Dimplex Bellingham 12kW BLM12SE Operating Instructions Manual Download Page 6

Connect the flue pipe to the stove making sure that it fits snugly 

into the base of the flue collar . Seal the collar and flue connection 

with fire cement or with other suitable high temperature sealant. 

Add flue sections as required; note that all flue sockets must face 

upwards. Ensure that the flue pipe end is no closer than 76mm 

to  the  side  or  rear  of  the  chimney  walls.  It  is  essential  that  all 

connections between the stove and the chimney flue are sealed 

and made airtight. 
Avoid using bends greater than 45° to the vertical 

(Fig 7)

. All flue 

pipes should be as close to vertical where possible. For rear flue 

connection the length of the horizontal run of the flue pipe should 

not exceed 150mm 

(Fig 8)

. Both chimney and flue pipe must be 

accessible for cleaning and if ALL parts of the chimney cannot 

be reached, a soot door must be fitted to enable this to be done. 

This product must not be installed on a shared flue.

Flue Draught

The chimney should be checked before the stove is installed to 

ensure that there is adequate flue pull. The draught can be checked 

initially by using a smoke match close to the flue opening. If the 

chimney doesn’t pull the smoke it may suggest that the chimney 

needs further attention. Any remedial work to the chimney flue 

should be carried out by a suitably qualified engineer. 
A flue draught of minimum 12 Pascal to maximum 25 Pascal is 

required for satisfactory appliance performance. The flue draught 

should be checked under fire at high output and if it exceeds the 

recommended maximum a flue draught stabiliser  (or flue damper 

as it is also known) must be fitted so the rate of burning can be 

controlled and prevent overfiring.

Flue Damper (Not Supplied)

When burning wood, a flue damper may be fitted to reduce the 

draught through the stove if the draught is too high. When the 

damper is set in the open position the chimney draws at full 

draught, increasing the volume of air flow through the stove and 

flue. Shutting the damper restricts the flow, slowing the rate of 

burning. The damper should be fitted to the stove flue and should 

be the same size as the flue pipe. As a rule it should be fitted no 

closer than 700mm from the flue outlet of the appliance.

A flue damper should not be fitted when burning solid fuels 

other than wood.

Room Ventilation

For safe operation this stove must be provided with combustion 

air supply in addition to normal room ventilation, in accordance 

with Building Regulations. Minimum ventilation requirements vary 

depending on whether the dwelling is considered to be of standard 

construction or of airtight construction, or if a flue draught stabiliser 

has been fitted. The required open air vent sizes are as follows:

Table 4 - Additional Room Ventilation Required

Standard build dwellings {air permeability >5.0m³ /(h.m²)}
No Flue Stabiliser

No additional vent required

With Flue Stabiliser

15 cm²

Airtight build dwellings {air permeability ≤5.0m³ /(h.m²)}
No Flue Stabiliser

27 cm²

With Flue Stabiliser

42 cm²

The stove may be connected to a dedicated combustion air supply 

using the air duct at the rear of the stove 

(see ‘X’ Fig 4)

. Connection 

can be made to an external wall vent using standard 4” flexible 

aluminium ducting. Plastic ducting must not be used.

An extractor fan must not be used in the same room as this 

appliance.

- 6 -

Floor Protection & Installation Clearances

In all instances the stove must be positioned on a non-combustible 

hearth that conforms to Building Regulations and is firm, secure 

and  capable  of  supporting  the  stove.  Care  should  be  taken  to 

ensure the stove is level.
The stove can be installed in suitably sized recess, either purpose 

built or an existing fireplace. In this instance  Building Regulations 

require that a solid constructional hearth of minimum 125mm must 

be used, including the thickness of the floor and any decorative 

top surface (e.g. tiling). We recommend a minimum air circulation 

space of at least 150mm around the sides and rear and 300mm 

above the top to obtain maximum heat output and for access to 

the rear of the stove. 
Building regulations stipulate minimum wall clearances for stoves 

from adjacent walls and constructional hearth 

(Table 3 & Fig 5)

The stove can also be installed freestanding in the room. In this 

instance a reduced thickness hearth may be used, which must 

be made from non-combustible board, sheet or tiles of minimum 

thickness12mm. 

(Fig 6)

 shows the minimum distances required 

from the hearth edge to the sides of the stove.

In all cases allow an apron of at least 300mm at the front of the 

stove in case of spills when de-ashing. 

Table 5

  shows  the  minimum  safe  distances  to  combustable 

materials  which  must  be  observed  in  all  installations. Any 

surrounding combustible material should not exceed 80°C. 

Table 5

Sides

Rear

Bellingham 5kW

500mm

250mm

Existing Fireplace

An existing fireplace opening can be bricked up or sealed with a 

register plate, 2.5mm sheet steel or concrete. A short length of 

flue pipe may then be used to connect the stove to the chimney. 

Ideally the old fireplace should be filled in so that there is a smooth 

streamlined entry into the flueway. 

(Fig 8)

Typical installation for Inglenook Fireplaces

Inglenook fireplaces can have very large bore chimneys 

(Fig 9)

Check with your installer – you may need a stainless steel flexible 

flue liner for solid fuel fitting. 

Commissioning

Upon completion of installation, the stove and flue system should 

be tested by a suitably qualified person to make sure it is safe for 

normal use. A smoke draw test should be completed to check for 

soundness of joints and seals and also that all smoke and fumes 

are taken from the appliance up the chimney and emitted safely. 
First warm the flue with a blowlamp or similar for about 10 minutes. 

Place a lit smoke pellet on the centre of the grate with the air 

controls open. Close the door – the smoke should be drawn up the 

flue and be seen to exit from the flue terminal. Complete the test 

with all windows and doors shut in the room where the appliance 

is fitted. 
If a ceiling fan is present it must be operated on max for the duration 

of the test. If there are any extraction fans in adjacent rooms these 

too must be operated on maximum setting during the test with the 

interconnecting doors open. If any spillage occurs, recheck the 

suitability of the flue system making sure there is adequate air 

supply to the room (as per Building Regulations).  

Light the appliance and slowly increase the temperature to 

operating  levels.  Open  the  main  fire  door  when  the  appliance 

reaches normal operating condition and carry out a spillage test 

using a smoke match or pellet around the door opening. If any 

spillage occurs, open all windows, allow the fire to go out and 

recheck the flue system and ventilation.

Summary of Contents for Bellingham 12kW BLM12SE

Page 1: ...te Leave the system ready for operation and instruct the user in the correct use of the appliance and operation of controls Installation should only be carried out by a suitably qualified installer Di...

Page 2: ...n Bellingham 5kw Nominal heat output Wood kW 5 0 Solid Fuel Ancit kW 4 9 Efficiency Wood 84 8 Solid Fuel Ancit 85 0 CO Emission 13 O2 Wood 0 34 Solid Fuel Ancit 0 33 Flue Gas Temp Wood C 210 Solid Fue...

Page 3: ...ppliance 300mm or 1200mm from hearth whichever is greater 0mm 51 150mm 75mm 0 150mm 150 300mm 75mm 150mm 300mm No Minimum Requirement H MIN 150mm X X T T MIN 150mm MIN 125mm See Table 3 Solid non comb...

Page 4: ...11 9 10 8 CLOSURE PLATE SEAL 150mm max Fire proof seal or fire cement 150mm max C B A 4...

Page 5: ...suitable protective gloves when handling In case of contact wash immediately with plenty of water Asbestos This appliance contains no asbestos If there is a possibility of disturbing asbestos as a res...

Page 6: ...ame room as this appliance 6 Floor Protection Installation Clearances In all instances the stove must be positioned on a non combustible hearth that conforms to Building Regulations and is firm secure...

Page 7: ...rformance the stove should not be overfilled with fuel above the height of the rear brick ideally the top 1 height of the rear brick should be visible at all times Overfilling can cause poor operation...

Page 8: ...th a proprietary glass cleaner or some damp newspaper Do not use abrasive materials as these can scratch the glass and make subsequent cleaning more difficult Wet logs on heated glass a badly aimed po...

Page 9: ...ainer It is a condition of the guarantee that the installation complies with relevant Building Regulations and is carried out by a suitably qualified individual HETAS registered in England and Wales o...

Page 10: ...10...

Page 11: ...R HANDLE ASSEMBLY 4 19089 0 16 GRATE FRAME 1 70421 0 5 DOOR CATCH 1 70181 0 17 RIDDLE ARM 1 70422 0 6 DOOR GLASS 1 70100 0 18 AIR CONTROL HANDLE 1 71035 0 7 GLASS FIXING BKT 1 70101 0 19 LEG 1 70096 0...

Page 12: ...n SO30 2DF t 44 0 844 879 3588 f 44 0 1489 773050 e aftersales dimplex co uk w www dimplex co uk Northern Ireland Glen Dimplex Northern Ireland 5 Charlestown Avenue Charlestown Industrial Estate Craig...

Reviews: