LI 9TU - LI 12TU 

9 Maintenance / Cleaning

9.1 Maintenance

To protect the paintwork, avoid leaning or putting objects on the
device. External heat pump parts can be wiped with a damp cloth
and domestic cleaner.

NOTE

Never use cleaning agents containing sand, soda, acid or chloride as
these can damage the surfaces.

To prevent faults due to sediment in the heat exchanger of the
heat pump, ensure that the heat exchanger in the heating system
can not be contaminated. We recommend protecting the evapo-
rator by installing a bird guard in the inlet duct. At least 80 % of
the cross section of the grating should be open. In the event that
operating malfunctions due to contamination still occur, the sys-
tem should be cleaned as described below.

9.2 Cleaning the Heating System

ATTENTION!

The integrated dirt trap must be cleaned at regular intervals.

The maintenance intervals should be defined according to the
degree of soiling in the system. The filter insert should also be
cleaned.
For cleaning, the heating circuit must be made pressureless in
the vicinity of the dirt trap, the filter compartment unscrewed, and
the filter insert removed and cleaned. Assembly carried out in re-
verse order requires attention to correct assembly of the screen
inserts and tightness of the screw joints.
The ingress of oxygen into the heating water circuit may result in
the formation of oxidation products (rust), particularly if steel
components are used. These products enter the heating system
via the valves, the circulating pumps and/or plastic pipes. It is
therefore essential - in particular with respect to the piping of un-
derfloor heating systems - that only diffusion-proof materials are
used.

NOTE

We recommend the installation of a suitable corrosion protection system
to prevent the formation of deposits (e.g. rust) in the condenser of the
heat pump.

Residue from lubricants and sealants may also contaminate the
heating water.
In the case of severe contamination leading to a reduction in the
performance of the liquifier in the heat pump, the system must be
cleaned by a heating technician.
Based on current information, we recommend using a 5 % phos-
phoric acid solution for cleaning purposes. However, if cleaning
needs to be performed more frequently, a 5 % formic acid solu-
tion should be used.
In either case, the cleaning fluid should be at room temperature.
We recommend flushing the heat exchanger in the direction op-
posite to the normal flow direction.
To prevent acidic cleaning agents from entering the heating sys-
tem circuit, we recommend connecting the flushing device di-
rectly to the flow and return flow of the liquifier of the heat pump.

It is important that the system be thoroughly flushed using appro-
priate neutralising agents to prevent any damage from being
caused by cleaning agent residue remaining in the system.
Acids must be used with great care and all relevant regulations of
the employers' liability insurance associations must be adhered
to.
The manufacturer's instructions regarding cleaning agent must
be complied with at all times.

9.3 Cleaning the Air System

Air ducts, evaporator, ventilator and condensate outflow should
be cleaned of contamination (leaves, twigs, etc.) before the heat-
ing period. Do this by opening the front of the heat pump. To do
this, the heat pump must be opened at the side. The bottom sec-
tion should be opened first, followed by the top section.

ATTENTION!

Before opening the device, ensure that all circuits are isolated from the
power supply.

Remove and rehang the side panel assemblies as described in
Chapter 4.
To prevent the evaporator and the condensate tray from being
damaged, do not use hard or sharp objects for cleaning.

10 Faults / Trouble-

Shooting

This heat pump is a quality product and is designed for trouble-
free operation.  In the event that a fault should occur, it will be
shown on the heat pump manager display. Simply consult the
Faults and Trouble-shooting page in the operating instructions of
the heat pump manager. If you cannot correct the fault yourself,
please contact your after-sales service technician.

ATTENTION!

Any work on the heat pump may only be performed by authorised and
qualified after-sales service technicians. 

11 Decommissioning/

Disposal

Before removing the heat pump, disconnect it from the power
source and close all valves. The deinstallation of the heat pump
must be performed by technical personnel. Observe all environ-
mentally-relevant requirements regarding the recovery, recycling
and disposal of materials and components in accordance with all
applicable standards. Particular attention should be paid to the
proper disposal of refrigerants and refrigeration oils.

Summary of Contents for 452160.66.52

Page 1: ...Pump for Indoor Installation Pompe chaleur air eau pour installation int rieure Montage und Gebrauchsanweisung Deutsch English Fran ais Instructions d installation et d utilisation Installation and Op...

Page 2: ......

Page 3: ...ung DE 5 6 3 Schall DE 5 7 Montage DE 6 7 1 Allgemein DE 6 7 2 Luftanschluss DE 6 7 3 Heizungsseitiger Anschluss DE 7 7 4 Temperaturf hler DE 7 7 5 Elektrischer Anschluss DE 9 8 Inbetriebnahme DE 10 8...

Page 4: ...Wohneinrichtungen vor gesehen Bei der Konstruktion und Ausf hrung der W rmepumpe wurden alle entsprechenden EG Richtlinien DIN und VDE Vorschriften eingehalten siehe CE Konformit tserkl rung Beim elek...

Page 5: ...eau anzuheben Da die der Luft entzogene Energie auf das Heizwasser bertragen wird bezeichnet man dieses Ger t als Luft Wasser W rmepumpe Die Luft Wasser W rmepumpe besteht aus den Hauptbauteilen Verda...

Page 6: ...zubeh r mit Westernstecker RJ 12 HINWEIS Bei Heizungsreglern mit abnehmbarem Bedienteil kann dieses direkt als Fernbedienstation genutzt werden 4 2 Geb udeleittechnik Der W rmepumpenmanager kann durch...

Page 7: ...hl sse der W rmepumpe eingehalten wird Die Seitenteile d rfen nicht durch Anschlussleitungen verdeckt sein Im Aufstellraum d rfen zu keiner Jahreszeit Frost oder h here Temperaturen als 35 C auftreten...

Page 8: ...Luftkanal ver wendet ist drauf zu achten dass die innere Querschnittsfl che von Luftansaug und Luftausblasseite durch den Luftkanal nicht verringert wird F r die Abdichtung zur W rmepumpe k nnen die...

Page 9: ...urchsatz der W rmepumpe ist in jedem Betriebszustand der Heizungsanlage sicherzustellen Dieses kann z B durch Installation eines doppelt differenzdrucklosen Verteilers oder eines berstr mventiles erre...

Page 10: ...tzt werden Montage als Rohranlagef hler Heizungsrohr von Lack Rost und Zunder s ubern Gereinigte Fl che mit W rmeleitpaste bestreichen d nn auftragen F hler mit Schlauchschelle befestigen gut festzieh...

Page 11: ...teckerklemme X3 A1 geschleift VORSICHT Kleinspannung 4 Das Sch tz K20 f r den Tauchheizk rper E10 ist bei mo noenergetischen Anlagen 2 WE entsprechend der Heiz k rperleistung auszulegen und bauseits b...

Page 12: ...er S d und West seite Mindestens ein Heizkreis muss ge ffnet bleiben z B Bad Das berstr mventil ist so weit zu ffnen dass sich bei der aktu ellen W rmequellentemperatur die in der nachstehenden Ta bel...

Page 13: ...reinigt wer den muss mit einer 5 igen Ameisens ure durchzuf hren In beiden F llen sollte die Reinigungsfl ssigkeit Raumtempera tur haben Es ist empfehlenswert den W rmetauscher entgegen der normalen D...

Page 14: ...llmengen 5 1 Ger teabmessungen 3 H x B x T mm 1560 x 960 x 780 1560 x 960 x 780 5 2 Gewicht der Transporteinheit en incl Verpackung kg 256 270 5 3 Ger teanschl sse f r Heizung Zoll G 1 1 4 G 1 1 4 5 4...

Page 15: ...dem Betriebsger usch der W rmepumpe im Heizbetrieb bei 35 C Vorlauftemperatur Der angegebene Schalldruckpegel stellt den Freifeldpegel dar Je nach Aufstellungsort kann der Messwert um bis zu 16 dB A...

Page 16: ...ieferer bezogene Teile und Ger te Anlagenm ngel die auf nicht vom Lieferer bezogene Teile zur ckzu f hren sind fallen nicht unter den Garantieanspruch Bei endg ltig fehlgeschlagener Nachbesserung wird...

Page 17: ...ed Water Pipe EN 5 6 3 Sound EN 5 7 Installation EN 6 7 1 General Information EN 6 7 2 Air Connection EN 6 7 3 Heating System Connection EN 7 7 4 Temperature sensor EN 7 7 5 Electrical connection EN 9...

Page 18: ...uest houses and similar other residential buildings The construction and design of the heat pump complies with all relevant EU directives DIN VDE regulations see CE declaration of conformity When conn...

Page 19: ...the air is transferred to the heating water this type of device is called an air to water heat pump The air to water heat pump consists of the main components evaporator ventilator and expansion valv...

Page 20: ...on takes place via an inter face special accessories with RJ 12 Western plug NOTE In the case of heating controllers with a removable operating element this can also be used directly as a remote contr...

Page 21: ...es Neither frost nor temperatures higher than 35 C must occur in the installation location at any time of the year Never install the device in rooms subject to high humidity Con densation can form on...

Page 22: ...is being used to that which has been sup plied as an accessory care must be taken to ensure that it does not reduce the cross sectional area of the air intake and air outlet sides The small and large...

Page 23: ...t be assured in all operating states of the heating system This can be accomplished for example by installing either a dual differential pressureless manifold or an overflow valve The pro cedure for s...

Page 24: ...nifold Mounting as a pipe mounted sensor Remove paint rust and scale from heating pipe Coat the cleaned surface with heat transfer compound apply sparingly Attach the sensor with a hose clip tighten f...

Page 25: ...it should be tapped upstream from the utility blocking contac tor or be connected to the household current as important protection functions could otherwise be lost during a utility block 3 The utili...

Page 26: ...an lead to faulty operation and increased energy consumption We recom mend carrying out the following procedure to correctly adjust the overflow valve Close all of the heating circuits that may also b...

Page 27: ...needs to be performed more frequently a 5 formic acid solu tion should be used In either case the cleaning fluid should be at room temperature We recommend flushing the heat exchanger in the direction...

Page 28: ...dimensions 3 H x W x L mm 1560 x 960 x 780 1560 x 960 x 780 5 2 Weight of the transportable unit s incl packaging kg 256 270 5 3 Device connections for heating system Inches G 1 1 4 G 1 1 4 5 4 Air d...

Page 29: ...on with a flow temperature of 35 C The specified sound pressure level represents the free sound area level The measured value can deviate by up to 16 dB A depending on the installation location 3 Plea...

Page 30: ...EN 14 452160 66 52 FD 9506 www dimplex de English LI 9TU LI 12TU...

Page 31: ...6 6 2 Ecoulement des condensats FR 6 6 3 Bruit FR 6 7 Installation FR 7 7 1 Remarques d ordre g n ral FR 7 7 2 Prise d air FR 7 7 3 Raccordement c t chauffage FR 8 7 4 Sonde de temp rature FR 8 7 5 B...

Page 32: ...omme non conforme La documentation accompagnant les projets doit galement tre prise en compte Toute modifica tion ou transformation de l appareil est proscrire 1 3 Dispositions l gales et directives C...

Page 33: ...de la construction le besoin accru en chaleur devra donc tre assur par des appareils sp ciaux c t construction Lors d un s chage de la construction en automne ou en hiver nous vous recommandons d inst...

Page 34: ...cteurs de puissance l unit de d mar rage progressif et le gestionnaire de pompe chaleur Le gestionnaire de pompe chaleur est un appareil de com mande et de r gulation lectronique facile utiliser Il co...

Page 35: ...soit le sens Le transport vers l emplacement d finitif devrait s effectuer l aide d une palette L appareil de base propose plusieurs possi bilit s de transport avec un chariot l vateur un diable ou l...

Page 36: ...s raccords d eau de chauffage de la pompe chaleur La pi ce d installation ne doit jamais tre expos e au gel ou des temp ratures sup rieures 35 C L appareil ne devrait jamais tre install dans des pi ce...

Page 37: ...e bonne qualit Si une gaine d air diff rente de celle disponible comme acces soire est utilis e veiller ce que le diam tre int rieur c t aspi ration et vacuation de l air ne soit pas r duit par la gai...

Page 38: ...it tre garanti dans la pompe chaleur quel que soit l tat de fonctionnement de l ins tallation de chauffage C est tout fait r alisable en montant un distributeur double sans pression diff rentielle ou...

Page 39: ...les tuyauteries Nettoyer les tuyaux de chauffage des restes de peinture liminer la rouille et les taches d oxydation Enduire les surfaces nettoy es de p te thermoconductrice appliquer en fine couche L...

Page 40: ...u relier au courant domestique Certaines fonctions de protection essentielles seraient sinon hors ser vice lors des dur es de blocage 3 Le contacteur de blocage de la soci t d lectricit K22 avec 3 con...

Page 41: ...rreur et une augmentation du besoin en nergie lec trique Pour r gler la soupape diff rentielle correctement nous vous conseillons de proc der de la mani re suivante Fermez tous les circuits de chauffa...

Page 42: ...ons de pro c der au nettoyage avec de l acide phosphorique 5 ou si le nettoyage doit avoir lieu plus souvent avec de l acide formique 5 Dans les deux cas le liquide de nettoyage doit tre la temp ra tu...

Page 43: ...m 1560 x 960 x 780 1560 x 960 x 780 5 2 Poids de des unit s de transport emballage compris kg 256 270 5 3 Raccordements de l appareil de chauffage pouces filet 1 1 4 filet 1 1 4 5 4 Raccordement la ga...

Page 44: ...ode chauffage une temp rature d part de 35 C Le niveau de pression sonore indiqu est celui d une propagation de champ libre Selon le lieu d installation la valeur mesur e peut varier de 16 dB A max 3...

Page 45: ...Circuit Diagrams Sch mas lectriques A VII 3 1 Steuerung Control Commande A VII 3 2 Steuerung Control Commande A VIII 3 3 Last Load Charge A IX 3 4 Anschlussplan Circuit Diagram Sch ma lectrique A X 3...

Page 46: ...QJ ZDWHU IORZ HDW SXPS RXWOHW H WHUQDO WKUHDG HDWLQJ ZDWHU UHWXUQ IORZ HDW SXPS LQOHW H WHUQDO WKUHDG IHHGWKURXJK RQGHQVDWH IHHGWKURXJK RQGHQVDWH OOHU HDX GH FKDXIIDJH 6RUWLH GH OD 3 LOHWDJH H WpULHXU...

Page 47: ...FHVVRU DLQH G DLU GLVSRQLEOH FRPPH DFFHVVRLUH 8PODXIHQGH EVFKUlJXQJ XU EGLFKWXQJ GHU 6WR NDQWH XQG 9HUEHVVHUXQJ GHU XIWI KUXQJ HYHO RQ DOO VLGHV IRU VHDOLQJ WKH HGJHV DQG LPSURYLQJ WKH DLU FLUFXLW LVH...

Page 48: ...ORVV LQ 3D 3HUWH GH SUHVVLRQ HQ 3D HLVWXQJVDXIQDKPH LQ N LQFO 3XPSHQOHLVWXQJVDQWHLO 3RZHU FRQVXPSWLRQ LQ N LQFO SRZHU LQSXW WR SXPS RQVRPPDWLRQ GH SXLVVDQFH HQ N FRPSULV SDUW GH FRQVRPPDWLRQ GH OD SR...

Page 49: ...H GH SUHVVLRQ HQ 3D HLVWXQJVDXIQDKPH LQ N LQFO 3XPSHQOHLVWXQJVDQWHLO 3RZHU FRQVXPSWLRQ LQ N LQFO SRZHU LQSXW WR SXPS RQVRPPDWLRQ GH SXLVVDQFH HQ N FRPSULV SDUW GH FRQVRPPDWLRQ GH OD SRPSH 9HUIO VVLJHU...

Page 50: ...W rmequelleneintrittstemperatur C Heat source temperature inlet C Temp rature d entr e de la source de chaleur C Wasseraustritt 2 K Water outlet 2 K Sortie d eau 2 K Wassereintritt Water inlet Entr e...

Page 51: ...www dimplex de 452160 66 52 FD 9506 A VII Anhang Appendix Annexes LI 9TU LI 12TU 3 Stromlaufpl ne Circuit Diagrams Sch mas lectriques 3 1 Steuerung Control Commande...

Page 52: ...A VIII 452160 66 52 FD 9506 www dimplex de Anhang Appendix Annexes LI 9TU LI 12TU 3 2 Steuerung Control Commande...

Page 53: ...www dimplex de 452160 66 52 FD 9506 A IX Anhang Appendix Annexes LI 9TU LI 12TU 3 3 Last Load Charge...

Page 54: ...A X 452160 66 52 FD 9506 www dimplex de Anhang Appendix Annexes LI 9TU LI 12TU 3 4 Anschlussplan Circuit Diagram Sch ma lectrique...

Page 55: ...www dimplex de 452160 66 52 FD 9506 A XI Anhang Appendix Annexes LI 9TU LI 12TU 3 5 Anschlussplan Circuit Diagram Sch ma lectrique...

Page 56: ...s Sorties analogiques J7 8 Digitaleing nge Digital inputs Entr es num riques J10 Bedienteil Control panel Unit de commande J11 frei free libre J12 J18 230V AC Ausg nge 230V AC outputs 230V AC outputs...

Page 57: ...25 V AC X5 1 Busverteilerklemme u a f r N24 Bus distribution terminal for N24 etc R glettes bus pour N24 entre autres Y1 4 Wege Umschaltventil Four way valve Vanne d inversion 4 voies Bauteile sind ba...

Page 58: ...tion diagram Sch ma d int gration hydraulique 4 1 Monoenergetische Anlage mit einem Heizkreis und Warmwasserbereitung Mono energy system with one heating circuit and domestic hot water preparation Ins...

Page 59: ...W rmepumpenmanager Heat pump manager Gestionnaire de pompe chaleur Reihen Pufferspeicher Buffer tank connected in series Ballon tampon en s rie Warmwasserspeicher Hot water cylinder Ballon d eau chau...

Page 60: ...Typ LI 9TU Type s LI 12TU Type s EG Richtlinien Niederspannungsrichtlinie 2006 95 EG EMV Richtlinie 2004 108 EG Druckger terichtlinie 97 23 EG EC Directives Low voltage directive 2006 95 EC EMC direc...

Page 61: ...www dimplex de 452160 66 52 FD 9506 A XVII Anhang Appendix Annexes LI 9TU LI 12TU...

Page 62: ...A XVIII 452160 66 52 FD 9506 www dimplex de Anhang Appendix Annexes LI 9TU LI 12TU...

Page 63: ...www dimplex de 452160 66 52 FD 9506 A XIX Anhang Appendix Annexes LI 9TU LI 12TU...

Page 64: ...schland GmbH Gesch ftsbereich Dimplex Am Goldenen Feld 18 D 95326 Kulmbach Irrt mer und nderungen vorbehalten Subject to alterations and errors Sous r serve d erreurs et modifications 49 0 9221 709 56...

Reviews: