLOWING:

A. Installation work and electrical wiring must be done by qualified

person(s) in accordance with all applicable codes and standards,
including fire-rated construction. Switch power off at service panel
and lock the service disconnecting means to prevent power from
being switched on accidentally during installation.

B. When cutting or drilling into wall or ceiling, do not damage

electrical wiring and other hidden utilities.

C. Ducted fans must always be vented to the outdoors.

D. Sufficient air is needed for proper combustion and exhausting of

gases through the flue (chimney) of fuel burning equipment to
prevent back drafting. Follow the heating equipment
manufacturer’s guideline and safety standards such as those
published by the National Fire Protection Association (NFPA), and
the American Society for Heating, Refrigeration and Air
Conditioning Engineers (ASHRAE), and local code authorities.

WARNING - TO REDUCE THE RISK OF FIRE, USE ONLY METAL

DUCTWORK

Summary of Contents for Euroline

Page 1: ...d lock the service disconnecting means to prevent power from being switched on accidentally during installation B When cutting or drilling into wall or ceiling do not damage electrical wiring and other hidden utilities C Ducted fans must always be vented to the outdoors D Sufficient air is needed for proper combustion and exhausting of gases through the flue chimney of fuel burning equipment to pr...

Page 2: ...ngled turns Instead use smooth gradual turns such as adjustable elbows or 45 degree angled turns For duct runs over 20 feet increase the duct diameter by one inch for every ten feet of duct A 90 degree elbow is equal to 5 feet of duct Using Vent A Hood roof jacks or wall louvers back page will ensure proper efficiency Airflow must not be restricted at the end of the duct run Do not use screen wire...

Page 3: ...he duct cover to the load bearing framework in the ceiling using appropriate hardware through the four inside corner mounting flanges on the top of the duct cover 4 Install the duct from the outside of the home down to the location of the exhaust outlet on the top of the transition plus 1 This will allow the transition to engage 1 inside of the duct Consult the connection diagrams on next page for...

Page 4: ...o brass screws on the bottom of the shield Gently close the back draft dampers from the top side of the hood To remove the blower housings unsnap the suitcase latches B one on each side of the housing The housings should be pulled forward and gently tipped to clear the blower wheels and then out of the hood Warning Make sure power is off and locked at the service disconnecting means on the service...

Page 5: ...and seal with duct tape The transition must fit inside the exhaust collar on the blower deck assembly Reconnect the electrical connector s For assemblies with two connectors connect the right harness to the front connector and the left harness to the back connector While taking care to properly align the duct connection between the transition and the duct in the ceiling reinstall the blower deck a...

Page 6: ...2 3 x 10 BACK VENT ELBOW MODEL DIM VP559 3 x 10 4 10 14 3 3 MULTI BLOWER TRANSITION MODEL DIM VP562 VP563 6 8 to 10 8 8 to 12 VP562 17 VP563 16 10 12 VP562 23 VP563 30 3 x 10 TO 7 TRANSITION MODEL DIM VP521 3 x 10 to 7 7 7 3 10 LOW PROFILE ROOF JACK MAXIMUM 4 12 PITCH MODEL DIM 6 VP539 VP540 VP541 6 Round 7 Round 8 Round 16 16 LOW PROFILE ROOF JACK MAXIMUM 4 12 PITCH MODEL DIM 10 VP552 VP553 10 Ro...

Reviews: