CONNECTION OF THE GENERATOR AND ATS 

TO THE BUILDING POWER SUPPLY NETWORK

8

Img. 3

ELECTRICAL

SUPPLY NETWORK

ELECTRICAL 

COUNTER

ATS

GENERATOR 

WITH ATSR

ELECTRICITY CONSUMERS

Opening of ATS unit and its connection to the mains must 

be carried out only by qualified specialist. The product is

under tension.

WARNING — DANGER!

The ATS unit may only be tampered with and connected 

by a qualified technician. The product is live.

WARNING — DANGER!

Open the ATS unit door. Inside you will see the connection terminals. Connect the ATS unit as shown in Figs. 

3-6 and according to the diagrams in the Appendix.

WIRING DIAGRAMS

9

Connect the ATS to the generator using the generator 

automatic start control cable (supplied as a set with 

ATS)

To start the generator in automatic mode, the start key on 

the generator’s control panel must be in the OFF position. 

The ATS contact socket is located on the control panel 

of the generator.

www.ks-power.de/en   

|

   

6

Summary of Contents for Konner & Sohnen 4260405362066

Page 1: ...Please read this manual carefully before use Manual KS ATS 3 18 HD KS ATS 1 40 HD KS ATS 4 63 HD AUTOMATIC TRANSFER SWITCH ATS EN...

Page 2: ...t allow moisture to enter the product as this increases the risk of electric shock Avoid direct contact with grounded surfaces pipes radiators etc Be careful when working with the power cord Replace i...

Page 3: ...trol cable length m 4 4 Dimensions mm 300 400 200 Net gross weight kg 5 7 6 1 6 1 6 5 Model KS ATS 4 63 HD Battery voltage DC8 0 18 V Power consumption 10 W Voltage 230V 400V Power 230 V kW 14 4 28 8...

Page 4: ...p power source generator In case of unsuccessful startup the ATS system attempts to start the generator three times with an interval of 6 seconds between the attempts If all three attempts are unsucce...

Page 5: ...or glows steadily when power consumers are connected Connection error indicator flashes 4 times per second and emits a beep when cables or connections are damaged Power indicator lights up when there...

Page 6: ...ime can be adjusted from 3 to 21 seconds Engine start delay time following deenergization of the main power supply factory set to 12 seconds LH Generator warm up time before connecting the load factor...

Page 7: ...nnected by a qualified technician The product is live WARNING DANGER Open the ATS unit door Inside you will see the connection terminals Connect the ATS unit as shown in Figs 3 6 and according to the...

Page 8: ...pendix ITY terminals for the main power supply A Phase 1 B Phase 2 C Phase 3 N NEUTRAL OUTPUT terminals for home or other power consumers L1 Phase 1 L2 Phase 2 L3 Phase 3 N NEUTRAL GENERATOR terminals...

Page 9: ...s indicated by melting or discoloration of parts due to the effect of high temperature score marks on the cylinder or piston surfaces destruction of connecting rod inserts or piston rings In addition...

Page 10: ...www ks power de en 9 1 2 KS ATS 3 18 HD A B C N L1 L2 L3 N U V W N CITY OUTPUT GENERATOR ANNEX...

Page 11: ...www ks power de en 10 L N L N L N CITY OUTPUT GENERATOR 3 4 KS ATS 1 40 HD...

Page 12: ...www ks power de en 12 KS ATS 4 63 HD 5 6 A B C N A B C N A B C N CITY POWER LOAD GENERATOR...