With the engine off, press and hold down the button   

   for 3 seconds to switch the controller to the 

setup mode. To select the setting, briefly press the 

 

   button. The parameters are changed cyclically. 

Number

Color

Connection function

1

Red

+12V

2

Yellow

Starter

3

Green

~24V

4

Blue

Fuel valve

5

Black

-12V

The timing of these parameters can be set to 3, 6, 12, 24 or 48 seconds. Select the required parameter, 
press   

 

 to increase or   

 

  to decrease the value.

Starter operation time (can be adjusted from 3 to 21 seconds).

Engine start delay time following deenergization of the main power supply 

(factory set to 12 seconds).

(LH) Generator warm-up time before connecting the load (factory set to 6 seconds).

Engine preheat time (factory set to 6 seconds). (The generator must be equipped 

with an engine preheating system). (The ATS models do not have this function).

Delay time during which the ATS unit will switch over power consumers to the main power 

supply upon restoration of the power supply (factory set to 6 seconds).

CONTROLLER SETTINGS

7

  

  PARAMETERS:

PARAMETERS:

  

  ATS CONNECTOR AND ITS CONNECTION

ATS CONNECTOR AND ITS CONNECTION

www.ks-power.de/en   

|

   

5

Summary of Contents for Konner & Sohnen 4260405362066

Page 1: ...Please read this manual carefully before use Manual KS ATS 3 18 HD KS ATS 1 40 HD KS ATS 4 63 HD AUTOMATIC TRANSFER SWITCH ATS EN...

Page 2: ...t allow moisture to enter the product as this increases the risk of electric shock Avoid direct contact with grounded surfaces pipes radiators etc Be careful when working with the power cord Replace i...

Page 3: ...trol cable length m 4 4 Dimensions mm 300 400 200 Net gross weight kg 5 7 6 1 6 1 6 5 Model KS ATS 4 63 HD Battery voltage DC8 0 18 V Power consumption 10 W Voltage 230V 400V Power 230 V kW 14 4 28 8...

Page 4: ...p power source generator In case of unsuccessful startup the ATS system attempts to start the generator three times with an interval of 6 seconds between the attempts If all three attempts are unsucce...

Page 5: ...or glows steadily when power consumers are connected Connection error indicator flashes 4 times per second and emits a beep when cables or connections are damaged Power indicator lights up when there...

Page 6: ...ime can be adjusted from 3 to 21 seconds Engine start delay time following deenergization of the main power supply factory set to 12 seconds LH Generator warm up time before connecting the load factor...

Page 7: ...nnected by a qualified technician The product is live WARNING DANGER Open the ATS unit door Inside you will see the connection terminals Connect the ATS unit as shown in Figs 3 6 and according to the...

Page 8: ...pendix ITY terminals for the main power supply A Phase 1 B Phase 2 C Phase 3 N NEUTRAL OUTPUT terminals for home or other power consumers L1 Phase 1 L2 Phase 2 L3 Phase 3 N NEUTRAL GENERATOR terminals...

Page 9: ...s indicated by melting or discoloration of parts due to the effect of high temperature score marks on the cylinder or piston surfaces destruction of connecting rod inserts or piston rings In addition...

Page 10: ...www ks power de en 9 1 2 KS ATS 3 18 HD A B C N L1 L2 L3 N U V W N CITY OUTPUT GENERATOR ANNEX...

Page 11: ...www ks power de en 10 L N L N L N CITY OUTPUT GENERATOR 3 4 KS ATS 1 40 HD...

Page 12: ...www ks power de en 12 KS ATS 4 63 HD 5 6 A B C N A B C N A B C N CITY POWER LOAD GENERATOR...

Page 13: ......

Page 14: ...Deutschland Hauptstr 134 51143 K ln www ks power de info dimaxgroup de Polska DIMAX International Poland Sp z o o Polen Warczawska 306B 05 082 Stare Babice www ks power pl info pl dimaxgroup de 47 02...

Reviews: